manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco ESFR-22 User manual

Tyco ESFR-22 User manual

Page 1 of 4 APRIL 2022 TFP321
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/model-
esfr-22_4-k-pen-early-sup-fast-res
Model ESFR-22
22.4 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Sprinkler
Identification
Number
See Table A
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
LPCB Certified
EAC Approved
Finish
Natural Brass
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Compression Screw � � � � � � � � � � Stainless Steel
Hook � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Strut� � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Link Assembly� � � � � � � � � � � � � � � � Solder, Nickel
Button �������������� Copper/Stainless Steel
Sealing Assembly ��Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder� When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water�
kler protection of the following storage
applications:
• Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• Uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• Some storage arrangements of rub-
ber tires, roll paper, flammable liq-
uids, and aerosols
Note: The sprinklers are not limited to
these storage applications.
For more specific criteria, see the Tech-
nical Data section, Table A, and the
applicable design standard�
The Model ESFR-22 Sprinklers can
eliminate the use of in-rack sprinklers
when protecting high-piled storage of
specific materials up to the following
heights:
• NFPA: 40 ft (12,2 m) with ceilings up
to 45 ft (13,7m)
• FM: 45 ft (13,7 m) with ceilings up to
50 ft (15,2 m)
For more specific criteria, see Table B
and the applicable design standard�
NOTICE
The TYCO Model ESFR-22 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any authorities
having jurisdiction such as FM Global.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM installation standard, or other appli-
cable standard, must be referenced
to ensure applicability and to obtain
complete installation guidelines. The
general guidelines in this technical data
sheet are not intended to provide com-
plete installation criteria.
General
Description
The TYCO Model ESFR-22 Pendent
Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers with a
nominal K-factor of 22�4� The sprinkler
assembly is shown in Figure 1� The
sprinklers’ suppression-mode design is
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage�
The Model ESFR-22 Sprinklers are
primarily used for ceiling-only sprin-
TFP321
Page 2 of 4
Design
Criteria
Use the following guidelines about the
TYCO Model ESFR-22 Sprinklers for
quick reference�
The National Fire Protection Associa-
tion (NFPA) and FM Global provide
installation standards that must be
used to properly design an automatic
sprinkler system utilizing ESFR Sprin-
klers� The guidelines provided by NFPA
and FM Global may differ� Conse-
quently, the appropriate standard must
be used for a given installation�
In all cases, the appropriate NFPA or
FM Global installation standard must be
referenced to ensure applicability and
to obtain complete installation guide-
lines� The guidelines are not intended
to provide complete installation criteria�
For more information, see Table B�
Design Guidelines
Roof Construction
Applications include unobstructed
or obstructed constructions, such as
smooth ceilings, bar joists, beam and
girder, or similar constructions�
Note: Where the depths of the
solid structural members, for
example, beams and stem, exceed
12 in. (302 mm), install ESFR Sprinklers
in each channel formed by the struc-
tural members.
Ceiling Slope
Maximum 2 in� rise for 12 in� run (16�7%)
Maximum Coverage Area
100 ft2(9,3 m2)
Minimum Coverage Area
64 ft2(5,8 m2) per NFPA 13 / FM Global
2-0
Maximum Spacing
• 12 ft (3,7 m) for building heights up
to 30 ft (9,1 m)
• 10 ft (3,1 m) for building heights
greater than 30 ft (9,1 m)
Note: In some cases, installation stan-
dards permit a greater spacing.
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in� (914 mm)
Deflector-to-Ceiling Distance
NFPA: 6 to 18 in� (152 to 457 mm)
Centerline of Thermal Sensing
Element-to-Ceiling Distance
FM Global: Refer to FM Global 2-0 for
Storage Sprinklers�
Installation
The TYCO Model ESFR-22 Sprinklers
must be installed in accordance with
the following instructions�
General Instructions
Damage to the fusible link assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only (that is, do not apply pres-
sure to the fusible link assembly), and
by using the appropriate sprinkler
wrench� Failure to do so can lead to an
unstable link assembly and premature
activation of the sprinkler� Damaged
sprinklers must be replaced�
A leak-tight 1 in� NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 0 to 30
lb-ft (26,8 to 40,2 N∙m)� Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler�
TABLE A
MODEL ESFR-22 PENDENT SPRINKLER
TECHNICAL DATA
Item Description
Sprinkler Identication Number (SIN) TY8223
K-factor, gpm/psi½(Lpm/bar½)22�4 gpm/psi½(320 Lpm/bar½)
Thread Size 1 in� NPT or ISO 7-R 1
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Components:
WRENCH
FLATS
3-13/16"
(96,8 mm)
9/16"
(14,3 mm)
NOMINAL
MAKE-IN
1-13/16"
(46,0 mm)
CENTERLINE
THERMAL
SENSING
ELEMENT
TEMPERATURE
RATING
-Hook4
-
7
8-
5
6
-
-Link Assembly
Sealing
Assembly
Button
Strut
-
2
3-
1-
Compression
Screw
Deector
Frame
1" NPT
2" (50,8 mm)
2
3
6
4
5
8
1
7
FIGURE 1
MODEL ESFR-22 (TY8223) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 22.4 K-FACTOR
TFP321
Page 3 of 4
Installing the Sprinkler
To install the sprinkler, perform the fol-
lowing steps:
Note: Install the Model ESFR-22 Pendent
Sprinkler in the pendent position as shown
in Figure 2.
Step 1. Handle the Model ESFR-22
Sprinkler only by the frame arms�
Apply pipe-thread sealant to the sprin-
kler� Hand-tighten the sprinkler into the
sprinkler fitting, and do not apply pres-
sure to the link assembly�
TABLE B
MODEL ESFR-22 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Step 2. Use only the W-Type 1 Sprin-
kler Wrench as shown in Figure 2 to
install the sprinkler� Fully engage or
seat the wrench recess on the sprin-
kler wrench flats as shown in Figure 1
and wrench-tighten�
Step 3. After installation, inspect the
link assembly of each sprinkler for
damage� In particular, verify that the
link assembly and hook are positioned
as shown in Figures 1 and 2, and that
the link assembly is not bent, creased,
or forced out of normal position in any
way� Replace damaged sprinklers�
Storage Type NFPA FM Global
Sprinkler Type ESFR Storage
Response Type FR QR
System Type Wet Wet
Temperature Rating 16 5° F ( 74°C )
212°F (100°C)
16 5° F ( 74°C )
212°F (100°C)
Open Frame (for example, no solid shelves) Single, Double,
Multiple-Row, or Portable Rack Storage of Class I-IV and
Group A or B Plastics
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) N/A N/A
N/A – Not Applicable
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
FIGURE 2
W-T YPE 1
SPRINKLER WRENCH
TFP321
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The TYCO Model ESFR-22 Pendent
Sprinklers must be maintained and ser-
viced in accordance with the following
information�
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action�
Sprinklers found to be leaking or exhib-
iting visible signs of corrosion must be
replaced�
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory�
Modified sprinklers must be replaced�
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush�
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation� Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or any other
action, must be replaced�
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with the following docu-
ments and standards:
• This technical data sheet
• Applicable standards of the National
Fire Protection Association such as
NFPA 25
• Standards of any authorities having
jurisdiction
Contact the installing contractor
or product manufacturer with any
questions�
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes�
Limited
Warranty
For warranty terms and conditions, visit
www�tyco-fire�com�
Ordering
Procedure
Contact your local distributor for avail-
ability� When placing an order, indicate
the full product name and Part Number
(P/N)�
Sprinkler Assemblies with
1 in. NPT Thread Connection
Specify: Model ESFR-22 (TY8223),
K=22�4, Early Suppression, Fast
Response Pendent Sprinkler with
1 in� NPT thread connection, (specify)
temperature rating, Natural Brass, P/N
(specify):
16 5° F ( 74° C ) ������������������58-464-1-165
212°F (100°C) �����������������58- 464-1-212
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-22 (TY8223),
K=22�4, Early Suppression, Fast
Response Pendent Sprinkler with
ISO 7-1 thread connection, (specify)
temperature rating, Natural Brass,
P/N (specify):
16 5° F ( 74° C ) ������������������58-465-1-165
212°F (100°C) �����������������58-465-1-212
Sprinkler Wrench
Specify: W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025

