Vacon NX ACTIVE FRONT END II Instructions for use

vacon®nx
ac drives
active front end ii (afe-ii)
arfiff05
application manual


Arfiff05 Standard AFE-II vacon • 3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Vacon Standard AFE-II application
INDEX Document code: DPD01979A
Software code: ARFIFF05V051
Date: 23.3.2018
VACON STANDARD AFE-II APPLICATION .......................................................................................3
1. Introduction...................................................................................................................................................................................... 6
1.1 Compatibility issues in parameters between versions.................................................................................................... 7
2. AFE Units ........................................................................................................................................................................................... 8
2.1 500 Vac units Air Cooled, 465-800 Vdc.............................................................................................................................. 8
2.2 690 Vac units Air Cooled, 640-1100 Vdc............................................................................................................................ 8
2.3 500 Vac units Liquid-Cooled, 465-800 Vdc........................................................................................................................ 9
2.4 690 Vac units Liquid-Cooled, 640-1100 Vdc...................................................................................................................... 9
2.5 690 Vac units Liquid –Cooled, 640-1200 Vdc..................................................................................................................10
3. Operation........................................................................................................................................................................................11
3.1 Charging of DC......................................................................................................................................................................11
3.2 Main Circuit breaker control (MCB control) ...................................................................................................................11
3.3 Quick Start instructions ......................................................................................................................................................12
3.4 Start Sequence .....................................................................................................................................................................13
3.5 Stop Sequence ......................................................................................................................................................................14
3.6 Start Stop timing diagram ..................................................................................................................................................15
4. CONTROL IO ....................................................................................................................................................................................16
5. AFE Application –Monitoring Values .......................................................................................................................................17
5.1 Monitoring values................................................................................................................................................................18
5.1.1 Monitoring 1 ....................................................................................................................................................................18
5.1.2 FieldBus Monitoring values...........................................................................................................................................18
5.1.3 Line Monitor OPT-D7 ......................................................................................................................................................18
5.1.4 Master Follower ..............................................................................................................................................................19
5.1.5 Monitoring values 2........................................................................................................................................................19
5.2 Monitoring Values description..........................................................................................................................................19
5.2.1 Monitoring 1 values........................................................................................................................................................19
5.2.2 Fieldbus monitoring values ...........................................................................................................................................21
5.2.3 Line monitoring OPT-D7.................................................................................................................................................26
5.2.4 Master/Follower..............................................................................................................................................................26
5.2.5 Monitoring values 2........................................................................................................................................................27
6. Parameter List................................................................................................................................................................................28
6.1 Basic parameters..................................................................................................................................................................28
6.2 Reference Handling.............................................................................................................................................................28
6.3 Input signals..........................................................................................................................................................................29
6.3.1 Digital inputs ....................................................................................................................................................................29
6.3.2 Analogue Input 1 .............................................................................................................................................................29
6.3.3 Analogue Input 2 .............................................................................................................................................................29
6.3.4 Cabin State DI...................................................................................................................................................................30
6.3.5 Options..............................................................................................................................................................................30
6.4 Output signals.......................................................................................................................................................................31
6.4.1 Digital Outputs.................................................................................................................................................................31
6.4.2 ANALOG OUTPUT 1 .........................................................................................................................................................31

