Tyco D Quartzoid TY3191 User manual

General
Description
The Issue D, 5.6 and 8.0 K-factor,
Upright and Pendent Sprinklers de-
scribed in this data sheet are standard
response - standard coverage, 11 mm
glass bulb type spray sprinklers de-
signed for use in light, ordinary, or
extra hazard, commercial occupan-
cies where high ambienttemperatures
may be encountered.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tantcoatedsprinklershavepassedthe
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect tothesuitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemicaltowhichthesprinklers will be
exposed.
WARNINGS
The Issue D Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards ofany otherauthorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3191 - Upright 5.6K, 1/2"NPT
TY3296 - Pendent 5.6K, 1/2"NPT
TY4191 - Upright 8.0K, 3/4"NPT
TY4292 - Pendent 8.0K, 3/4"NPT
TY3191 is a redesignation for G1036.
TY3296 is a redesignation for G1040.
TY4191 is a redesignation for G1136.
TY4292 is a redesignation for G1140.
Technical
Data
Approvals
UL and C-UL Listed.
FM Approved.
(Refer to Table A for complete ap-
proval information including corrosion
resistant status.)
Maximum Working Pressure
175 psi (12,1 bar).
Discharge Coefficient
K=5.6GPM/psi
1/2 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)
Temperature Ratings
RefertoTableA.
Finishes
RefertoTableA
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
Bulb (11mm dia.) . . . . . . . Glass
Bulb Seats . . . . . . . . . . Bronze
Spacer . . . . . . . . . . . . Bronze
Pin . . . . . . . . . . . . . . Bronze
Button . . . . . . . . . . . . Bronze
Spring Plates . . . . . . . . Inconel
Gaskets . . . . . . . . . . . Copper
Issue D Quartzoid
®
— 5.6 and 8.0 K-factor
High Temperature, Upright and Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 4 TFP690
DECEMBER, 2007
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
tooperateina firesituationor cause
it to operate prematurely.

Page2of4 TFP690
FIGURE 1
STANDARD RESPONSE ISSUE D UPRIGHT (TY3191) AND PENDENT (TY3296) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
FIGURE 2
STANDARD RESPONSE ISSUE D UPRIGHT (TY4191) AND PENDENT (TY4292) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
650°F/343°C
650°F/343°C
(12,7 mm)
NOMINAL
UPRIGHT
PlatesSprinkler;
1/2"
(74,6 mm)
CROSS SECTION
NOMINAL
MAKE-IN
(12,7 mm)
MAKE-IN
1/2"
PENDENT
(79,4 mm) 5
3-1/8"
4
3
11
SSP-1 for
Upper Bulb
Lower Bulb
Temperature rating
is indicated on Lower
Bulb Seat.
*
Seat
2
*
-
3
4-
7
8
9
Sprinkler
Seat
Pendent Lower
Bulb
Gasket
Gasket
Bulb
-
9
-
-
10
11
2-15/16" 10
NPT
3/4"
Components:
SSU-3 for
-
2
1
6
-
1
Upright
Deflector,
Frame
Spring
Spacer
Button
Pin
-
7-
8
-
6-
5
WRENCHINGAREA
UPRIGHT CROSS SECTIONPENDENT
2-15/16"
(74,6 mm)
(79,4 mm)
3-1/8"
1
6
7
8
9
2
10
5
3
11
4
NPT
1/2"
NOMINAL
MAKE-IN
7/16"
(11,1 mm)
(11,1 mm)
NOMINAL
MAKE-IN
7/16"
Temperature rating
is indicated on Lower
*
650°F/343°C
650°F/343°C
Upright
Pendent
Upper Bulb
Spring
-Spacer7 -
-
-
-
10
11
8
9
Gasket
Bulb
Gasket
Lower
-
-
-
5
6
3
Button
Pin
SSP-1 for
-
-
Components:
1
2Frame
Deflector,
SSU-3 for
Sprinkler;
Sprinkler
*
Seat
Plates
Bulb
Bulb Seat.
4-Lower Bulb
Seat
WRENCHINGAREA

Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Issue D Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM’s Loss Prevention
Data Sheets).
Installation
The Issue D Sprinklers must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present.The diameter of the
air bubble is approximately 1/4 inch
(6,4 mm).
A 1/2 inch NPT sprinkler joint should
be obtained with a minimum to maxi-
mum torque of 7 to 14 ft.lbs. (9,5 to
19,0 Nm). A 3/4 inch NPT sprinkler
joint should be obtained with a mini-
mum to maximum torque of 10 to 20
ft.lbs. (13,4 to 26,8 Nm). Higher levels
of torque may distort thesprinkler inlet
and cause leakage or impairment of
the sprinkler.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
11 Sprinkler Wrench (Ref. Figure 3).
With reference to Figures 1 and 2, the
W-Type 11 Sprinkler Wrench is to be
applied to the wrenching area.
Care and
Maintenance
The Issue D Sprinklers must be main-
tained and serviced in accordance
with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
itcontrols,permissiontoshutdownthe
affectedfireprotection system mustbe
obtained from the proper authorities
and all personnelwho may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.Also,replaceanysprinklerthat
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommendedtobeinitiallyperformedfor
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify theintegrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
TFP690 Page 3 of 4
TYPE TEMP. BULB
LIQUID NATURAL
BRASS CHROME
PLATED
SPRINKLER FINISH (See Note 4)
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Where Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are
UL and C-UL Listed as Corrosion Resistant Sprinklers.
N/A: Not Available
TABLE A, LABORATORY LISTINGS AND APPROVALS
LEAD
COATED
5.6
1/2"
NPT
PENDENT
(TY3296)
and
UPRIGHT
(TY3191)
8.0
3/4"
NPT
PENDENT
(TY4292)
and
UPRIGHT
(TY4191)
400°F/204°C
500°F/260°C Black
Black
1, 2
K
400°F/204°C
500°F/260°C
650°F/343°C
Black
Black
Black
1, 2, 3 1, 2
1, 2
3
FIGURE 3
W-TYPE 11 SPRINKLER
WRENCH
"LARGE FRAME
SPKR" END FOR
QUARTZOID
ONLY USE
SPRINKLERS

tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
Automaticsprinkler systems shouldbe
inspected, tested, and maintained bya
qualified Inspection Service in accord-
ance with local requirements and/or
national codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects inmate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeensubjecttomisuse,improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizesanypersonto assumeforit,
any other obligation in connection with
the sale of products or parts of prod-
ucts.TFBPshall not beresponsiblefor
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,specialor consequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityand fitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Issue D
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table B).
Sprinkler Wrench:
Specify: W-Type 11 Sprinkler Wrench,
P/N 56-452-1-001.
Page4of4 TFP690
© 2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
P/N 51 — XXX — X — XXX
500°F/260°C500
TEMPERATURE
RATING
400°F/204°C4001
SPRINKLER
TABLE B
PART NUMBER SELECTION
ISSUE D UPRIGHT AND PENDENT SPRINKLERS
650°F/343°C
(5.6K Only)
650
NATURAL BRASS
9
MODEL/SIN
CHROME PLATED
7LEAD COATED136 8.0K UPRIGHT (3/4"NPT)
140 8.0K PENDENT (3/4"NPT)
5.6K UPRIGHT (1/2"NPT)
5.6K PENDENT (1/2"NPT)
036
040 TY3296
TY3191
TY4292
TY4191
This manual suits for next models
3
Other Tyco Irrigation System manuals

Tyco
Tyco EC-11 Series User manual

Tyco
Tyco EC-5 Series User manual

Tyco
Tyco DS-2 Series User manual

Tyco
Tyco TY-L Series User manual

Tyco
Tyco TY-L Series User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco TY7158 User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco ELO-231 Series User manual

Tyco
Tyco RFII-C Series User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco TY-L Series User manual

Tyco
Tyco F950 User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco TY-QRF-5.6 User manual

Tyco
Tyco F690 User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco CC3 User manual