This manual suits for next models

1

Other Tyco Irrigation System manuals

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco FSC 80 K-factor User manual

Tyco

Tyco FSC 80 K-factor User manual

Tyco AQUAMIST ULF AM27 User manual

Tyco

Tyco AQUAMIST ULF AM27 User manual

Tyco 16.8 K-factor User manual

Tyco

Tyco 16.8 K-factor User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco RFIII User manual

Tyco

Tyco RFIII User manual

Tyco TY-FRL-5.6 Series User manual

Tyco

Tyco TY-FRL-5.6 Series User manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco Issue D Quartzoid TY3191 User manual

Tyco

Tyco Issue D Quartzoid TY3191 User manual

Tyco Gem PSN 56-701-9-010 User manual

Tyco

Tyco Gem PSN 56-701-9-010 User manual

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco FASTFLEX YN25 User manual

Tyco

Tyco FASTFLEX YN25 User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco SW-20 User manual

Tyco

Tyco SW-20 User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco Ultra K17 K-factor User manual

Tyco

Tyco Ultra K17 K-factor User manual

Tyco LFII Series Guide

Tyco

Tyco LFII Series Guide

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Popular Irrigation System manuals by other brands

Rain Click Plus manual

Rain

Rain Click Plus manual

Autopot 9Pot system Set-up guidelines

Autopot

Autopot 9Pot system Set-up guidelines

Reliable F1FR56 owner's manual

Reliable

Reliable F1FR56 owner's manual

Welcare AQUA-PULSE WATER FLOSSER WAWF100 Instruction manual &  warranty information

Welcare

Welcare AQUA-PULSE WATER FLOSSER WAWF100 Instruction manual & warranty information

Irritrol IBOC Plus Programming and Operating Quick Reference

Irritrol

Irritrol IBOC Plus Programming and Operating Quick Reference

Rain Bird isa 300/400 Installation, programming, and operation guide

Rain Bird

Rain Bird isa 300/400 Installation, programming, and operation guide

Johnson Controls tyco TY2335 manual

Johnson Controls

Johnson Controls tyco TY2335 manual

TOOLCRAFT 2388926 operating instructions

TOOLCRAFT

TOOLCRAFT 2388926 operating instructions

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Nelson PC-S3000 quick start guide

Nelson

Nelson PC-S3000 quick start guide

Nelson 3000 Series Assembly instructions

Nelson

Nelson 3000 Series Assembly instructions

Metabo Dry-running Sensor Hydrostop operating instructions

Metabo

Metabo Dry-running Sensor Hydrostop operating instructions

FLORABEST 273587 Assembly and Safety Advice

FLORABEST

FLORABEST 273587 Assembly and Safety Advice

Eden 94112-EDAMZ manual

Eden

Eden 94112-EDAMZ manual

Viking MICROFAST VK327 Care and Handling

Viking

Viking MICROFAST VK327 Care and Handling

AQUAvalve 16Pot system Set-up guidelines

AQUAvalve

AQUAvalve 16Pot system Set-up guidelines

KÜBLER SPORT PERROT RollcarT-V Assembly and use instruction

KÜBLER SPORT

KÜBLER SPORT PERROT RollcarT-V Assembly and use instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.