Tyco DN40 User manual

General
Description
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic
Actuation (Fig. 1) is designed for use
in applications, such as refrigerated
areas, requiring the maximum degree
of protection against inadvertent flood-
ing of the sprinkler system piping.
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic
Actuation utilizes a Model DV-5 Deluge
Valve and a Riser Check Valve. The
Riser Check Valve (that does not re-
quire the use of priming water) isolates
the Deluge Valve from the system air
pressure. The releasing trim for the
Deluge Valve utilizes a Solenoid Valve
and a Dry Pilot Actuator in a series
configuration. The system air pressure
holds the Dry Plot Actuator closed,
whereas the Solenoid Valve remains
closed until it is electrically energized
by a Deluge Valve Releasing Panel
(automatic control unit). The Releas-
ing Panel is operated by either a fire
detection device or manual electric
pull station.
In order for the Double Interlock Pre-
action System to automatically actu-
ate, two independent events must oc-
cur. The deluge valve releasing panel
must operate and open the Solenoid
Valve upon automatic operation of the
electric fire detection initiating circuit
or manual operation of the electric-
manual pull initiating circuit, and the
sprinkler system piping must lose air
pressure due to operation of one or
more sprinklers.
The Double Interlock Preaction Sys-
tem will automatically actuate only
when both the Dry Pilot Actuator and
the Solenoid Valve are open at the
same time. Accidental opening of just
the Dry Pilot Actuator (for example: a
lift truck accidentally dislodges a sprin-
kler), or just energizing the Solenoid
Valve (for example: an accidental op-
eration of an electric pull station), will
only cause an alarm, and will not actu-
ate the system or flood the sprinkler
system piping.
The Model DV-5 Deluge Valve (de-
scribed in Technical Data Sheet
TFP1305) is a diaphragm style valve
that depends upon water pressure in
the Diaphragm Chamber to hold the
Diaphragm closed against the water
supply pressure. When the DV-5 Valve
is set for service, the Diaphragm
Chamber is pressurized through the
trim connections from the inlet side of
the system’s main control valve, for
example an O.S.&Y. gate valve or but-
terfly valve (Fig. 1).
Operation of the Solenoid Valve and
Dry Pilot Actuator at the same time
releases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2 mm)
Priming Supply Restriction (Item 7 -
Fig. 2A) in the diaphragm supply con-
nections. This results in a rapid pres-
sure drop in the Diaphragm Chamber
below the valve trip point. The water
supply pressure then forces the Dia-
phragm open permitting water to flow
Page 1 of 16 TFP1460
MARCH, 2005
Preaction System with Model DV-5 Deluge Valve
Double Interlock — Electric/Pneumatic Actuation
1-1/2 thru 8 Inch (DN40 and DN200)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
(TEXT CONTINUED ON PAGE 9)

Page2of16 TFP1460
FIGURE 1 — PART 1 OF 2
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
— SYSTEM SCHEMATIC (Front View)—
Model DV-5 Deluge Valve
Main Control Valve (N.O.)
1
2
-
-
Diaphragm Chamber Supply3-
Local Manual Control Station4-
Automatic Sprinklers5-
Heat Detectors, Smoke Detectors,6 -
Water Supply Pressure Gauge7-
Diaphragm Chamber Pressure8-
Control Valve (N.O.)
13
7
3
1
2
4
11 21
Gauge
etc. (Fire Detection)
14
5
15
System Drain Valve (N.C.)9-
Main Drain Valve (N.C.)10 -
Fail-Safe Valve11 -
Waterflow Pressure Alarm Switch12 -
Water Motor Alarm (Optional)13 -
Solenoid Valve14 -
Deluge Valve Releasing Panel15 -
(Shown at Rear of Valve)
(Shown at Rear of Valve)
Riser Check Valve16 -
System Shut-Off Valve (N.O.)17 -
Air Pressure Gauge18 -
Automatic Air/Nitrogen Supply19 -
Low Pressure Alarm Switch20 -
5
17
19
9
20
18
16
Dry Pilot Actuator21 -
8
6

Page 3 of 16
TFP1460
FIGURE 1 — PART 2 OF 2
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
— SYSTEM SCHEMATIC (Rear View)—
Model DV-5 Deluge Valve
Main Control Valve (N.O.)
1
2
-
-
Diaphragm Chamber Supply3-
Local Manual Control Station4-
Automatic Sprinklers5-
Heat Detectors, Smoke Detectors,6 -
Water Supply Pressure Gauge7-
Diaphragm Chamber Pressure8-
Control Valve (N.O.) Gauge (Shown at Front of Valve)
etc. (Fire Detection)
System Drain Valve (N.C.)9-
Main Drain Valve (N.C.)10 -
Fail-Safe Valve11 -
Waterflow Pressure Alarm Switch12 -
Water Motor Alarm (Optional)13 -
Solenoid Valve14 -
Deluge Valve Releasing Panel15 -
(Shown at Front of Valve)
Riser Check Valve16 -
System Shut-Off Valve (N.O.)17 -
Air Pressure Gauge18 -
Automatic Air/Nitrogen Supply19 -
Low Pressure Alarm Switch20 -
1
2
10
12
6
15
5
5
(Shown at Front of Valve)
19
13
20 17
9
(Shown at Front of Valve)
(Shown at Front of Valve)
Dry Pilot Actuator21 -
16
14
21
(Shown at Front of Valve)

