Unipower DPBF1U Series User manual

Page 2
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
Contents
1.0 INTRODUCTION ..................................................................................................................4
2.0 FEATURES & OPTIONS.......................................................................................................5
3.0 PRODUCT LINE....................................................................................................................5
4.0 SAFETY & INDUSTRY STANDARDS................................................................................6
5.0 WARRANTY (summary) .......................................................................................................6
6.0 DESCRIPTION OF OPERATION.........................................................................................7
7.0 SPECIFICATIONS.................................................................................................................8
8.0 CONFIGURATION................................................................................................................9
9.0 FRONT PANEL DESCRIPTION.........................................................................................11
10.0 UNPACKING AND INSPECTION......................................................................................14
11.0 INSTALLATION..................................................................................................................14
12.0 SETUPAND TESTING .......................................................................................................15
REV DESCRIPTION CHK’d & APPR’d / DATE
5 PCO# 45395 MM / 07-31-19

Page 3
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
FIGURES
Figure 1. DPGF1U & DPBF1U Front Views 4
Figure 2. Block Diagram 7
Figure 3. DPBF1U Front Panel View 11
Figure 4. DPGF1U Front Panel View 11
Figure 5. Input Bus Bar Detail 11
Figure 6. Output Barrier Strip Detail 12
Figure 7. Alarm Contact & Ground Detail 13
Figure 8. Series Connection of Multiple Panels 14
TABLES
Table 1. Basic Congurations 5
Table 2. LED State Denitions 7
Table 3. GMT Fuse Values 9
Table 4. Input Cable Lug Sizes & Types 12
Table 5. Alarm Relay Contacts 13

Page 4
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
OPERATING MANUAL
DPBF1U & DPGF1U SERIES
DC POWER DISTRIBUTION PANELS
1.0 INTRODUCTION
These distribution panels provide protected power distribution to telecommunication equipment.
They oer fuse or circuit breaker positions on the A and B sides of the panel. The A and B loads
of the distribution panel are totally independent and isolated from each other. There is a green/red
LED for each load to indicate normal operation or an open circuit due to a blown fuse or tripped
circuit breaker.
The panels areonly 1.75 inches (1mounting position) high tominimize rack space andcan be mounted
in either a 19- or 23-inch relay rack with corresponding brackets. They can be mounted from the
front of the rack with osets every ¼-inch from front to back to align with existing rackmounted
equipment.
Figure 1 shows the two series of panels. The rst is the DPGF1U Series which has 4 or 6 GMT
fused circuits on bothAand B sides. The second is the DPBF1U Series with up to 4 circuit breaker
circuits on both A and B sides.
NO-C-NC NO-C-NC
B
A
T
R
T
N
1 2 3 4 5 6 FA
1 5 6 B
A
T
R
T
N
1 2 3 4 5 6 FA
1 5 6
DPGF1U: GMT Fuse Distribution Panel
NO-C-NC NO-C-NC
ON
I
O
OFF
BAT
RTN
1 2 3 4
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
BAT
RTN
1 2 3 4
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
DPBF1U: Circuit Breaker Distribution Panel
Figure 1. DPGF1U & DPBF1U Front Views
The panels can be congured for 12, 24 or 48 volts with either positive or negative ground. Because
the A and B sides are independent and isolated, they can be congured separately. For example,
theAside can be 48V positive ground and the B side can be 24V negative ground. The voltage and
polarity of each side must be congured at the factory. All models are reverse polarity protected.
Each bus (Aand B) has a green/red visual alarm and one Form C relay alarm contact for connection
to external audible or visual alarms.

