ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1/8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap-
plied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.
If attempts to retouch the wax coating
with complete coverage are unsuc-
cessful, additional wax can be ordered
in the form of a wax stick (the end of
which is color coded). Only the correct
color coded wax is to be used, and
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the
steel rod heated as previously de-
scribed, touch the rod to the area re-
quiring additional wax with the rod an-
gled downward, and then touch the
wax stick to the rod approximately
one-half inch away from the area re-
quiring retouching. The wax will melt
and run down onto the sprinkler.
The Series TY-L Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. After installing the Style 20 or
30 Mounting Plate, as applicable, over
the sprinkler threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
10 Recessed Sprinkler Wrench (Ref.
Figure 8). With reference to Figure 1,
2, or 3, the W-Type 10 Recessed Sprin-
kler Wrench is to be applied to the
sprinkler wrenching flanges.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 20 or 30 Clo-
sure over the Series TY-L Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling.
Care and
Maintenance
TheSeriesTY-LSprinklersmustbe
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Page6of8 TFP110