Page4of16 TFP1460
FIGURE 2A — PART 1 OF 3
1-1/2 and 2 INCH (DN40 and DN50) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-127)
— EXPLODED VIEW —
with Electric/Pneumatic
Release is comprised
of Items 1-46 plus Items
Supervised Double1.
NOTES:
Interlock Preaction Trim
P1-P28.
See Figure 2 of TFP1305 for
Deluge Valve Port identification.
5.
Item 15.
Route all Tubing to Drip Funnel,6.
2.
All Fittings and Nipples are
galvanized (Standard Order).
CH: Common Hardware.
3.
4.
NOTES:
35
37
38
28
3/4" x 1/2" x 3/4" Tee
29
NO. QTY.DESCRIPTION P/N
39
40
42
45
46
27
1/2" Tee 2 CH..............
1/4" 90° Elbow 1......... CH
1/2" 90° Elbow 7......... CH
NO. QTY.DESCRIPTION P/N
1/2" x 1/4" x 1/2" Tee
44
34
3CH....
2CH....
36
3/4" Tee 1 CH..............
41
43
3/4" x 1/2" 90° Elbow 1.... CH
33
32
31
1/2" Cross 1 CH............
3/4" 90° Elbow 1......... CH
1/4" x Close Nipple 2 CH.....
1/2" x Close Nipple 2 CH.....
1/2" x 1-1/2" Nipple 11 CH.....
1/2" x 2-1/2" Nipple
3/4" x 1-1/2" Nipple
2CH.....
1/2" x 7" Nipple 1 CH........
6CH.....
3/4" x 2" Nipple 1 CH........
3/4" x 4" Nipple 1 CH........
1/2" x 2" Nipple 2 CH........
1/2" x 5" Nipple 1 CH........
46-005-1-002P2 1/4" Gauge Test Valve 1..
92-343-1-012
250 psi/ 1750 kPa
1Air Pressure Gauge . . . . .
P4
P3 Model DP-1 Dry Pilot
Actuator 52-280-1-0011..............
P6 1/4" Pressure Relief
Valve 92-343-1-0201................
P7 1/2" Swing Check Valve 46-049-1-0041.
46-047-1-004P8 1/2" Globe Valve 1.......
Ordered
Separately
Solenoid Valve Per Data
1Sheet TFP2180 . . . . . . . .
P9
1/4" Plug 3............. CH
P16
P14
P13 1/2" Union 2............ CH
1/2" 90° Elbow 4......... CH
1/2" x 1/4" x 1/2" Tee 1 CH....P17
1/2" Cross 1............ CH
1/2" x 1/2" x 1/4" Tee 1 CH....
P15
P25
P26
1/2" x 9" Nipple 1 CH........
P12
1/2" 45° Elbow 1......... CH
P11
P24
1/4" x Close Nipple 1 CH.....
1/2" x Close Nipple 2 CH.....
1/2" x 1-1/2" Nipple 8 CH
P18
.....
P21
P22
P23
P19
1/2" x 2" Nipple 2 CH........
P20
1/2" Tubing Connector CH1..
1/2" x 24" Tubing CH1.......
P10
Select Nipple per Table 1 CH..
P27
1CH
P28
Select Nipple per Table . .
Low Air Pressure
Alarm Switch (PS40-2A) 25731.
P5
46-048-1-0053/4" Angle Valve 1.......
1" x 3/4" x 1/2" Tee 1 CH.....
1" x 2" Nipple 1 CH..........
3/4" x 1-1/2" Nipple 1 CH.....
46-005-1-0022 1/4" Gauge Test Valve 1..
3 Model MC-1 Manual
Control Station 52-289-2-0011.........
4 Model AD-1 Automatic
Drain Valve 52-793-2-0041...........
20
1/2" Tubing Connector CH2..
15
92-211-1-003
92-343-1-007
16
Drip Funnel Bracket
Drip Funnel
1
1...........
....
18
92-032-1-0023/32" Vent Fitting . . . . . . . 1
19
1/4" x 18" Tubing CH1.......
10 52-353-1-0051.........1/2" Y-Strainer
9
92-322-1-002
1/2" Spring Loaded
1Check Valve . . . . . . . . . .
12
46-050-1-0041/2" Ball Valve 2.........8
46-049-1-0053/4" Swing Check Valve 1.11
13
3/4" Plug 1............. CH
24
1/4" Plug 1............. CH
1/2" x 12" Tubing CH1.......
NO.
1
QTY.DESCRIPTION P/N
92-343-1-005
300 psi/ 2000 kPa
2Water Pressure Gauge . .
22
6 Waterflow Pressure
Alarm Switch (PS10-2A) 25711.
26
1/2" Union 5............ CH
3/4" Union 1............ CH
25
92-211-1-005
Drip Funnel Connector 1
..
14
5
92-020-1-009
7 Priming Supply
1Restriction . . . . . . . . . . . .
17
21
1/2" x 18" Tubing CH1.......
23
46-048-1-0053/4" Angle Valve 1.......
P1
1/2" x 3-1/2" Nipple 1 CH.....
1/2" x 8" Nipple 1 CH........
15
14
36
44
30
13
28
4
39
36
P21
P22P10
P14
P23
P22
P24
P17
P20
P12
P2
P23
P15
SEPARATELY)
(ORDERED
P5
P1
P3
23
36
41
31
1
36
3
26
35
19
18
26
7
30
26
37
37
8
36
23
36
36
10
P21
36
20
36
26
18
42
23
35
39
29
23
26
P15
26
52-343-1-001
Fail-Safe Valve,
1Model FSV-1 . . . . . . . . . .
9
P9
P27
P26 P28
33
1
25
21
43
8
34
31
36
40
36
34
2" (DN50)
MODEL DV-5
DELUGE VALVE
SHOWN
26
223
GROOVE x GROOVE
11
44
32
44
38
27
12 46
44
31
33
22
16
(GREEN
TINT)
38
45
17
6
FOR OPTIONAL
ELECTRICALLY
CONTROL VALVE
(BVS-3/4")
LOCATION
N.O. ALARM
SUPERVISED
44
24
44
P25
P26
1/2" x 2-1/2"
1/2" x 6"
1/2" x 2"
1/2" x 5-1/2"
Select Nipple per Table 1 CH..
P19
1/2" x 1-1/2" 1/2" x 2"
30
P11
1-1/2" (DN40)
Number
43
Nipple
2" (DN50)
per DV-5 Deluge Valve Size
Select Appropriate Nipple Sizes
P22
P13
P22
P22
P16
P15
P22
P8
P4
P6
P7
5
(HEX ENDS,
"FSV-1")
P25
P15
P22
P13
P22
P18
P12
P12
UNUSED
PLUG
PORTS RISER
CHECK VALVE
(NOTE 2)
Use only the Model CV-1FR
Riser Check Valve.

FIGURE 2A — PART 2 OF 3
3 INCH (DN80) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-124)
— EXPLODED VIEW —
32
45
27
46
1
24
20
35
8
33
30
35
39
35
33
12
3" (DN80)
MODEL DV-5
DELUGE VALVE
SHOWN
25
222
43
46-005-1-0022 1/4" Gauge Test Valve 1..
3 Model MC-1 Manual
Control Station 52-289-2-0011.........
4 Model AD-1 Automatic
Drain Valve 52-793-2-0041...........
20
1/2" Tubing Connector CH2..
15
92-211-1-003
92-343-1-007
16
Drip Funnel Bracket
Drip Funnel
1
1...........
....
18
92-032-1-0023/32" Vent Fitting . . . . . . . 1
19
1/4" x 18" Tubing CH1.......
10 52-353-1-0051.........1/2" Y-Strainer
9
92-322-1-002
1/2" Spring Loaded
1Check Valve . . . . . . . . . .
12
46-050-1-0041/2" Ball Valve 2.........8
46-049-1-0053/4" Swing Check Valve 1.11
13
46-048-1-0071-1/4" Angle Valve 1......
35
1/4" x Close Nipple 2 CH.....
3/4" Plug 1............. CH
24
1/4" Plug 1............. CH
1/2" x 18" Tubing CH2.......
1/2" x Close Nipple 1 CH
37
.....
1/2" x 1-1/2" Nipple 14 CH
38
.....
28
3/4" x 1/2" x 3/4" Tee
29
NO.
1
QTY.DESCRIPTION P/N
92-343-1-005
300 psi/ 2000 kPa
2Water Pressure Gauge . .
22
6 Waterflow Pressure
Alarm Switch (PS10-2A) 25711.
39
1/2" x 2-1/2" Nipple
40
1/2" x 4" Nipple 1 CH........
42
1/2" x 5" Nipple 1 CH........
45
46
3/4" x 1-1/2" Nipple
1CH.....
1/2" x 8" Nipple 1 CH........
5CH.....
3/4" x 2" Nipple 1 CH........
1-1/4" x 2" Nipple 1 CH.......
1CH
27
1/2" Tee 2 CH..............
26
1/4" 90° Elbow 1......... CH
1/2" Union 5............ CH
3/4" Union 1............ CH
25 1/2" 90° Elbow 7......... CH
92-211-1-005
Drip Funnel Connector 1
..
14
NO. QTY.DESCRIPTION P/N NO. QTY.DESCRIPTION P/N
5 1/2" x 1/4" x 1/2" Tee
44
34
3CH....
2CH....
36
3/4" Tee 1 CH..............
GROOVE x GROOVE
43
11
31
43
43
23
40
1/2" x 3-1/2" Nipple 1 CH.....
41
1/2" x 4-1/2" Nipple 2 CH.....
43
1-1/4" x 4" Nipple . . . . . . .
30
32
21
16
(GREEN
TINT)
15
14
P12
P12
36
35
44
43
29
17
UNUSED
PLUG
PORTS
13
6
FOR OPTIONAL
ELECTRICALLY
CONTROL VALVE
(BVS-3/4")
LOCATION
N.O. ALARM
SUPERVISED
See Figure 2 of TFP1305 for
Deluge Valve Port identification.
5.
Item 15.
Route all Tubing to Drip Funnel,6.
2.
All Fittings and Nipples are
galvanized (Standard Order).
CH: Common Hardware.
3.
4.
Use only the Model CV-1FR
Riser Check Valve.
NOTES:
P19
P27
P26
P9
1-1/4" 90° Elbow 1....... CH
3/4" x 1/2" 90° Elbow 1.... CH
26
P24
46-005-1-002P2 1/4" Gauge Test Valve 1..
P1
92-343-1-012
250 psi/ 1750 kPa
1Air Pressure Gauge . . . . .
P4
P3 Model DP-1 Dry Pilot
Actuator 52-280-1-0011..............
P6 1/4" Pressure Relief
Valve 92-343-1-0201................
P7 1/2" Swing Check Valve 46-049-1-0041.
46-047-1-004P8 1/2" Globe Valve 1.......
Ordered
Separately
Solenoid Valve Per Data
1Sheet TFP2180 . . . . . . . .
P5
P9
1/4" Plug 3............. CH
P16
P14
P13 1/2" Union 2............ CH
1/2" 90° Elbow 4......... CH
1/2" x 1/4" x 1/2" Tee 1 CH....P17
1/2" Cross 1............ CH
1/2" x 1/2" x 1/4" Tee 1 CH....
P15
P25
P26
1/2" x 5" Nipple 1 CH........
P12
1/2" 45° Elbow 1......... CH
P11
P24
1/4" x Close Nipple 1 CH.....
1/2" x Close Nipple 2 CH.....
1/2" x 1-1/2" Nipple 8 CH
P18
.....
P21
P22
P23
P19
1/2" x 2" Nipple 3 CH........
P20
1/2" Tubing Connector CH1..
1/2" x 24" Tubing CH1.......
P10
1/2" x 10-1/2" Nipple 1 CH....
P27
Low Air Pressure
Alarm Switch (PS40-2A) 25731.
with Electric/Pneumatic
Release is comprised
of Items 1-46 plus Items
Supervised Double1.
NOTES:
Interlock Preaction Trim
P1-P27.
4
P23
P15
P13
P23
1-1/4" x 2" Nipple 1 CH.......
1-1/4" x 3" Nipple 1 CH.......
1-1/4" x 1-1/4" x 1/2" Tee 1 CH.
46-048-1-0071-1/4" Angle Valve 1......
P22
P22
P22
P16
P15
P22
P7
P18
P6
P8
38
92-020-1-009
7 Priming Supply
1Restriction . . . . . . . . . . . .
17
21
23
33
32
31
30
1/2" Cross 1 CH............
35
P21
P22P10
P14
P23
P22
P11
P17
P20
P12
P2
P22
P15
SEPARATELY)
(ORDERED
P5
P1
P3
22
35
41
30
1
35
3
25
34
19
18
25
7
29
25
35
37
8
35
22
35
35
52-343-1-001
Fail-Safe Valve,
1Model FSV-1 . . . . . . . . . .
10
P21
35
19
35
25
18
42
22
35
39
28
22
P25
9
25
P15
25
P13
P4
P22
1/2" x 7" Nipple 1 CH........
RISER
CHECK VALVE
(NOTE 2)
5
(HEX ENDS,
"FSV-1")
Page 5 of 16
TFP1460