4 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.4.3 Options..............................................................................................................................................................................32
6.5 Limit Settings ........................................................................................................................................................................33
6.5.1 Current Limit ....................................................................................................................................................................33
6.5.2 Power Limit ......................................................................................................................................................................33
6.5.3 Frequency Limit ...............................................................................................................................................................33
6.5.4 AC Voltage Limit ..............................................................................................................................................................33
6.5.5 DC Voltage Limit ..............................................................................................................................................................33
6.6 Drive Control parameters...................................................................................................................................................34
6.6.1 Control...............................................................................................................................................................................34
6.7 Protections............................................................................................................................................................................35
6.7.1 General..............................................................................................................................................................................35
6.7.2 Temperature sensor protections..................................................................................................................................35
6.7.3 Fieldbus.............................................................................................................................................................................36
6.7.4 OPT-D7 protections ........................................................................................................................................................36
6.7.5 Options..............................................................................................................................................................................36
6.8 Fieldbus parameters............................................................................................................................................................37
6.9 ID Control Functions............................................................................................................................................................38
6.9.1 Value control....................................................................................................................................................................38
6.9.2 DIN ID Control 1...............................................................................................................................................................38
6.10 Keypad control (Control keypad: Menu M3) ..................................................................................................................39
6.11 System menu (Control keypad: Menu M6) .....................................................................................................................39
6.12 Expander boards (Control keypad: Menu M7) ...............................................................................................................39
7. Description of parameters .......................................................................................................................................................... 40
7.1 Basic parameters..................................................................................................................................................................40
7.2 Reference Handling.............................................................................................................................................................41
7.3 Input signals..........................................................................................................................................................................42
7.3.1 Digital inputs ....................................................................................................................................................................42
7.3.2 Analogue Inputs...............................................................................................................................................................44
7.3.3 Cabin State DI...................................................................................................................................................................47
Options ..................................................................................................................................................................................47
7.3.4..................................................................................................................................................................................................47
7.4 Output signals.......................................................................................................................................................................48
7.4.1 Digital outputs .................................................................................................................................................................48
7.4.2 Analogue outputs ............................................................................................................................................................50
7.4.3 Options outputs...............................................................................................................................................................52
7.5 Limit Settings ........................................................................................................................................................................53
7.5.1 Current limits ...................................................................................................................................................................53
7.5.2 Power Limits.....................................................................................................................................................................53
7.5.3 Frequency limits ..............................................................................................................................................................53
7.5.4 AC Voltage limits .............................................................................................................................................................54
7.5.5 DC Voltage limit parameters .........................................................................................................................................55
7.6 Drive control .........................................................................................................................................................................56
7.6.1 Control...............................................................................................................................................................................58
7.7 Protections............................................................................................................................................................................60
7.7.1 General..............................................................................................................................................................................60
7.7.2 Temperature sensor protections..................................................................................................................................61
7.7.3 Fieldbus.............................................................................................................................................................................62
7.7.4 OPT-D7 Protections.........................................................................................................................................................63
7.8 Fieldbus parameters............................................................................................................................................................64
7.9 ID Functions ..........................................................................................................................................................................65
7.9.1 Value Control ...................................................................................................................................................................65
7.9.2 DIN ID Control..................................................................................................................................................................67
7.10 Keypad control .....................................................................................................................................................................68
8. Status and control words in detail ............................................................................................................................................69
8.1 Basic In ByPass (0)................................................................................................................................................................69

Arfiff05 Standard AFE-II vacon • 5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8.2 FB Control Word...................................................................................................................................................................70
8.2.1 Standard (1)......................................................................................................................................................................70
8.2.2 Vacon AFE 1 profile (2)...................................................................................................................................................71
8.2.3 Vacon AFE 2 Profile (3)...................................................................................................................................................73
8.3 FB Status Word.....................................................................................................................................................................75
8.4 Fault Word 1 .........................................................................................................................................................................77
8.5 Fault Word 2 .........................................................................................................................................................................77
8.6 Warning Word 1...................................................................................................................................................................78
8.7 Auxiliary Control Word .......................................................................................................................................................79
8.8 Status Word (Application) ID 43........................................................................................................................................80
9. Problem Solving.............................................................................................................................................................................82
10. Fault codes.................................................................................................................................................................................83

6 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1. INTRODUCTION
The AFE unitis a regenerativepowerconverterforthe front-endof a commonDC bus product line.
The AFE unitis utilizedby using inverterhardwarewith specialsoftware.An externalL(CL)-filter
and chargingcircuit is needed.This unit isselected when lowharmonics arerequired. The principle
connection of AFE drive hasbeen describedin Figure 1.
The Regenerative Application is easy and flexible to use due to its versatile fieldbus features. The
parametersof the Regenerative Applicationare explainedinChapter 7 of this manual.
The basic I/O-configuration of the AFE drive consists of OPT-A1 and OPT-A2 option cards. The basic
I/O configurationhasbeen describedin table2-1.
As a defaultthe control place (P3.1) of theAFE drive is Keypad.
This applicationrequires NXP3control boardVB00761.
Figure 1, AFE connection

Arfiff05 Standard AFE-II vacon • 7
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.1 Compatibility issuesinparametersbetween versions
V025
•Compatibility Issue: MCB Force Open inverted. This to follow NXC cabinet
default signals.
Update Note 1: This applicationparametersare notkeptbackwards compatible if newfeaturesor
improvementswouldbe difficulttoimplementby doing so.Readthis change note and chapter
Compatibility issuesinparametersbetweenversions beforeupdatingthe application.
Update Note 2:
application,especially in cases whenversionnumber change is considerably high.
Applicationis constantly developed;thisincludes changing parameterdefaultvalues,and if
parametersaredirectly downloadedto drive improved default valuesmay be lost.

