manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Control Unit
  8. •
  9. Tyco BFV-N User manual

Tyco BFV-N User manual

Model BFV-N Butterfly Valve
Grooved End
Page 1 of 4 JULY 2015 TFP1510
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Listed by California State Fire Marshall
under Listing No. 7770-1670:100
All laboratory listings and approvals are for
indoor and outdoor use.
Sizes
2-1/2 thru 10 Inch (DN65 thru DN250)
Maximum Working Pressure
2-1/2 to 8 Inch (DN65 to DN200)
300 psi (20,7) bar
10 Inch (DN250)
175 psi (12,0 bar)
Materials of Construction
Body
Ductile iron conforming to ASTM A395
Body Coating
Polyamide
Disc
Ductile iron conforming to ASTM A395
Disc Seal
Grade EPDM “E” encapsulated rubber
conforming to ASTM D2000
Upper & Lower Stem
Type 416 Stainless Steel
conforming to
ASTM 582
Lower Plug
PVC
Operator
Gear operator with iron housing
General
Description
The Model BFV-N Grooved End But-
terfly Valves (Ref. Figure 1) are indi-
cating type valves designed for use in
fire protection systems where a visual
indication is required as to whether the
valve is open or closed. They are used,
for example, as system, sectional, and
pump water control valves. They have
cut groove inlet and outlet connections
that are suitable for use with grooved
end pipe couplings that are listed and
approved for fire protection systems.
For applications requiring supervision
of the open position of the valve, the
Gear Operators for the Model BFV-N
Butterfly Valves are provided with
two sets of factory installed inter-
nal switches each having SPDT con-
tacts (Ref. Figure 3). The supervisory
switches transfer their electrical con-
tacts when there is movement from the
valve’s normal open position during the
first two revolutions of the handwheel.
NOTICE
The Model BFV-N Grooved End But-
terfly Valves described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
TFP1510
Page 2 of 4
Nominal
Valve
Sizes
Inches
(DN)
Pipe
OD
Inches
(mm)
Nominal Installation Dimensions
Inches (mm) Weight
Lbs.
(kg)
A B C D E F G H
2-1/2
(65)
2.88
(73,0)
3.85
(98,0)
11.94
(303,3)
3.25
(83,0)
5.67
(144,0)
5.90
(149,9)
5.82
(147,8)
2.13
(54,1) 022
(10,0)
76,1m m
(65)
3.00
(76,1)
3.85
(98,0)
11.94
(303,3)
3.25
(83,0)
5.67
(144,0)
5.90
(149,9)
5.82
(147,8)
2.13
(54,1) 022
(10,0)
3
(80)
3.50
(88,9)
3.85
(98,0)
12.48
(317,0 )
3.54
(90,0)
5.94
(150,9)
5.90
(149,9)
5.82
(147,8)
2.13
(54,1) 023
(10,4)
4
(100)
4.50
(114,3)
4.56
(116,0)
14.18
(360,2)
4.35
(110,0 )
6.31
(160,3)
5.90
(149,9)
7. 6 4
(194,1)
2.13
(54,1) 028
(12,7)
5
(125)
5.56
(141,3)
5.86
(149,0)
15.17
(385,3)
4.84
(123,0)
7.3 2
(185,9)
5.90
(149,9)
7. 6 4
(194,1)
2.13
(54,1) 031
(14,1)
165,1mm
(150)
—
(16 5,1)
5.86
(149,0)
17.5 4
(445,5)
5.93
(151,0)
8.62
(218,9)
5.90
(149,9)
7. 6 4
(194,1)
2.13
(54,1)
0.67
(17, 0)
41
(18,6)
6
(150)
6.63
(168,3)
5.86
(149,0)
17.5 4
(445,5)
5.93
(151,0)
8.62
(218,9)
5.90
(149,9)
7. 6 4
(194,1)
2.13
(54,1)
0.67
(17, 0)
41
(18,6)
8
(200)
8.63
(219,1)
5.26
(134,0)
19.42
(493,3)
6.87
(174,0)
9.80
(248,9)
9.80
(248,9)
7.91
(200,9)
2.13
(54,1)
5.86
(148,8)
53
(24,1)
10
(250)
10.75
(273,1)
6.29
(160,0)
24.03
(610,4)
9.17
(233,0)
11.61
(294,9)
18.00
(4 57, 2 )
9.49
(241,0)
3.03
( 7 7,0 )
7.41
(188,2)
88
(40,0)
1/2A @ 125 VDC
1/4A @ 250 VDC
15.1A/12HP @ 125, 250 VAC
5A @ 125 VAC "L"
END OF LINE
RESISTOR
PANEL
ORANGE
ORANGE
YELLOW
YELLOW
SUPERVISORY
SWITCH
SWITCH SHOWN
WITH VALVE
FULL OPEN
GREEN
VIOLET
AUXILIARY
SWITCH SHOWN
WITH VALVE
FULL OPEN
BLUE
RED
BELL
SWITCH
GND
POWER
+
- -
+
CONTACT RATING:
INDICATOR
FLAG
GEAR
OPERATOR
1/2" NPT
CONDUIT
CONNECTION
F HANDWHEEL
DISC
BODY
E
D
C
B
G
A
H
FIGURE 1
MODEL BFV-N GROOVED END BUTTERFLY VALVE
NOMINAL DIMENSIONS
FIGURE 2
MODEL BFV-N BUTTERFLY VALVE
INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION
TFP1510
Page 3 of 4
Installation
The Model BFV-N Grooved End Butter-
fly Valves may be installed with flow in
either direction and can be positioned
either horizontally or vertically.