FIGURE 2A — PART 3 OF 3
4, 6, and 8 INCH (DN100, DN150, and DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-121)
— EXPLODED VIEW —
28
29
21
46
11
29
49
32
49
1
24
20
41
39
8
33
28
47
35
38
16
(GREEN
TINT)
FOR OPTIONAL
ELECTRICALLY
CONTROL VALVE
(BVS-3/4")
LOCATION
N.O. ALARM
SUPERVISED
35
33
15
12
36
45
44
27
See Figure 2 of TFP1305 for
Deluge Valve Port identification.
5.
Item 15.
Route all Tubing to Drip Funnel,6.
2.
All Fittings and Nipples are
galvanized (Standard Order).
CH: Common Hardware.
3.
4.
17
35
UNUSED
PLUG
PORTS
13
P21
25
222
Use only the Model CV-1FR
Riser Check Valve.
NOTES:
48
23
31
14
P22P10
P14
P23
P15
P12
P12
P26
P22
P13
P24
P22
P16
P15
P29
P22
P29
P19
P9
P8
P27
P15
P7
P11
P25
P17
P20
P12
P2
P22
P15
SEPARATELY)
(ORDERED
P5
P1
P3
22
35
39
28
1
35
3
25
34
19
18
25
7
27
36
25
35
38
8
35
22
35
35
46-005-1-0022 1/4" Gauge Test Valve 1..
3 Model MC-1 Manual
Control Station 52-289-2-0011.........
4 Model AD-1 Automatic
Drain Valve 52-793-2-0041...........
20
1/2" Tubing Connector CH2..
15
92-211-1-003
92-343-1-007
16
Drip Funnel Bracket
Drip Funnel
1
1...........
....
17
92-032-1-0023/32" Vent Fitting . . . . . . . 1
19
1/4" x 24" Tubing CH1.......
10 52-353-1-0051.........1/2" Y-Strainer
9
92-322-1-002
1/2" Spring Loaded
1Check Valve . . . . . . . . . .
12
46-050-1-0041/2" Ball Valve 2.........8
46-049-1-0053/4" Swing Check Valve 1.11
13
46-048-1-0092" Angle Valve 1.........
2" 90° Elbow 1..........
33
CH
35
1/4" x Close Nipple 2 CH.....
3/4" Plug 1............. CH
1/4" Plug 1............. CH
1/2" x 24" Tubing CH2.......
1/2" x Close Nipple 1 CH
36
.....
1/2" x 1-1/2" Nipple 11 CH.....
31
3/4" x 1/2" x 3/4" Tee 2 CH....
32
1" x 3/4" x 1" Tee 1 CH.......
NO.
1
QTY.DESCRIPTION P/N
92-343-1-005
300 psi/ 2000 kPa
2Water Pressure Gauge . .
21
639
1/2" x 3" Nipple 1 CH........
1/2" x 5" Nipple 2 CH........
41
43
48
3/4" x 1-1/2" Nipple
1/2" x 7" Nipple 2 CH........
1CH.....
49
3/4" x 2" Nipple 1 CH........
1" x Close Nipple 2 CH.......
1" x 3" Nipple 1 CH..........
2" x 3" Nipple 2 CH..........
29
1/2" Tee 2 CH..............
25
1/4" 90° Elbow 1......... CH
1/2" Union 5............ CH
24
1" Union 1.............. CH
27
1/2" 90° Elbow 7......... CH
92-211-1-005
Drip Funnel Connector 1
..
14
5
1/2" x 1/4" x 1/2" Tee 3 CH....
40
44
28
1/2" Cross 1............ CH
30
34
37
38
1/2" x 2-1/2" Nipple 2 CH.....
42
52-343-1-001
Fail-Safe Valve,
1Model FSV-1 . . . . . . . . . .
92-020-1-009
7 Priming Supply
1Restriction . . . . . . . . . . . .
26
18
22
23
46-005-1-002P2 1/4" Gauge Test Valve 1..
P1
92-343-1-012
250 psi/ 1750 kPa
1Air Pressure Gauge . . . . .
P4
P3 Model DP-1 Dry Pilot
Actuator 52-280-1-0011..............
P6 1/4" Pressure Relief
Valve 92-343-1-0201................
P7 1/2" Swing Check Valve 46-049-1-0041.
46-047-1-004P8 1/2" Globe Valve 1.......
Ordered
Separately
Solenoid Valve Per Data
1Sheet TFP2180 . . . . . . . .
P5
NO. QTY.DESCRIPTION P/N
P9 46-048-1-0092" Angle Valve 1.........
1/4" Plug 3............. CH
P16
2" x 3" Nipple 2 CH..........
P14
P13 1/2" Union 2............ CH
1/2" 90° Elbow 4......... CH
1/2" x 1/4" x 1/2" Tee 1 CH....P17
1/2" Cross 1............ CH
1/2" x 1/2" x 1/4" Tee 1 CH....
P15
P25
P26
1/2" x 11" Nipple 1 CH.......
P12
1/2" 45° Elbow 1......... CH
P11
P24
1/4" x Close Nipple 1 CH.....
1/2" x Close Nipple 2 CH.....
1/2" x 1-1/2" Nipple 6 CH
P18
.....
P21
P22
P23
2" x 2" x 1/2" Tee 1 CH.......P19
1/2" x 2" Nipple 1 CH........
P20
1/2" x 4-1/2" Nipple 2 CH.....
1/2" Tubing Connector CH1..
1/2" x 24" Tubing CH1.......
P10
NO. QTY.DESCRIPTION P/N
P29
Select Nipple per Table 1 CH..
P27 1 CH
P28 1 CH
Select Nipple per Table . .
Select Nipple per Table . .
45
Select Nipple per Table 1 CH..
46
1CH
47
1CH
Select Nipple per Table . .
Select Nipple per Table . .
1CHSelect Nipple per Table . .
6
1" x 1/2" 90° Elbow 1 CH.....
Waterflow Pressure
Alarm Switch (PS10-2A) 25711.
P4
Low Air Pressure
Alarm Switch (PS40-2A) 25731.
37 4
30
with Electric/Pneumatic
Release is comprised
of Items 1-49 plus Items
Supervised Double1.
NOTES:
Interlock Preaction Trim
P1-P29.
P18
P6
4" (DN100)
MODEL DV-5
DELUGE VALVE
SHOWN
FLANGE x GROOVE
10
P21
35
19
35
25
18
40
22
42
43
26
P24
22
1/2" x 9" Nipple 1 CH........
25
P22
9
25
47
P13
P28
5
(HEX ENDS,
"FSV-1")
RISER
CHECK VALVE
(NOTE 2)
1/2" x 2-1/2"
1/2" x 1-1/2"
1/2" x 4"
3/4" x 2-1/2"
1/2" x 7"
1/2" x 3-1/2"
1/2" x 2"
1/2" x 5-1/2"
1/2" x 2"
1/2" x 5"
3/4" x 3-1/2"
1/2" x 5-1/2"
1/2" x 6"
1/2" x 2-1/2"
3/4" x 4-1/2"
1/2" x 2"
1/2" x 8 -1/2"
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
(DN100)
43
46
42
41
Nipple
No. 4"
(DN200)(DN150)
1/2" x 5-1/2"
6" 8"
P27
P28
P26 1/2" x 3"
1/2" x 8"
1/2" x 4"
Page6of16 TFP1460