Page 5
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
2.0 FEATURES & OPTIONS
2.1 The following is a summary of the important features of the Series.
Thin Height: 1.75 inches (1RU)
19 or 23-Inch Rack Mounting
Dual A/B Loads
Current Capacity: 80 to 150A per Load (Depends on Model)
Operating Voltage: 12, 24 or 48VDC
Positive or Negative Ground
Red/Green LED Indicators
1 Form C Relay Contact per Bus
Protection: GMT Fuses or Magnetic Circuit Breakers
Independent and Isolated Loads
Input Connections: Crimp Type Lugs
Output Connections: Barrier Terminal Strips
Reverse Polarity Protected
2.2 Options. There are three standard options available:
Option C - Clear plastic rear cover to protect connectors and wiring from damage. This
option will be supplied automatically unless it is specicially requested to be deleted.
Option S - This option internally links the A bus to the B bus so that a fully congured unit
canbesuppliedDCfromasinglefeed. TheAandBsideshavethesamevoltageandpolarity.
3.0 PRODUCT LINE
The following table shows the 3 basic conguration that are available for each type of panel. ‘x’
denotes the voltage and polarity. Full conguration details are given in section 8.
BASE MODEL INPUT
FEEDS MAX. #
BREAKERS / FUSES AMPS
EACH FEED TOTAL
AMPS
DPBF1U-Ax 14 Breakers 150 150
DPBF1U-Ax-Bx-S 8 Breakers 150 150
DPBF1U-Ax-Bx 2 4 + 4 Breakers 96 192
DPGF1U-Ax 14 or 6 Fuses 80 80
DPGF1U-Ax-Bx-S 8 or 12 Fuses 80 80
DPGF1U-Ax-Bx 2 4 or 6 + 4 or 6 Fuses 64 128
Table 1. Basic Congurations

Page 6
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
4.0 SAFETY & INDUSTRY STANDARDS
4.1 DPBF1U&DPGF1USeries powerdistribution panelsmeet thefollowing safetyrequirements:
STANDARD
UL60950-1, 2nd Edition
CSA22.2 No. 60950-1, 2nd Edition
EN60950-1, 2nd Edition
4.2 DPBF1U&DPGF1USeriespowerdistributionpanels areCEmarkedtoindicateconformance
to the European Union’s Low Voltage Directive.
4.3 These Distribution Panels operate at voltages that could potentially be hazardous.
Furthermore, inadvertent short circuiting of the system battery and/or rectier by mis-
connection or other error could be harmful. This product should be handled, tested and
installed only by qualied technical persons who are trained in the use of power systems
and are well aware of the hazards involved.
4.4 When operating this Distribution Panels the chassis ground terminal must be connected to
the system frame ground or other proper safety ground for the protection of personnel.
4.5 All connections to the Distribution Panels should be carefully checked for errors before
applying power to them.
4.6 The internal voltages may be at hazardous potentials. The top cover should not be removed.
There are no user-serviceable components in these units. Removing the top cover will void
the warranty.
5.0 WARRANTY (summary)
DPBF1U & DPGF1U Series power distribution panels are warranted for two (2) years from date of
shipment against defects in material and workmanship. This warranty does not extend to products
which have been opened, altered or repaired by persons other than persons authorized by the
manufacturer or to products which become defective due to acts of God, negligence or the failure
of customer to fully follow instructions with respect to installation, application or maintenance.
For a complete text of UNIPOWER’s warranty conditions please request a copy from your local
Sales Oce.

Page 7
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
6.0 DESCRIPTION OF OPERATION
6.1 Power Distribution Circuits. A simplied schematic diagram of the distribution panels
is shown in Figure 2. The battery input to each load connects to a high-current copper bus
bar from which the individual fuses or circuit breakers distribute power to the loads. The
return input connects to a similar bus bar to which the individual loads terminate. The A
and B loads are totally independent and isolated with the exception of models incorporating
the ‘S’ option.
CIRCUIT
BREAKERS
or
GMT FUSES
BATT. BATT.
INPUT
RET.
INPUT
RET.
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
LOADS LOADS
1 2 3... N N ...3 2 1
A SIDE
ALARM
CIRCUITS
b SIDE
ALARM
CIRCUITS
A SIDE B SIDE
-S OPTION
-S OPTION
Figure 2. Block Diagram
6.2 Alarm Circuits. The alarm circuits detect a tripped circuit breaker or blown and, in this
event, turn on the red part of the LEDs. The alarm circuits also each drive Form C relay
contacts. If one or more circuits open or if there is an input power failure, the relays are
de-energized and the contacts are used to control external audible or visual alarms. The A
and B alarm circuits are also independent and isolated from each other.
LED & RELAY STATE MEANINGS
LED State Relay State Meaning
Green Energized (N.O. is closed) OK
Red De-energized
(N.O. is open)
Breaker Trip
or
Breaker OFF
or
Fuse Blown
OFF No Input Power
Table 2. LED State Denitions

