
TFP171
Page 4 of 12
Installation
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings. A leak-tight
1/2 in. NPT sprinkler joint should
be obtained by applying a mini-
mum-to-maximum torque of 7 ft-lb
to 14 ft-lb (9,5 N·m to 19,0 N·m). A
leak tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 ft-lb to 20 ft-lb (13,4 N·m to
26,8N·m). Higher levels of torque can
distort the sprinkler inlet and cause
leakage or impairment of the sprin-
kler. Do not attempt to compensate for
insufcient adjustment in the escutch-
eon plate by under or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler tting to suit.
Series TY-FRB Upright and Pendent
Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Step 1. Install pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench as shown in
Figure14. Apply the sprinkler wrench
to the sprinkler wrench ats as shown
in Figure 1 to Figure 5.
Series TY-FRB Recessed Pendent
Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions:
Step 1. After installing the Style 10, 20,
30, or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler tting.
Step 2. Tighten the sprinkler into the
sprinkler tting using only the W-Type 7
Recessed Sprinkler Wrench as shown
in Figure 15. Apply the sprinkler wrench
to the sprinkler wrench ats as shown
in Figure 1 to 4.
Step 3. After the ceiling is installed
or the nish coat is applied, slide on
the Style 10, 20, 30, or 40 closure over
the Series TY-FRB Recessed Pendent
Sprinkler and push the closure over the
mounting plate until its ange comes in
contact with the ceiling.
Care and
Maintenance
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section. Before closing a re
protection system main control valve
for maintenance work on the re pro-
tection system that it controls, obtain
permission to shut down the affected
re protection systems from the proper
authorities and notify all personnel who
may be affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a re situation.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be taken to avoid damage
to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. For more information, see
Installation section.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufac-
turer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see Installation section.
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections according to NFPA
25 should sufce. Inspections of cor-
rosion-resistant sprinklers are recom-
mended at close range, instead of from
the oor level per NFPA. Inspection at
close range can better determine the
exact sprinkler condition and the long-
term integrity of the corrosion-resistant
material, which can be affected by the
corrosive conditions present.