Page 7 of 16
TFP1460
FIGURE 2B
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM
— OPERATIONAL COMPONENTS —
NOTES:
CONDUIT
1/2 INCH
FOR "ELECTRIC
CONNECTION
DETECTION"
(NORMALLY
CLOSED)
ACTUATOR
DRY PILOT
(NORMALLY
FAIL-SAFE
VALVE
CLOSED)
AIR SUPPLY
PRESSURE
GAUGE
F
PRESSURE
GAUGE
DIAPHRAGM
CHAMBER
SYSTEM
(NORMALLY
CLOSED)
SEPARATELY
ORDERED
SOLENOID
VALVE,
G
TEST VALVE
ALARM
(NORMALLY
CLOSED)
PRESSURE
GAUGE
SUPPLY
WATER
SYSTEM
CLOSED)
(NORMALLY
DRAIN VALVE
MAIN
B
C
ALARM
WATER MOTOR
CONNECTION FOR
3/4 INCH NPT
VENT FITTING
(GREEN TINT)
CONTROL
STATION
MANUAL
CONNECTION FROM
WATER SUPPLY
CONTROL VALVE
CHAMBER SUPPLY
1/2 INCH NPT (NORMALLY
OPEN)
DIAPHRAGM
UNUSED
PLUG
PORTS
CLOSED)
(NORMALLY
DRAIN VALVE
SYSTEM MAIN
AUTOMATIC
DRAIN
(NORMALLY
CONTROL VALVE
AIR SUPPLY
SYSTEM
OPEN)
1
NIPPLE
4
NIPPLE
3
NIPPLE
CHECK VALVE
RISER
(NOTE 1)
ALARM SWITCH
PRESSURE
1/2" x 1-1/2"
1/2" x 1-1/2"
1/2" x 4-1/2"
3/4" x 1-1/2"
MAIN DRAIN
CONNECTION
(SIZED PER TABLE)
MAIN DRAIN
CONNECTION
(SIZED PER
TABLE)
SYSTEM
CONNECTION
TO DRAIN
INCH NPT
WITH 1-1/4
FUNNEL
VALVE
DRIP
1/2 INCH NPT
CONNECTION
FOR SYSTEM
AIR SUPPLY
4" (DN100)
MODEL DV-5
DELUGE VALVE
SHOWN
FLANGE x GROOVE
D
5
NIPPLE
6
NIPPLE
7
NIPPLE
1/2" x 5"
1/2" x 2"
1/2" x 2"
PRESSURE
ALARM SWITCH
WATERFLOW
A
E
1/2" x 2-1/2"
1/2" x 1-1/2"
1/2" x 4"
3/4" x 2-1/2"
1/2" x 7"
1/2" x 3-1/2"
1/2" x 2"
1/2" x 5-1/2"
1/2" x 2"
1/2" x 5"
3/4" x 3-1/2"
1/2" x 5-1/2"
1/2" x 6"
1/2" x 2-1/2"
1/2" x 8-1/2"
1/2" x 2"
1/2" x 5-1/2"
3/4" x 4-1/2"
1/2" x 3"
1/2" x 8"
1/2" x 4"
2
NIPPLE
1-1/2" (DN40)
1
2
3
4
2" (DN50) 4" (DN100) 6" (DN150)3" (DN80) 8" (DN200)
Select Appropriate Nipple Sizes per DV-5 Deluge Valve Size
With Model CV-1FR Check Valve
5
6
7
Number
Nipple
See Figure 2 of TFP1305 for Deluge Valve
Port identification.
4.
Route all Tubing to Drip Funnel.5.
Install subassemblies in alphabetical order.
6. When DV-5 trips, the Fail-Safe Valve opens,
partially diverting the diaphragm supply to
2.
3.
Nipples 1-7 vary in length relative to the
Model DV-5 size and Riser Check Valve
used. Select per the appropriate table. All
other nipples packed unassembled shall be
installed per the appropriate trim exploded
view, Figure 2A Part 1, 2, or 3.
LOW AIR
drain, allowing diaphragm chamber to remain
de-pressurized after a decrease in system
flow.
1. Use only the 2" Model CV-1FR Riser Check
Valve with 1-1/2" and 2" DV-5 Valves. Use
corresponding sized Model CV-1FR Riser
Check Valves for 3"-8" Model DV-5 Valves.
1/2" x 6"
1/2" x 2-1/2"
1/2" x 1-1/2"
1/2" x Close
1/2" x 1-1/2"
1/2" x 3-1/2"
3/4" x 1-1/2"
1/2" x 5-1/2"
1/2" x 2"
1/2" x 1-1/2"
1/2" x Close
1/2" x 2"
1/2" x 3-1/2"
3/4" x 1-1/2"
Size
Main Drain 3/4" NPT 3/4" NPT 2" NPT 2" NPT1-1/4" NPT 2" NPT
System
Size
Drain 3/4" NPT 3/4" NPT 2" NPT 2" NPT1-1/4" NPT 2" NPT
Main