Page 8
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
7.0 SPECIFICATIONS
The following specications are typical at 25°C unless otherwise noted.
INPUT / OUTPUT
Panel Capacity ...........................................See Panel Conguration Table
Conguration
DPBF1U
Single Bus ................................................................ 1 to 8 Breakers
Dual Bus..........................................................1 to 4 Breakers Each
DPGF1U
Single Bus ...........................................................1 to 12 GMT Fuses
Dual Bus.......................................................1 to 6 GMT Fuses Each
Breaker/Fuse Capacity1 ............................................................. ½A to 30A
Voltage2
24/48V Nominal.....................................................................21-60VDC
12V Nominal.......................................................................10.5-15VDC
Polarity................................................................................Polarity Neutral
ALARMS
Alarm Indicator .....................................................Dual-Color LED Per Bus
LED Status Indication........................................................Green = Normal
Red = Breaker/Fuse Trip/Open Alarm
O = No Power
Alarm Connections.............................One Form C Relay Contact Per Bus
SAFETY STANDARDS................................................UL60950-1 2nd Ed.
CAS22.2 No.950-1 2nd Ed., EN60950-1 2nd Ed.
ENVIRONMENTAL
Operating Temp. Range ..................................................... -10°C to +70°C
Storage Temp. Range........................................................ -40°C to + 85°C
Humidity........................................................0% to 95%, Non-Condensing
PHYSICAL SPECIFICATIONS
Case Material ......................................................................................Steel
Finish............................................................................Powder Coat Black
Dimensions, Inches (mm)..................................1.75 H x 19.00 W x 9.00 D
(44.5 x 483 x 229)
Weight .........................................................................10.30 lbs. (4.67 kg.)
Rack Mounting Width .........................................................19 or 23 Inches
CONNECTIONS
Input Connections.......................................Crimp Type Lug or ¼ - 20 Stud
Output Connections................................. Barrier Terminal Strips, No. 6-32
Chassis Ground Connection..................................................No. 8-32 Stud
Alarm Relay Connections...................Spring Clamp Terminals,16-26AWG
NOTES: 1. See tables for available breaker & fuse sizes.
2. See Ordering Guide to specify voltage.

Page 9
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
8.0 CONFIGURATION
8.1 DPGF1U Conguration Details
Example: DPGF1U-A1-4-B6-6 species
separately congured A and B
sections. TheA section is 24/48V
with 4 x 20A max. fuses. The B
section is 12V with 4 x 15A max.
plus 2 x 20A max. fuses.
CODE VOLTAGE & POLARITY
1 24/48V (polarity neutral)
6 12V (polarity neutral)
CODE FUSE CONFIGURATION
4 4 X 20A max.
6 4 x 15A max. / 2 x 20A max.
Model: DPGF1U-A □-□-B □-□
NOTES: 1. If section B is not used a blank panel is installed at the factory.
2. The sum of all fuse currents on either side must not exceed the total rating.
GMT FUSES
AMPS PART NUMBER COLOR
½ 401-1500-0010 Red Order fuses separately.
UNIPOWER recommends Bussman
fuses for this panel.
They may be ordered from
UNIPOWER using the part numbers
shown.
¾ 401-1500-0020 Brown
1 401-1500-0030 Gray
11/3401-1500-0040 White
2 401-1500-0050 Orange
3 401-1500-0060 Blue
5 401-1500-0070 Green
10 401-1500-0080 Red/White
12 401-1500-0090 Green/Yellow
15 401-1500-0110 Red/Blue
20 401-1523-0000 Green/White
DUMMY 401-1500-0100
Table 3. GMT Fuse Values

Page 10
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
8.2 DPBF1U Conguration Details
EXAMPLE:
DPBF1U-A1-B6 species separately
congured A and B sections.
The A section is 24/48V; the B section is
12V.
NOTE:
If section B is not used a blank panel is installed at the factory. The sum of all breaker currents
on either side must not exceed the total rating. When the ‘S’ option is specied each side of the
panel is limited to 75A (total 150A).
Model No.: DPBF1U-A -B --
CODE AMPS
F 1
G 2.5
H 5
I 10
J 15
K 20
L 25
M 30
STANDARD
BREAKERS
CODE OPTION
CFront Cover
(Clear Plastic)
CODE VOLTAGE & POLARITY
1 24/48V (polarity neutral)
6 12V (polarity neutral)
* A & B sides must be identical
voltage and polarity.
CODE OPTION
SSingle Bus 8-way *

