manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Control Unit
  8. •
  9. Tyco FC410RIM User manual

Tyco FC410RIM User manual

Other Tyco Control Unit manuals

Tyco Narvik-Yarway 51 User manual

Tyco

Tyco Narvik-Yarway 51 User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco iSTAR Ultra Operator's manual

Tyco

Tyco iSTAR Ultra Operator's manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco Grinnell F540 User manual

Tyco

Tyco Grinnell F540 User manual

Tyco DN100 User manual

Tyco

Tyco DN100 User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco DV-3HP User manual

Tyco

Tyco DV-3HP User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco AV-1-300 User manual

Tyco

Tyco AV-1-300 User manual

Tyco ACC-1 User manual

Tyco

Tyco ACC-1 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco HSM2955 User manual

Tyco

Tyco HSM2955 User manual

Tyco DV-2 User manual

Tyco

Tyco DV-2 User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco RSV-1 User manual

Tyco

Tyco RSV-1 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco DN40 User manual

Tyco

Tyco DN40 User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco VIZOR User manual

Tyco

Tyco VIZOR User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

TECHNICAL SPECIFICATION
Type IdentificationValue: 161
System Compatibility: Use only with FC Fire Alarm Controllers
Environment: Indoor Application only
Operating Temperature: -25 to +70 oC
Storage Temperature: -40 to +80 oC
Operating Humidity: Up to 95% non-condensing
Dimensions (HxWxD): 87x148x14mm
Mounting Requirements: One FC backbox surface mount
Battery Requirements:
Standby Current: 0.46mA max
Alarm Current: 4.5mA max
Addressable Device Condi-
tions: – Normal
– Active
– Output Stuck
– Device Type Invalid
– Device No Response
Relay Contact Rating: DC – 2A @ 24V dc
+Note: The module must not be used to switch mains voltages
Recommended Wire Size: Min. 1.5 mm2Max. 2.5 mm2
Electromagnetic Compatibility
The FC410RIM complies with the following:
Øproduct family standard EN50130-4 in respect of Conducted Distur-
bances, Radiated Immunity, Electrostatic Discharge, Fast Transients
and Slow High Energy;
ØEN50081-1 for emissions.
INTRODUCTION
The FC410RIM Relay Interface Module provides one volt-free relay change-
over contact on a latching relay. The relay is controlled by a command sent
from the FC fire controller via the addressable loop. The relay state (acti-
vated, deactivated or stuck) is returned to the controller.
FEATURES
FC410RIM features include the following:
ØAddressable functionality.
The control panel sends a command to operate the relay, then reports an
activated or deactivated state back to the panelthrough the use of a set of
contacts dedicated to monitor the state of the relay.
ØOne volt-free dry contact relay output.
ØOutput to drive a high voltage relay HVR800.
ØLED status indicator which is normally off. When the FC410RIM receives
a command to activate, the LED lights.
WIRING & INSTALLATION NOTES
!CAUTION:THE O+ AND O- TERMINALS MUST NOT BE USED.FOR
CONNECTING THE FC410RIM TO AN HVR800, SEE PUBLICATION
17A-03-HVR OR 120-415-528.
The following notes apply:
1) There are no user-required settings (switches, headers) on the
FC410RIM. All wiring must be free of earths.
2) All wiring must conform to the applicable standards.
3) See Figure 4 for FC410RIM Simplified Wiring Diagram.
4) For 24V dc powered applications, only use a regulated supply suitable
for fire protective signalling service.
5) For powered circuit operation, route the positive conductor through the
FC410RIM to the external device, while connecting the common (neu-
tral) conductor to the external circuit.
6) For dry contact switching, connect the external circuit to the COM and N/O
or N/C terminals for normally open or normally closed operation as required.
7) Verify that relay wiring is correct for the FC410RIM before connecting to
the addressable loop circuit.
8) For connection to an HVR800 High Voltage Relay Module, refer to In-
stallation Sheet 17A-03-HVR or 120-415-528.
INSTALLATION TO FC470CV DOUBLE GANG COVER
1) Assemble the FC410RIM to FC470CV Double Gang cover, using the
four screws and washers provided.
2) Snap on the ancillary housing PCB cover.
3) Fit cover onto FC backbox.
ADDRESS SETTINGS
The FC410RIM has a default factory set address of 255, this must be set to
the loop address of the device using the FC490ST Loop Service Tool. The
FC410RIM may be programmed with the address prior to being installed by
using the internal programming port (see Fig.2) or after being installed by
using the programming port on the front cover (see Fig.3).
+Note: once the address has been programmed, take note of the device
location and address number, to include on site drawings.
CABLING
The maximum section of the cable that can be connected at any one termi-
nal is 2.5mm2. The section is calculated based on the characteristics of the
cable and the load.
ORDERING INFORMATION
FC410RIM: Relay Input Module:
FC470CV: Double-Gang cover
RECYCLING INFORMATION
Customers are recommended to dispose of their used equipments (panels,
detectors, sirens, and other devices) in an environmentally sound manner.
Potential methods include reuse of parts or whole products and recycling of
products, components, and/or materials.
WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
DIRECTIVE
In the European Union, this label indicates that this product
should NOT be disposed of with household waste. It should be
deposited at an appropriate facility to enable recovery and re-
cycling.
The manufacturer reserves the right to change the technical specifications
of this product without prior notice.
ENGLISH
FIG. 1 FC410RIM Relay Interface Module
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
PROGRAMMIERANSCHLUSS
L+ L- L+ L- O+ O- N/O C N/C
TB2
TB3
TB1
FIG. 2 FC410RIM fissata al coperchio
FC410RIM ins Gehäuse eingebaut
FC410RIM fitted to cover
PORTA DI PROGRAMMAZIONE
ADDRESS SETTING PORT
PROGRAMMIERAN
S
CHLU
SS
FIG. 3 FC410RIM Placca
Kurzschlussisolator Vorderseite
Facia Plate
ALIMENTATORE
POWER SUPPLY UNIT
ENERGIE-
VERSORGUNG
DISPOSITIVO ESTERNO/
CIRCUITO COMMUTABILE
EXTERNAL DEVICE/
SWITCHABLE CIRCUIT
EIN-UND AUSSCHALT-
BARER VERBRAUCHER
CIRCUITO ELETTRONICO SWITCHING
ELECTRONIC SWITCHING CIRCUIT
SCHALTBARE BAUGRUPPE
CENTRALE FC
FC CONTROLLER
FC ZENTRALE
L1
L1
L1
RIGHT
LEFT
L+ L- L+ L- O+ O- N/O C N/C
L+ L- L+ L- O+ O- N/O C N/C
P1
P1
L1
FC410RIM Schema di collegamento
Typische Verdrahtung des FC410RIM
FIG. 4
FC410RIM Simplified Wiring Diagram