Page8of16 TFP1460
FIGURE 3
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM
— NOMINAL INSTALLATION DIMENSIONS —
(698,5)
27.50
(689,0)
27.13
(787,4)
31.00
MINIMUM CLEARANCE.
*
(254,0)
10.00
(289,0)
11.38
(298,5)
11.75
(363,5)
14.31
(266,7)
10.50
(165,1)
6.50
(200,0)
7.88
(217,5)
8.56
(252,4)
9.94
(181,0)
7.13
(9,5)
0.38
(39,7)
1.56
(644,5)
25.38
(752,5)
29.63
(44,5)
1.75
(88,9)
3.50
(266,7)
10.50
(181,0)
7.13
(231,8)
9.13
(266,7)
10.50
(152,4)
6.00
(152,4)
6.00
(390,5)
15.38
(DN50)
2"
(79,4)
3.13
(177,8)
7.00
(225,4)
8.88
(266,7)
10.50
(147,6)
5.81
(147,6)
5.81
(76,2)
3.00
(101,6)
4.00
(376,2)
14.81
(DN40)
1-1/2"
(101,6)
4.00
(177,8)
7.00
(181,0)
7.13
(76,2)
3.00
(177,8)
7.00
(79,4)
3.13
(198,4)
7.81
(265,1)
10.44
(266,7)
10.50
(170,0)
6.69
(108,0)
4.25
(536,6)
21.13
(DN80)
3"
(368,3)
14.50
(42,9)
1.69
(177,8)
7.00
ABCDE GHJKLMF
Nominal Installation Dimensions in Inches and (mm)
Size
Valve
(170,0)
6.69
(6,4)
0.25
(DN100)
4"
(DN150)
6"
(919,2)
36.19
(904,9)
35.63
(454,0)
17.88
(476,3)
18.75
(158,8)
6.25
(158,8)
6.25
(330,2)
13.00
(330,2)
13.00
(304,8)
12.00
(406,4)
16.00
(539,8)
21.25
(1028,7)
40.50
(273,1)
10.75
(269,9)
10.63
(927,1)
36.50
(DN200)
8"
(44,5)
1.75
(266,7)
10.50
(158,8)
6.25
(181,0)
7.13
(181,0)
7.13
CHAMBER SUPPLY
CONNECTING TRIM
(FIELD FABRICATED)
MAIN
CONTROL
VALVE
A
DIAPHRAGM
1/2" NPS
G
H
LEFT VIEW
*
B
F
DC
E
2" NPS
DRAIN
L
KJ
FRONT VIEW
**
*
1-1/4" NPS
DRAIN
M

into the system piping, as well as
through the Alarm Port to actuate the
system alarms.
As water flows into the system, the
Model FSV-1 Fail-Safe Valve (Item 5 -
Fig. 2A, also described in Technical
Data Sheet TFP1386) becomes pres-
surized and upon operation constantly
vents the DV-5 Diaphragm Chamber
so as to maintain the DV-5 Valve in the
open (operated) position until the sys-
tem is reset.
WARNING
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic
Actuation described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of the related devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Technical
Data
Approvals
UL and C-UL Listed. FM Approved.
Deluge Valve
Model DV-5.
Riser Check Valve
Model CV-1FR.
NOTE
1-1/2 inch (DN40) risers utilize a 2 inch
(DN50) Riser Check Valve in combina-
tion with the 1-1/2 inch (DN40) Model
DV-5 Deluge Valve.
Valve Trim
The Double Interlock Preaction Sys-
tem with Electric/Pneumatic Actuation
Trim (Fig. 2A/2B) forms a part of the
laboratory listings and approvals. The
trim is necessary for proper operation
of the DV-5 Valve.
Each package of trim includes the fol-
lowing items:
•Water Supply Pressure Gauge
•Diaphragm Chamber
Pressure Gauge
•Diaphragm Chamber Connections
•Manual Control Station
•Main Drain Valve
•System Drain Valve
•Alarm Test Valve
•Automatic Drain Valve
•System Air Pressure Gauge
•Air Supply Connections
•Low Air Pressure Alarm Switch
•Waterflow Pressure Alarm Switch
•Dry Pilot Actuator
•Pressure Operated Relief Valve
To ease field assembly of the trim ar-
rangement, the trim components are
provided partially assembled as
showninFigure2B.
The trim arrangement is provided with
galvanized or black nipples and fit-
tings. The galvanized trim is intended
for non-corrosive or corrosive condi-
tions, whereas the black trim is princi-
pally intended for use with AFFF sys-
tems.
NOTE
When the system pressure is greater
than 175 psi (12,1 bar), provision is to
be made to replace the standard order
300 psi (20,7 bar) Water Pressure
Gauges, shown in Figure 2A/2B with
separately ordered 600 psi (41,4 bar)
Water Pressure Gauges.
System Design Considerations
Because a double interlock preaction
system requires time for a drop in sys-
tem air pressure to occur (concurrently
with the response time for the separate
fire detection system) before it will al-
low water to enter the system piping,
this system has characteristics similar
to a dry pipe sprinkler system. There-
fore, the system design considerations
for a dry pipe system are normally
applied to a double interlock preaction
system — including a 30% increase in
design area; a maximum 1 minute
water delivery time for system capaci-
ties of 750 gallons (2800 litres) or
more; and, prohibition of gridded sys-
tem piping.
In order to readily perform the System
Inspection Procedure described in the
Care and Maintenance section, it is
Page 9 of 16
TFP1460
GRAPH A
DOUBLE INTERLOCK PREACTION SYSTEM
AIR PRESSURE REQUIREMENTS
WATER S
U
PPLY PRESS
U
RE IN PSI
100
RANGE OF ACTUATOR OPENING PRESSURE
MINIMUM SYSTEM AIR PRESSURE
AIR PRESSURE IN PSI
20 60
15
0
30
45
140 180 250200

Page 10 of 16 TFP1460
200 400 1000 3000200060010050
FLOW RATE IN GALLONS PER MINUTE (GPM)
3.0
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
0.8
0.4
0.5
0.6
0.7
1.0
0.9
2.0
6.0
4.0
5.0
9.0
7.0
8.0
10.0
15.0
FLOW RATE IN LITRES PER MINUTE (LPM)
200 1000600400
(1 GPM = 3,785 LPM)
2000 70003000 5000 10000
(1 PSI = 0,06895 BAR)
NOMINAL PRESSURE DROP IN BAR
0,040
0,030
0,050
0,080
0,060
0,070
0,090
0,100
0,200
0,800
0,400
0,300
0,600
0,500
0,700
1,000
0,900
2 INCH (DN50)
1-1/2 INCH (DN40)
6 INCH (DN150)
4 INCH (DN100)
3 INCH (DN80)
8 INCH (DN200)
GRAPH B
DELUGE AND CHECK VALVE COMBINATION*
— NOMINAL PRESSURE LOSS VERSUS FLOW —
* Model DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve
**1-1/2 inch Model DV-5 Deluge Valve combined with 2 inch Model CV-1FR Riser Check Valve
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with C=120, is as
follows:
15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination** calculated on a typical flow rate of 100 GPM.
28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 GPM.
37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 GPM.
48 feet of 4 inch Sch. 40 pipe for the 4 inch Valve Combination* calculated on a typical flow rate of 600 GPM.
73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 GPM.
103 feet of 8 inch Sch. 30 pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 GPM.