Page 11
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
9.0 FRONT PANEL DESCRIPTION
9.1 Front View. Figures 3 and 4 show the front of the DPBF1U and DPGF1U distribution
panels respectively. Inputs are at the left and right ends of the back panel. Side A outputs
are at two rows of barrier terminal strips on the left side, and side B outputs are the same
on the right side. At the center of the back panel are two spring clamp terminal blocks for
the Form C relay contact outputs.
Below these is a chassis ground terminal.
NO-C-NC NO-C-NC
ON
I
O
OFF
BAT
RTN
1 2 3 4
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
BAT
RTN
1 2 3 4
ON
I
O
OFF
ON
I
O
OFF
ON
I
O
OFF
A SIDE B SIDE
Alarm LED A
A Side Breakers B Side Breakers
Alarm LED B
1234 1234
Alarm Contacts
A Input
¼-20 Studs
Ground
#8-32 Stud
B Outputs
#6-32
Terminal Strip
A Outputs
#6-32
Terminal Strip
B Input
¼-20 Studs
Figure 3. DPBF1U Front Panel View
NO-C-NC NO-C-NC
B
A
T
R
T
N
1 2 3 4 5 6 FA
1 5 6 B
A
T
R
T
N
1 2 3 4 5 6 FA
1 5 6
A SIDE B SIDE
Alarm LED A
A Side Fuses B Side Fuses
Alarm LED BAlarm Contacts
A Input
¼-20 Studs
Ground
#8-32 Stud
B Outputs
#6-32
Terminal Strip
A Outputs
#6-32
Terminal Strip
B Input
¼-20 Studs
Figure 4. DPGF1U Front Panel View
9.2 Input Connections. See Figure 5.The DC power inputs to the distribution panels are made
by means of crimp type lugs or direct connection to ¼-20 studs to two copper bus bars on
side A and side B. The upper bus bar is the battery connection (whether + or -) and the
lower bus bar is the return (whether + or -).
0.625”
1.48”
0.5”
0.34”
0.375”
0.65”
0.32”
Figure 5. Input Bus Bar Detail

Page 12
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
9.3 Crimp Type Lugs. A list of compatible crimp type lugs is shown in the following table
for AWG wire sizes from no. 1 to 8 and one- or two- hole lugs. These lugs can be ordered
directly from the manufacturer, Panduit Corp., using the model numbers shown in table 4.
Astandard kit of four two-hole crimp type lugs for no. 6AWG copper wire is available from
UNIPOWER. Order kit no. 775-1434-0000.
WIRE
AWG .25DIA.
HOLES PANDUIT CORP.
PART NUMBER UNIPOWER
PART NUMBER
81
2LCA8-14-L
LCD8-14A-L 625-1665-0010
625-1665-0110
61
2LCA6-14-L
LCD6-14A-L 625-1665-0020
625-1665-0120
41
2LCA4-14-L
LCD4-14A-L 625-1665-0030
625-1665-0130
21
2LCA2-14-Q
LCD2-14A-Q 625-1665-0040
625-1665-0140
11
2LCA1-14-E
LCD1-14A-E 625-1665-0050
625-1665-0150
Table 4. Input Cable Lug Sizes & Types
9.4 Output Connections. Output connections for A and B loads are shown in Figure 6. There
are 10 sets of barrier terminal strip connections for each side, A and B. The connections
are numbered to correspond with the numbers of the front panel breakers. The upper strip
connections are from the battery through the breakers; the lower strip connections are the
returns. Side B is on the left and side A on the right, as shown.
Each terminal is a no. 6-32 screw and is rated at 30 amperes. Wire sizes from no. 10 AWG
up to no. 22AWG may be used for connections. Figure 7 below shows detailed spacing of
the terminals.
When DPBF1U is tted with either 40A or 50A breakers the additional load rating is
accomodated by tting adaptors that bridge two barrier strip terminals and provide a single
#10-32 screw. Minimum wire size for these connections is 8 AWG.
A maximum of two high current breakers is allowed on each bus.
1 2 3 4 5 6 7 8 9 10
40-50A
LOADS
#10-32
1A to 30A
LOADS
#6-32
0.75
(19.1)
0.5
(12.7)
0.378
(9.60)
Figure 6. Output Barrier Strip Detail

