Do not pull the cover plate relative to
the enclosure. Separation may result.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
ed or over heated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers -before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the cover plate assembly.
If a cover plate assembly becomes
dislodged during service, replace it
immediately.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: Model CHEC, 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinkler, 155°F (68°C),
P/N 51-396-1-155
Separately Ordered Cover Plate
Specify: 139°F (59°C) Model CHEC
Cover Plate Assembly with Specify
Finish, P/N (specify):
Pure White (RAL 9010)* . . . . . . . . .56-396-3-135
Signal White (RAL 9003) . . . . . . . .56-396-4-135
Chrome......................56-396-9-135
Custom......................56-396-X-135
* Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
NOTICE
As long as the sprinkler strap (see
Figure 1) or the protective cap (see
Figure 4) remains in place, the system
is considered to be “Out of Service”.
Step 6. After the wall has been com-
pleted with the nominal 2-1/2 in. (63,5
mm) diameter mounting hole and in
preparation for installing the cover plate
assembly, remove and discard the pro-
tective cap and the sprinkler strap. If
the sprinkler has been damaged in any
way including accidental over spray
from nishing the wall, replace the
entire sprinkler/support cup assembly.
NOTICE
For information and instructions about
removing the sprinkler strap, refer to
technical data sheet TFP700.
Step 7. Push the cover plate/retainer
assembly into the support cup, and as
necessary, make the nal adjustment
of the cover plate with respect to the
wall by turning the cover plate/retainer
assembly clockwise until its ange just
comes in contact with the wall.
If it becomes necessary to remove
the cover plate, it can be removed by
unscrewing in a counter-clockwise
direction.
If the cover plate/retainer assembly
cannot be engaged with the support
cup or the cover plate/retainer assem-
bly cannot be engaged sufciently to
contact the wall, the sprinkler tting
must be repositioned.
Care and
Maintenance
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, permission to shut down the
affected re protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualied Inspection Service in accor-
dance with local requirements and/or
national codes.
When properly installed, there is a
nominal 5/32 in. (4,0 mm) air gap
between the lip of the cover plate and
the wall, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the wall is to
be repainted after the installation of
the sprinkler, care must be exercised
to ensure that the new paint does not
seal off any of the air gap.
Factory painted cover plates must not
be repainted. They should be replaced,
if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a re.
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
CAP
FIGURE 3
W-TYPE 7 SPRINKLER
WRENCH
FIGURE 4
DISPOSABLE PROTECTIVE
CAP