recommended that a System Shut-Off
Valve be installed above the Riser
Check Valve, as shown in Figure 1. The
System Shut-Off Valve should be a
listed or approved (as appropriate) in-
dicating valve with a supervisory
switch to monitor the normally open
position.
Detection System
The Double Interlock Preaction Sys-
tem With Electric/Pneumatic Actuation
Trim provides for electric operation of
the DV-5 Valve by a detection system
consisting of electrical devices such as
heat sensitive thermostats, smoke de-
tectors, and/or electric manual pull sta-
tions. Information on the various types
of separately ordered Solenoid Valves
that may be used with this trim pack-
age is given in Technical Data Sheet
TFP2180. Nominal installation dimen-
sions for the Double Interlock Preac-
tion System With Electric/Pneumatic
Actuation Trim are shown in Figure 3.
The deluge valve releasing panel
(automatic control unit) with battery
back-up, fire detection devices, man-
ual pull stations, and signaling devices
that are utilized with the Double Inter-
lock Preaction System with Elec-
tric/Pneumatic Actuation must be UL
Listed, ULC Listed, C-UL Listed, or FM
Approved, as applicable.
NOTES
Approval by Factory Mutual is contin-
gent on the use of an FM Approved
24VDC Solenoid Valve (P/N 52-287-1-
024 or P/N 52-287-1-124). FM only
approves solenoid valves for use in
non-hazardous locations.
Consult with the Authority Having Ju-
risdiction regarding installation criteria
pertaining to electric actuation cir-
cuitry.
The Double Interlock Preaction Sys-
tem With Electric/Pneumatic Actuation
Trim is provided with a Model FSV-1
Fail-Safe Valve (Item 5 - Fig. 2A, also
described in Technical Data Sheet
TFP1386); consequently, the release
circuit of the releasing panel need only
provide the standard ten minutes of
alarm condition intended to energize
the Solenoid Valve to open. After the
ten minute duration, at which point
should the Solenoid Valve become de-
energized and closes (especially while
operating under battery back-up), the
Fail-Safe Valve will have already auto-
matically operated to constantly vent
the DV-5 Diaphragm Chamber,
thereby preventing the DV-5 Dia-
phragm Chamber from becoming re-
pressurized and preventing an inad-
vertent closing of the DV-5 during a fire
event.
System Air Pressure Requirements
The required system air pressure for
the Double Interlock Preaction System
with Electric/Pneumatic Actuation is
shown in Graph A as a function of the
anticipated water supply pressure. It is
recommended that the system air
pressure be maintained by one of the
following methods:
•A maximum 200 psi (13,8 bar) plant
air supply in combination with the
Model AMD-1 Air Maintenance De-
vice described in Technical Data
Sheet TFP1221.
•A dedicated air compressor in com-
bination with the Model AMD-2 Air
Maintenance Device described in
Technical Data Sheet TFP1231.
•A maximum 3000 psi (206,9 bar)
nitrogen cylinder in combination with
the Model AMD-3 Nitrogen Mainte-
nance Device described in Techni-
cal Data Sheet TFP1241.
NOTES
The dew point of the air or nitrogen
supply, for a system exposed to freez-
ing conditions, must be maintained be-
low the lowest ambient temperature to
which the system piping will be ex-
posed. Introduction of moisture into
the system piping can create ice build
up which could prevent proper opera-
tion of the system.
Friction Loss
The nominal pressure loss versus flow
data for the Model DV-5 Deluge Valve
plus Riser Check Valve is provided in
Graph B.
Installation
NOTES
1-1/2 inch (DN40) risers utilize a 2 inch
(DN50) Riser Check Valve in combina-
tion with the 1-1/2 inch (DN40) Model
DV-5 Deluge Valve.
Proper operation of the Model DV-5
Deluge Valves depends upon their trim
being installed in accordance with the
instructions given in this Technical
Data Sheet. Failure to follow the ap-
propriate trim diagram may prevent
the DV-5 Valve from functioning prop-
erly, as well as void listings, approvals,
and the manufacturer’s warranties.
Field adjustments of the Air Mainte-
nance Device, Low Pressure Alarm
Switch, and Pressure Relief Valve are
required.
When using compressed air as op-
posed to compressed nitrogen for re-
frigerated area service, alternate air
supply connections with an air dryer
may be required by the Authority Hav-
ing Jurisdiction. The “1/2 Inch NPT
Connection For System Air Supply”
showninFigure2Bistobeplugged
when using an alternate air supply
connection; the location of the Air
Pressure Maintenance is to be as
specified by the Authority Having Ju-
risdiction; and, Step 10 regarding the
adjustment of the Pressure Relief
Valve can be omitted, since the Pres-
sure Relief Valve in this case will be
ineffective.
The DV-5 Valve must be installed in a
readily visible and accessible location.
The DV-5 Valve and associated trim
must be maintained at a minimum tem-
perature of 40°F/4°C.
Heat tracing of the DV-5 Valve or its
associated trim is not permitted. Heat
tracing can result in the formation of
hardened mineral deposits that can
prevent proper operation.
The Model DV-5 Deluge Valve is to be
installed in accordance with the follow-
ing criteria:
Step 1. All nipples, fittings, and de-
vices must be clean and free of scale
and burrs before installation. Use pipe
thread sealant sparingly on male pipe
threads only.
Step 2. The DV-5 Valve must be
trimmed in accordance with Figure
2A/2B.
Step 3. Care must be taken to ensure
that check valves, strainers, globe
valves, etc. are installed with the flow
arrows in the proper direction.
Step 4. Drain tubing to the drip funnel
Page 11 of 16
TFP1460