Page 13
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
9.5 Form C Relay Contact Outputs. The center of the back panel has connections to the
Form C relay contact outputs for connection to external audible or visual alarm circuits.
See Figure 7.
Alarm
Contacts
Alarm LEDs
B Input
¼-20 Studs
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
A B
ALARM
Ground
8-32 Stud
A Side Breakers B Side Breakers
A Outputs
6-32 Terminal Strip
B Outputs
6-32 Terminal Strip A Input
¼-20 Studs
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
B SIDE A SIDE
NO-C-NC NO-C-NC
5
6
3
4
1
2
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
5
6
3
4
1
2
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
OFF
OON
I
15
17.12 (434.9)
1.74
(44.2)
REAR VIEW
FRONT VIEW
Case depth: 8.94 (227.1)
2.28
(57.8)
Clear Perspex
Safety Cover
Figure 7. Alarm Contact & Ground Detail
Connection is made via two Phoenix Contact spring clamp terminal blocks. ALM-B is
for the Form C relay contact of side B and ALM-A is for the Form C relay contact of side
A. The terminals, viewed from left to right, are the normally open (NO) common (C) and
normally closed (NC) contacts, respectively. See table 5 below.
PIN FUNCTION CONTACT SCHEMATIC
NC N.C. (normally closed)
RELAY
C
ONTACTS
OUTPUTS
N.C.
C
N.O.
C C (common)
NO N.O. (normally open)
Table 5. Alarm Relay Contacts
“Normally Closed” and “Normally Open” are dened with the distribution panel powered
and providing power to all outputs, i.e. no circuit breakers tripped.
The ratings of the relay contacts are 0.6A at 125VAC or 2A at 30VDC. The spring clamp
terminals accept wire sizes nos. 16 to 26 AWG.
When the input power is connected to a side (A or B), the Form C relay of that side is
energized. If there is either loss of input power, one or more circuit breakers trip or the relay
is de-energized, the normally open contacts close and the normally closed contacts open.
9.6 Chassis Ground Connection. Just below the Form C relay contact terminals is the chassis
ground terminal. This terminal is a no. 8-32 stud with a nut.
NOTE THAT IT IS ESSENTIAL THAT THIS TERMINAL IS CONNECTED TO THE
SYSTEM FRAME GROUND TO ENSURE SAFE OPERATION.

Page 14
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
10.0 UNPACKING AND INSPECTION
10.1 This power distribution panel was carefully tested, inspected and packaged for shipment
from our factory. The unit and circuit breakers are shipped separately. Upon receipt of the
unit it should be carefully unpacked and inspected for any damage in shipment.
10.2 If there is evidence of damage, do not attempt to test the unit. The freight carrier should
be notied immediately and a claim for the cost of the rectier system should be led with
the carrier for direct reimbursement. Be sure to include the model and serial number of the
damaged unit in all correspondence with the freight carrier. Also save the shipping carton
and packing material as evidence of damage for the freight carrier’s inspection.
10.3 UNIPOWER will cooperate fully in case of any shipping damage investigation.
10.4 Always save the packing materials for later use in shipping the unit. Never ship the rectier
system without proper packing.
11.0 INSTALLATION
11.1 Mounting. This distribution panel can be mounted in either 19- or 23-inch racks by using
the supplied reversible brackets. Mount it from the front of the rack using the correct osets
to align with existing rack-mounted equipment.
The bracket osets are every quarter inch from front to back.
11.2 Connections. Input connections should be made with one- or two-terminal crimp type lugs
using copper wire size from no. 1 to 8 AWG, depending on current and wire loop distance.
See Sections 9.2 and 9.3. Output connections are made to the barrier terminal strips. See
Section 9.4 and Figure 7.
NOTE: Single feed models with option S tted have both left and right side input bus
bars tted. It is only necessary to connect the input feed to one side for correct operation.
The unused side is directly connected to the live input feed and can be used for supplying
additional panels. See gure 8 below.
CAUTION:The total load must not exceed 80A for DPGF1U or 150A for DPBF1U on any
one pair of bus bars in the chain.
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
SIDE A
SIDE B
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
ALM B ALM A
NO-C-NC NO-C-NC
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
SIDE A
SIDE B
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
ALM B ALM A
NO-C-NC NO-C-NC
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
SIDE A
SIDE B
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
ALM B ALM A
NO-C-NC NO-C-NC
80A/150A MAX. FEED
RETURN
Figure 8. Series Connection of Multiple Panels