The grooved end pipe couplings used
with the Model BFV-N must be listed or
approved for fire protection service and
installed in accordance with the manu-
facturers instructions.
The Model BFV-N Butterfly Valve may
be installed with any schedule of pres-
sure class of pipe or tubing that is listed
or approved for fire protection.
As applicable, refer to Figure 2 for the
internal switch wiring diagram.
Conduit and electrical connections
are to be made in accordance with
the authority having jurisdiction and/
or the National Electrical Code. With
reference to Figure 2, the supervisory
switch is intended for connection to
the supervisory circuit of a fire alarm
control panel in accordance with NFPA
72. The auxiliary switch is intended for
the unsupervised connection to aux-
iliary equipment in accordance with
NFPA 70, National Electric Code.
NOTE: For outdoor applications with
internal supervisory switches, it is rec-
ommended that wiring connections
be made at a temperature above 15°F
(-9°C), in order to insure sufficient flex-
ibility of the wire lead insulation.
Stop
Adjustment
Procedure
The gear operator’s OPEN and SHUT
position have been factory set. The
following procedure should be used if
slight adjustments are needed. Refer to
Figure 3.
Step 1. Turn the Handwheel until the
valve is fully closed.
Step 2. Remove two lockscrews (A)
from the gear operator body.
Step 3. Turn the Shut Stop Screw (B)
clockwise until snug.
Step 4. Turn the Handwheel until the
valve is fully open.
Step 5. Turn the Open Stop Screw (C)
clockwise until snug.
Step 6. Close the valve by turning the
Handwheel until the valve is fully in
the closed position. Ensure the disc
has returned to the fully closed posi-
tion and the disc is centered in the seat
area. Readjust the Shut Stop Screw if
necessary.
Step 7. Replace two lockscrews (A)
into the gear Operator body locking
the stops into position.
10 INCH (DN250)
8 INCH (DN200)
6 INCH (DN150)
5 INCH (DN125)
4 INCH (DN100)
3 INCH (DN80)
2-1/2 INCH (DN65)
2.0
0.4
0.1
0.2
0.3
0.6
0.5
0.8
1.0
3.0
4.0
5.0
60 100 200 600400 1000 2000 1000060004000
600 1000060001000 2000 4000 20000 40000400
0,30
0,20
0,08
0,10
0,06
0,04
0,05
0,03
0,02
0,01
FLOW RATE IN LITRES PER MINUTE (LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
(1 PSI = 0,06895 BAR)
NOMINAL PRESSURE DROP IN BAR
(1 GPM = 3,785 LPM)
15000
300
AC
A
B
OPEN
SHUT
GRAPH A
DN65 THROUGH DN250 MODEL BFV-N BUTTERFLY VALVE
NOMINAL PRESSURE DROP VERSUS FLOW
FIGURE 3
MODEL BFV-N GROOVED END
BUTTERFLY VALVE
OPERATOR ADJUSTMENT
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP1510
Page 4 of 4
Copyright © 2015 Tyco Fire Products, LP. All rights reserved.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Grooved End Butterfly Valves
Specify: (specify inch size) Model
BFV-N Grooved End Butterfly Valve
with internal supervisory switches,
P/N (specify):
2-1/2 inch (DN65) ............59-300-F-025N
76,1mm (DN65)* .............59-300-F-076N
3 inch (DN80) ...............59-300-F-030N
4 inch (DN100) ..............59-300-F-040N
5 inch (DN125) ..............59-300-F-050N
165,1mm (DN150)* . . . . . . . . . . . 59-300-F-165N
6 inch (DN150) ..............59-300-F-060N
8 inch (DN200) ..............59-300-F-080N
10 inch (DN250) ............. 59-300-F-100N
*Available for EMEA and APAC markets only
Care and
Maintenance
Before closing a fire protection system
control valve for maintenance or
inspection work on either the valve or
fire protection system which it con-
trols, permission to shut down the
affected fire protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this decision must be notified.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in accordance with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any authority having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions. Any impairment must
be immediately corrected.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified inspec-
tion service.