must be installed with smooth bends
that will not restrict flow.
Step 5. The main drain and drip funnel
drain may be interconnected provided
a check valve is located at least 12
inches (300 mm) below the drip funnel.
Step 6. Suitable provision must be
made for disposal of drain water.
Drainage water must be directed so
that it will not cause accidental dam-
age to property or danger to persons.
Step 7. Connect the Diaphragm
Chamber Supply Control Valve to the
inlet side of the system’s main control
valve in order to facilitate setting of the
DV-5 Valve (Fig. 3).
Step 8. Unused pressure alarm
switch connections must be plugged.
Step 9. A suitable automatic supervi-
sory air (nitrogen) supply, as described
in the Technical Data Section, is to be
installed in accordance with the appli-
cable Technical Data Sheet. Refer to
Graph A for the system air pressure
requirements.
An air dryer, when specified, is to be
installed as required by the Authority
Having Jurisdiction.
Step 10. The Pressure Relief Valve
(P6 - Fig. 2A) is factory set to relieve at
a pressure of approximately 45 psi (3,1
bar), which can typically be used for a
maximum system pressure of 40 psi
(2,8 bar). The Pressure Relief Valve
may be reset; however, it must be reset
to relieve at a pressure that is in ac-
cordance with the requirements of the
Authority Having Jurisdiction.
To reset the Pressure Relief Valve, first
loosen the jam nut and then adjust the
cap accordingly — clockwise for a
higher pressure setting or counter-
clockwise for a lower pressure setting.
After verifying the desired pressure
setting, tighten the jam nut.
Step 11. The Low Pressure Alarm
Switch (Item P4 - Fig. 2A) is to be
adjusted to operate on falling pressure
at approximately 6 psi (0,4 bar) below
the minimum Double Interlock Dry
System air pressure requirement
shown on Graph B.
Use the instructions provided with the
switch to adjust the pressure setting.
Step 12. Conduit and electrical con-
nections are to be made in accordance
with the requirements of the authority
having jurisdiction and/or the National
Electric Code.
Step 13. Before a system hydrostatic
test is performed in accordance with
NFPA 13 system acceptance test re-
quirements, the DV-5 Diaphragm
Chamber is to be depressurized; the
Automatic Drain Valve (4, Fig. 2A) is to
be temporarily replaced with a 1/2 inch
NPT plug, the 3/32 inch Vent Fitting (17
- Fig. 2A) is to be temporarily replaced
with a 1/4 inch NPT plug, and the Dia-
phragm Cover Bolts must be uni-
formly and securely tightened using
a cross-draw sequence. After tight-
ening, double-check to make certain
that all of the Diaphragm Cover Bolts
are securely tightened.
Valve Setting
Procedure
Steps 1 through 15 are to be per-
formed when initially setting the Model
DV-5 Deluge Valve; after an opera-
tional test of the fire protection system;
or, after system operation due to a fire.
Step 1. Close the Main Control Valve.
Step 2. Close the Diaphragm Cham-
ber Supply Control Valve and the Sys-
tem Air Supply Control Valve.
Step 3. Open the Main Drain Valve,
System Drain Valve, and all auxiliary
drains in the system. After water
ceases to discharge, close the System
Drain Valve and auxiliary drain valves.
Leave the Main Drain Valve open.
NOTE
Do not open the Inspector’s Test Con-
nection and auxiliary drains if resetting
after a system test; otherwise, system
air pressure will be relieved unneces-
sarily.
Step 4. Depress the plunger of the
Automatic Drain Valve to verify that it
is open and that the DV-5 Valve is
completely drained.
Step 5. Clean the Strainer in the Dia-
phragm Chamber Supply connection
by removing the clean-out plug and
strainer basket. The Strainer may be
flushed out by momentarily opening
the Diaphragm Chamber Supply Con-
trol Valve.
Step 6. Inspect for and clear all ice
plugs where system piping has been
exposed to freezing conditions and
when there has been a flow of water
into the system.
Step 7. Replace all damaged or oper-
ated sprinklers. Replacement sprin-
klers must be of the same type and
temperature rating as those that oper-
ated.
NOTE
In order to prevent the possibility of a
subsequent operation of an over-
heated solder type sprinkler, any sol-
der type sprinklers possibly exposed
to a temperature greater than their
maximum rated ambient must also be
replaced.
Step 8. Service the air dryer, if appli-
cable, in accordance with the manu-
facturer’s instructions.
Step 9. Open the System Air Supply
Control Valve and allow the system to
automatically re-establish its nominal
system air pressure per Graph A. Ob-
serve the Automatic Drain Valve for
leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem within the Riser Check Valve.
Step 10. Reset the actuation system.
Manual Actuation — Push the operat-
ing lever up; however, do not close the
hinged cover at this time.
Electric Actuation — Reset the electric
detection system in accordance with
the manufacturer’s instructions to de-
energize the Solenoid Valve.
Step 11. Open the Diaphragm Cham-
ber Supply Control Valve and allow full
pressure to build up in the Diaphragm
Chamber.
Step 12. Operate (open) the Manual
Control Station to vent trapped air from
the Diaphragm Chamber. If necessary,
first open the hinged cover, and then
fully pull down on the operating lever.
SLOWLY close the operating lever, by
pushing it up, after aerated water
ceases to discharge from the Manual
Control Station drain tubing. Close the
hinged cover and insert a new break
rod in the small hole through the top of
the enclosing box.
Step 13. Inspect the drain connections
from the Manual Control Station and
the Dry Pilot Actuator. Any leaks must
be corrected before proceeding to the
next step.
Step 14. Verify the ability for the DV-5
Diaphragm to hold pressure as fol-
lows:
With the diaphragm chamber pressur-
ized per Step 12, temporarily close the
Diaphragm Chamber Supply Control
Valve and observe the Diaphragm
Chamber Pressure Gauge for a drop in
pressure.
If a drop in pressure is noted, the DV-5
Diaphragm is to be replaced and/or
any leaks must be corrected before
proceeding to the next step.
If the Diaphragm Chamber Pressure
Gauge does not indicate a drop in
pressure, re-open the Diaphragm
Chamber Supply Control Valve and
proceed to the next step.
Step 15. Slowly open the Main Control
Valve. Close the Main Drain Valve as
soon as water discharges from the
Page 12 of 16 TFP1460

drain connection. Observe the Auto-
matic Drain Valve for leaks. If there are
leaks, determine/correct the cause of
the leakage problem. If there are no
leaks, the DV-5 Valve is ready to be
placed in service and the Main Control
Valve must then be fully opened.
NOTES
When the Main Control Valve is
opened, the pressure on the Dia-
phragm Chamber may increase. This
increase in pressure is normal, and if
the pressure is greater than 250 psi
(17,2bar),thepressureistobere-
lieved by partially and temporarily
opening the Manual Control Station;
however, do not allow the pressure as
indicated on the Diaphragm Chamber
Pressure Gauge to drop below the
supply pressure shown on the Water
Supply Pressure Gauge, since this ac-
tion may result in tripping of the DV-5
Valve.
After setting a fire protection system,
notify the proper authorities and ad-
vise those responsible for monitoring
proprietary and/or central station
alarms.
Care and
Maintenance
The following procedures, inspections,
and maintenance must be performed
as indicated, in addition to any specific
requirements of the NFPA, and any
impairment must be immediately cor-
rected.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
It is recommended that the System
Inspection Procedure be performed at
least semi-annually by a qualified In-
spection Service. The Double Interlock
Preaction System Inspection Proce-
dure may be followed in lieu of per-
forming any of the operational tests
recommended in the Technical Data
Sheets for the Model DV-5 Deluge
Valve, Riser Check Valve, 24 VDC So-
lenoid Valve, Dry Pilot Actuator, and
Model MC-1 Manual Control Station.
NOTES
It is recommended that the individuals
responsible for the care and mainte-
nance of the Double Interlock Preac-
tion System develop a working under-
standing of the system, in general,
prior to performing inspection and/or
maintenance procedures. These in-
structions, as well as individual in-
structions for the deluge valve, riser
check valve, solenoid valve, dry pilot
actuator, manual control station,
switches, and pressure maintenance
device should be reviewed.
The following procedures pertain to
the automatic control valve portion of
the Double Interlock Preaction Sys-
tem. Refer to the manufacturer’s in-
structions and NFPA 25 for care and
maintenance procedures for all other
devices (e.g., electric detection, main
control and system shut-off valves, su-
pervisory devices, sprinklers, etc.).
Before performing the System Inspec-
tion Procedure, which will result in op-
eration of alarms, notify the proper
authorities and all personnel who may
be affected.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
System Inspection Procedure
Step 1. Close the Main Control Valve
(Fig. 1) and then open the DV-5 Main
Drain Valve (Fig. 2B).
Step 2. Manually operate Deluge
Valve Releasing Panel, and verify the
following:
•Verify the operation of the Releasing
Panel and its associated alarms.
•Verify that there is no leakage from
the Dry Pilot Actuator (Fig. 2B).
NOTES
During this procedure, the Solenoid
Valve is opened; however, the Dry Pi-
lot Actuator should remain closed and
the DV-5 Deluge Valve Diaphragm
Chamber should remain pressurized.
This procedure is used to verify that
the DV-5 Deluge Valve will remain set
if the electric detection system oper-
ates but the sprinkler system remains
in its normally pressurized condition.
Step 3. Open the Inspector’s Test Con-
nection but be prepared to close it im-
mediately after verifying that the Low
Pressure Alarm Switch (Fig. 2B) and
its associated alarms operate properly.
The Low Pressure Alarm Switch
should operate at the previously estab-
lished pressure (refer to Installation
section, Step 11).
Close the Inspector’s Test Connection.
Step 4. Close the Diaphragm Chamber
Supply Control Valve (Fig. 2B).
Step 5. Close the System Shut-off
Valve (Fig. 1) after the system air pres-
sure has been restored to normal.
Step 6. Manually restore the electric
fire detection system to a normal con-
dition in accordance with the manufac-
turer’s instructions.The Solenoid Valve
will then be de-energized and returned
to its normally closed position.
Step 7. Open the Diaphragm Chamber
Supply Control Valve (Fig. 2B).
Step 8. Open the Main Control Valve
(Fig. 1) one turn beyond the position at
which water just begins to flow from
the Main Drain Valve.
Page 13 of 16
TFP1460