Page 15
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
The Form C relay contact output connections are made to the spring clamp terminal blocks.
See Section 9.5. The chassis ground connection is made to the no. 8-32 stud. See Section
9.6. This safety ground connection should be made before operating the panel.
11.3 CheckingConnections. Carefully checkthe polarity of input connections to the distribution
panel and output connections to the load before operating the panel. Reverse connections
will not harm the distribution panel as reverese polarity protection is incorporated. However
it may cause serious harm to the load. Check to make sure that the chassis safety ground
connection is made. Make sure that all connections are clean and secure to minimize contact
resistance.
11.4 Rear Safety Cover. Once all of the above have been completed, t the clear plastic safety
cover to the back of the unit using the supplied mounting studs and screws. Instruction for
tting the mounting studs the panel are included in the accessory kit.
12.0 SETUP AND TESTING
12.1 It is not necessary to have the distribution panel mounted in a rack for initial testing. This
can be done on a bench. It is also not necessary to have loads connected to the panel for
this testing.
12.2 With the input power source o, connect the input wires to the A side of the distribution
panel. Connect ground to the chassis ground terminal. Insert all fuses into fuse holders or
set all circuit breakers to on.
12.3 Turn on the input power source. The A side LED should be green. If it is red, one of the
fuses is blown or a circuit breaker is tripped. If the LED is o, there is no input power to
the unit. Check the output voltage at each set of output terminals with a digital voltmeter.
12.4 With the A side LED green, use an ohmmeter to check the Form C relay contact outputs.
On the upper row of the wire-wrap terminals (sideA) measure the resistance between pins 1
and 2 and between pins 4 and 5. Both should read “short”. Measure the resistance between
pins 2 and 3 and between pins 5 and 6. Both should read “open”.
12.5 On the A side insert a blown fuse into fuse no. 1 position or trip circuit breaker no. 1. The
A side LED should turn red. On the upper row (side A) of wire wrap terminals, measure
the resistance between pins 1 and 2 and between pins 4 and 5. Both should read “open”.
Measure the resistance between pins 2 and 3 and between pins 5 and 6. Both should read
“short”. Replace the blown fuse with a good one or reset the circuit breaker.
12.6 On the A side check each succeeding fuse by replacing it with a blown fuse, or breaker by
tripping it, and verify that the LED turns red. It is not necessary to recheck the Form C
relay contacts.

Page 16
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: DPBF-DPGF-MAN Rev. 5 dpbf_dpgf-man-Rev5-0719.indd
This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for
consequences from printing errors or inaccuracies. Specications are subject to change without notice.
12.7 Repeat the same tests of Sections 12.2 through 12.6 on the B side of the distribution panel.
Refer to table 5.
12.8 The distribution panel may now be connected to its intended application.
12.9 If the distribution panel did not operate properly in the above tests, go back and double
check the connections and the polarity of the input source to make sure it is correct.
Product support can be obtained using the following addresses and telephone numbers.
Corporate oce:
UNIPOWER, LLC
210 N University Dr
Coral Springs, FL 33071
United States
Manufacturing facility:
UNIPOWER, LLC
65 Industrial Park Rd
Dunlap, TN 37327
United States
Manufacturing facility:
UNIPOWER Slovakia SRO
ZLATOVSKA 1279
Business Center 22
91105 Trencin, Slovakia
Phone: +1-954-346-2442
Toll Free: 1-800-440-3504
Web site – www.unipowerco.com
When contacting UNIPOWER, please be prepared to provide:
1. The product model number, spec number, S build number, and serial number
- see the equipment nameplate on the front panel
2. Your company’s name and address
3. Your name and title
4. The reason for the contact
5. If there is a problem with product operation:
• Is the problem intermittent or continuous?
• What revision is the rmware?
• What actions were being performed prior to the appearance of the problem?
• What actions have been taken since the problem occurred?
This manual suits for next models
1
Table of contents
Other Unipower Power Distribution Unit manuals

Unipower
Unipower DPB1U SERIES User manual

Unipower
Unipower DPP2U Series User manual

Unipower
Unipower DPP1U Series User manual

Unipower
Unipower Sageon II 200A (N+1) User manual

Unipower
Unipower UNIFLEX DRU1U Series User manual

Unipower
Unipower PDUAC3U-120-08 User manual

Unipower
Unipower DPP1U-A1 User manual

Unipower
Unipower 1U Series User manual

Unipower
Unipower Sageon II User manual