
1
92125r3 4-20mA Installation
www.vac.se - www.vacaccessories.com
V200 4/20mA Installation
1. Installthepotentiometer module(1)in
the designed section of the unit as
shown.Tighten thescrew thatsecures
the pot arm and spring.
Thepotgearwheel shouldbe aligned
andsecuredto thelargergearwheel(2).
2. Installthe4-20mA transmitter module(3)
into the designed position and tighten the
respectivescrews.
3. Whenusedfor the4-20mAfeedback,secure
thepotentiometer connector(4)tothe
transmitter(3).
NOTE: Make sure V200E/P has first been properly calibrated!
1. Powerupthe currentloop.
2. Connect a lowohmic amperemeter over thetest points(5).
3. Setthevalve/actuator to4mAor thezero
position.
4. Turnthefeedbackpotentiometer shaft(6)with
a screw driver until you read 3.5 - 4.5 mAon the meter.
5. Adjustthetrim potentiometer(7)markedzero
so that the meter reads 4mA.
6. Increase the input signal to a full
20mAor 100%.
7. Adjustthetrim potentiometer(8)marked
span until the meter reads 20mA.
8. Re-checkthezero position(4mA)and
make fine adjustments if necessary.
Avery basiccalibrationcan beaccomplished
without a meter, using the two LED’s.
Red LED lights up at 4mA, Green LED lights up at 20mA.
V200 4/20mA Calibration
CCV
7
5
8
Pot adjustment.eps
CCV
Power Supply: 7-30VDC
Load max 850 Ohms @ 24 VDC
6
6
6
5
CCV
CCV
1
24
4
1
3
2
3