Step 9. Close the Main Drain Valve
(Fig. 2B).
Step 10. Close the Air Supply Control
Valve (Fig. 2B).
Step 11. Open the Dry Pilot Actuator
by partially opening the System Main
Drain Valve (Fig. 2B) to relieve air pres-
sure at the inlet to the Actuator. Verify
that there is no leakage from the Dry
Pilot Actuator.
NOTES
During this procedure, the Dry Pilot
Actuator is opened; however, the So-
lenoid Valve should remain closed and
the DV-5 Deluge Valve Diaphragm
Chamber should remain pressurized.
This procedure is used to verify that
the DV-5 Deluge Valve will remain set
if the Dry Pilot Actuator operates due
to loss of system air pressure and the
electric detection system remains in a
normal condition.
Step 12. Open (energize) the Solenoid
Valve by operating the deluge valve
releasing panel, and verify the follow-
ing:
•Verify that the DV-5 Valve operates,
as is indicated by a discharge of
water from the System Main Drain
Valve and the Automatic Drain
Valve. The Automatic Drain Valve
may or may not close depending on
the flow past the partially open Main
Control Valve.
•Verify that the Model FSV-1 Fail-
Safe Valve has operated as is indi-
cated by water discharging into the
Drip Funnel from the 1/2 inch drain
tube connected to the Model FSV-1
Fail-Safe Valve.
•Verify that the Waterflow Pressure
Alarm Switch (Fig. 2B) and its asso-
ciated alarms properly operate.
•Verify that the Water Motor Alarm, if
applicable, properly operates.
NOTE
This procedure simulates opening of
both the Dry Pilot Actuator (loss of
system air pressure) and Solenoid
Valve (operation of the deluge valve
releasing panel) to verify automatic
system operation.
Step 13. Reset the Double Interlock
Preaction System in accordance with
the Resetting Procedure section.
Fail-Safe Valve
If water does not discharge from the
1/2 inch tube connected to the Model
FSV-1 Fail-Safe Valve during Step 12
of the System Inspection Procedure,
the Model FSV-1 Fail-Safe Valve is to
be disassembled, cleaned, and in-
spected as follows:
Step 1. Take the sprinkler system out
of service by using Steps 1 through 4
of the Resetting Procedure.
Step 2. Remove the FSV-1 from the
Double Interlock Preaction Trim.
Step 3. Refer to Technical Data Sheet
TFP1386 and completely disassem-
ble the FSV-1.
Step 4. Clean all parts, and replace
worn or damaged parts as necessary
Step 5. Reassemble the FSV-1 in ac-
cordance with Technical Data Sheet
TFP1386 and then reinstall the FSV-1
into the Double Interlock Preaction
Tr i m .
Step 6. Place the system into service
in accordance with the Resetting Pro-
cedure section and then perform the
System Inspection Procedure to verify
proper operation of the system, as well
as the FSV-1 Fail-Safe Valve.
Quarterly Waterflow Alarm Test
Procedure
Testing of the system waterflow alarms
must be performed quarterly. To test
the waterflow alarm, open the Alarm
Test Valve, which will allow a flow of
water to the Waterflow Pressure Alarm
Switch and/or Water Motor Alarm.
Upon satisfactory completion of the
test, close the Alarm Test Valve.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Page 14 of 16 TFP1460

Ordering
Procedure
With reference to Table A on Page 16,
the following items must be ordered
separately:
•Deluge Valve
•Riser Check Valve
•Coupling (Deluge Valve to Riser
Check Valve)
•Double Interlock Preaction Trim
•Automatic System Air Supply
•Solenoid Valve
•Accessories
NOTE
1-1/2 inch (DN40) risers utilize a 2 inch
(DN50) Riser Check Valve in combina-
tion with the 1-1/2 inch (DN40) Model
DV-5 Deluge Valve.
Part Numbers for factory pre-trimmed
Model DV-5 Valves are provided in the
Price Book.
Replacement Trim Parts:
Specify: (description) for use with
Model DV-5 Deluge Valve, P/N (see
Figure 2A).
Page 15 of 16
TFP1460
DELUGE VALVE (SELECT ONE)
P/N’s are for American Standard Groove x Groove Connections, and Threaded Ports, For
other configurations refer to Technical Data Sheet TFP1305. Specify: (size) Model DV-5
groove x groove Deluge Valve, P/N (specify).
1-1/2 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-919
2 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-910
3 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-912
4 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-913
6 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-915
8 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-916
RISER CHECK VALVE (SELECT ONE)
P/N’s are for American Standard Grooved Connections. For other configurations refer to
Technical Data Sheet TFP950 for the groove x groove Model CV-1FR Riser Check Valve.
Specify: (size), Model CV-1FR groove x groove Riser Check Valve, P/N (specify).
For 1-1/2
inch risers, use the 2 Inch Riser Check Valve.
2 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-020
3Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-030
4 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-040
6Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-060
8Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-080
COUPLING (SELECT ONE)
P/N’s are for American Standard Grooved Connections. For other configurations and
finishes refer to Technical Data Sheet TFP1830 and TFP1880. A coupling to attach the
Riser Check Valve to the outlet of the Deluge Valve must be separately ordered. Specify:
(Size), (Figure #), painted, (description), P/N (specify).
For 1-1/2 inch risers, order an
additional Reducing Coupling for the outlet of the 2 inch Riser Check Valve.
2 x 1-1/2 Inch Figure 716 Painted Reducing Coupling . . . . . . . . . . . . . . . . . . . . . . . P/N 7162015ES
2 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77220ASC
3 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77230ASC
4 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77240ASC
6 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77260ASC
8 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77280ASC
DOUBLE INTERLOCK PREACTION TRIM (SELECT ONE)
Specify: (specify size and finish — galvanized is standard) Semi-Preassembled Double
Interlock Preaction System With Electric/Pneumatic Actuation Trim for Model DV-5 Deluge
Valves, P/N (specify).
1-1/2 & 2 Inch Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-127
1-1/2 & 2 Inch Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-127
3 Inch Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-124
3 Inch Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-124
4, 6 & 8 Inch Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-121
4, 6 & 8 Inch Black. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-121
AUTOMATIC SYSTEM AIR SUPPLY (SELECT ONE)
A device capable of maintaining a nominal system air or nitrogen pressure per Graph A
must be separately ordered. Specify: (Specify model and description), P/N (specify).
Model AMD-1 Air Maintenance Device (TFP1221) . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-324-2-002
Model AMD-2 Air Maintenance Device (TFP1231) . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-326-2-001
Model AMD-3 Nitrogen Maintenance Device (TFP1241) . . . . . . . . . . . . . . . . . . . . . P/N 52-328-2-001
SOLENOID VALVE (SELECT ONE)
A Solenoid Valve compatible with the anticipated maximum water supply pressure must
be ordered separately. Refer to Technical Data Sheet TFP2180 for other voltage ratings
and NEMA classifications. Specify: 24 VDC, NEMA 2, 4 and 4X, (specify 175 or 250 psi)
Solenoid Valve, P/N (specify).
175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-287-1-024
250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-287-1-124
ACCESSORIES (AS NEEDED)
Specify: (description), PN (specify).
600 PSI Water Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 92-343-1-004
Model WMA-1 Water Motor Alarm (TFP921) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-630-1-001
TABLE A — ORDERING LIST

Page 16 of 16 TFP1460
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Other manuals for DN40
1
This manual suits for next models
1
Table of contents
Other Tyco Control Unit manuals
Popular Control Unit manuals by other brands

InWin
InWin RS424-07 user manual

Navico
Navico BSM-1 installation manual

Azbil
Azbil ACTIVAL VY5302B Specifications & instructions

Data Translation
Data Translation DT9850 Series user manual

rako
rako RAIPC Installation and operating instructions

Dormakaba
Dormakaba ED connection board CAN Assembly instruction