Other Tyco Control Unit manuals

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco VIZOR User manual

Tyco

Tyco VIZOR User manual

Tyco DV-1 User manual

Tyco

Tyco DV-1 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco DV-2 User manual

Tyco

Tyco DV-2 User manual

Tyco ACC-1 User manual

Tyco

Tyco ACC-1 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco DV-3 User manual

Tyco

Tyco DV-3 User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco Star Hydrus S30 User manual

Tyco

Tyco Star Hydrus S30 User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco ACC-1 User manual

Tyco

Tyco ACC-1 User manual

Tyco 8700 Series User manual

Tyco

Tyco 8700 Series User manual

Tyco HSM2955 User manual

Tyco

Tyco HSM2955 User manual

Tyco BFV-N User manual

Tyco

Tyco BFV-N User manual

Tyco STAR Model A User manual

Tyco

Tyco STAR Model A User manual

Tyco MULTIMATIC F470H User manual

Tyco

Tyco MULTIMATIC F470H User manual

Tyco DPV-1 User manual

Tyco

Tyco DPV-1 User manual

Tyco DV-5 Operating and maintenance instructions

Tyco

Tyco DV-5 Operating and maintenance instructions

Tyco DN100 User manual

Tyco

Tyco DN100 User manual

Tyco AV-1-300 User manual

Tyco

Tyco AV-1-300 User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Popular Control Unit manuals by other brands

mr. steam TEMPO/PLUS owner's manual

mr. steam

mr. steam TEMPO/PLUS owner's manual

Keyautomation CT102B Instructions and warnings for installation and use

Keyautomation

Keyautomation CT102B Instructions and warnings for installation and use

SMART-AVI SMTCP-2 user manual

SMART-AVI

SMART-AVI SMTCP-2 user manual

red lion PAXCDL user manual

red lion

red lion PAXCDL user manual

Heath Zenith Motion Sensor Light Control SH-5412 owner's manual

Heath Zenith

Heath Zenith Motion Sensor Light Control SH-5412 owner's manual

Thomas Dudley DUDLEY PINTO quick start guide

Thomas Dudley

Thomas Dudley DUDLEY PINTO quick start guide

Delta DVP series instruction sheet

Delta

Delta DVP series instruction sheet

Paradox ZX16D quick start guide

Paradox

Paradox ZX16D quick start guide

Contec CPSN-SSI-4C Reference manual

Contec

Contec CPSN-SSI-4C Reference manual

Delta TECK II Technical data

Delta

Delta TECK II Technical data

AutomationDirect D0-DCM manual

AutomationDirect

AutomationDirect D0-DCM manual

Ublox ANNA-B4 Series System integration manual

Ublox

Ublox ANNA-B4 Series System integration manual

Ublox PAM-7Q Hardware Integration Manual

Ublox

Ublox PAM-7Q Hardware Integration Manual

SPX FLOW APV CU4plus AS-i instruction manual

SPX FLOW

SPX FLOW APV CU4plus AS-i instruction manual

KEBCO 00.F4.010-3009 instruction manual

KEBCO

KEBCO 00.F4.010-3009 instruction manual

Black Box 5 manual

Black Box

Black Box 5 manual

SIGMA TEK C-DIAS manual

SIGMA TEK

SIGMA TEK C-DIAS manual

Data Video RMC-260 instruction manual

Data Video

Data Video RMC-260 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.