
COVER
PLATE
RETAINER
ASSEMBLY
CUP
CEILING
SEAL
SHOWN
AIR
AND DUST
SEAL
LIP OF
COVER
FIGURE 4
OPTIONAL AIR AND DUST SEAL FOR THE ILLUSION (TY5521)
cannot be engaged with the Support
Cup or the Cover Plate/Retainer As-
sembly cannot be engaged sufficient-
ly to contact the ceiling, the Sprinkler
Fitting must be repositioned.
Care and
Maintenance
The TYCO ILLUSION, 11.2 K-factor,
Extra Large Orifice Concealed Pen-
dent Sprinklers must be maintained
and serviced in accordance with this
section.
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate
and the ceiling, as shown in Figure
2. This air gap is necessary for prop-
er operation of the sprinkler by allow-
ing heat flow from a fire to pass below
and above the Cover Plate to help as-
sure appropriate release of the Cover
Plate in a fire situation. If the ceiling is
to be repainted after the installation of
the Sprinkler, care must be exercised
to ensure that the new paint does not
seal off any of the air gap.
Factory painted Cover Plates must
not be repainted. They should be re-
placed, if necessary, by factory paint-
ed units. Non-factory applied paint
may adversely delay or prevent sprin-
kler operation in the event of a fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection sys-
tem main control valve for mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the prop-
er authorities and all personnel who
may be affected by this action must
be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without re-
installing the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association (e.g., NFPA 25), in
addition to the standards of any oth-
er authorities having jurisdiction. The
installing contractor or sprinkler man-
ufacturer should be contacted relative
to any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national codes.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assembly:
Specify: ILLUSION (TY5521), Ex-
tra Large Orifice Concealed Pen-
dent Sprinkler with (specify) temper-
ature rating and (specify) finish, P/N
(specify).
160°F (71°C) 212°F (100°C)
TY5521 50-711-1-160 50-711-1-212
Separately Ordered Cover Plate:
Specify: ILLUSION Cover Plate, (spec-
ify) temperature rating with (specify)
finish, P/N (specify).
139°F (59°C)(a) 165°F (74°C )(b)
Grey White (RAL9002)
. . . . . . . . . 56-892-0-135 56-892-0-165
Brass ....56-892-1-135 56 -892-1-165
Pure White (c) (RAL9010 )
. . . . . . . . . 56-892-3-135 56-892-3-165
Signal White (RAL9003)
. . . . . . . . . 56-892-4-135 56-892-4-165
Chrome...56-892-8-135 56-892-8-165
Brush Chrome
. . . . . . . . . 56-892-9-135 56-892-9-165
Custom...56-892-X-135 56-892-X-165
(a) For use with 160°F (71°C) sprinklers.
(b) For use with 212°F (100°C) sprinklers.
(c) Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
TFP184
Page 4 of 4