8 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2. AFEUNITS
Air andliquid-cooled products listed inchapter 2are compatible withAFEapplicationARFIFF05.
Hardwareand softwaresupportforAFEuse is only availableforthese products.
DownloadingAFEapplicationtoproducts other than thoselisted inchapter 2 is considered to be a
non-standard product which functionality hasnot beenverifiedordocumented. In such cases User
takesfull responsibility for possible hardwareandsoftwareproblems. Applicationsupport isnot
availablefornon-standard products.
2.1 500VacunitsAirCooled, 465-800Vdc
Code
Frame
IL-cont[A]
IH-cont
[A]
NXA_0168 5 A0T02SG
FI9
170
140
NXA_0205 5 A0T02SG
FI9
205
170
NXA_0261 5 A0T02SG
1xFI9
261
205
NXA_0385 5 A0T02SG
1xFI10
385
300
NXA_0460 5 A0T02SG
1xFI10
460
385
NXA_1150 5 A0T02SG
1xFI13
1150
1030
NXA_1300 5 A0T02SG
1xFI13
1300
1150
2.2 690VacunitsAirCooled, 640-1100Vdc
Code
Frame
IL-cont[A]
IH-cont
[A]
NXA_0125 6 A0T02SG
1xFI9
125
100
NXA_0144 6 A0T02SG
1xFI9
144
125
NXA_0170 6 A0T02SG
1xFI9
170
144
NXA_0261 6 A0T02SG
1xFI10
261
208
NXA_0325 6 A0T02SG
1xFI10
325
261
NXA_0920 6 A0T02SG
1xFI13
920
820
NXA_1030 6 A0T02SG
1xFI13
1030
920

Arfiff05 Standard AFE-II vacon • 9
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.3 500VacunitsLiquid-Cooled,465-800 Vdc
Code
Chassis
Ith [A]
Il [A]
Ih [A]
NXA01685A0T02WS
CH5
168
153
112
NXA02055A0T02WS
CH5
205
186
137
NXA02615A0T02WS
CH5
261
237
174
NXA03005A0T02WF
CH61
300
273
200
NXA03855A0T02WF
CH61
385
350
257
NXA04605A0T02WF
CH62
460
418
307
NXA05205A0T02WF
CH62
520
473
347
NXA05905A0T02WF
CH62
590
536
393
NXA06505A0T02WF
CH62
650
591
433
NXA07305A0T02WF
CH62
730
664
487
NXA08205A0T02WF
CH63
820
745
547
NXA09205A0T02WF
CH63
920
836
613
NXA10305A0T02WF
CH63
1030
936
687
NXA11505A0T02WF
CH63
1150
1045
767
NXA13705A0T02WF
CH64
1370
1245
913
NXA16405A0T02WF
CH64
1640
1491
1093
NXA20605A0T02WF
CH64
2060
1873
1373
NXA23005A0T02WF
CH64
2300
2091
1533
2.4 690VacunitsLiquid-Cooled,640-1100 Vdc
Code
Chassis
Ith [A]
Il [A]
Ih [A]
NXA01706A0T02WF
CH61
170
155
113
NXA02086A0T02WF
CH61
208
189
139
NXA02616A0T02WF
CH61
261
237
174
NXA03256A0T02WF
CH62
325
295
217
NXA03856A0T02WF
CH62
385
350
257
NXA04166A0T02WF
CH62
416
378
277
NXA04606A0T02WF
CH62
460
418
307
NXA05026A0T02WF
CH62
502
456
335
NXA05906A0T02WF
CH63
590
536
393
NXA06506A0T02WF
CH63
650
591
433
NXA07506A0T02WF
CH63
750
682
500
NXA08206A0T02WF
CH64
820
745
547
NXA09206A0T02WF
CH64
920
836
613
NXA10306A0T02WF
CH64
1030
936
687
NXA11806A0T02WF
CH64
1180
1073
787
NXA13006A0T02WF
CH64
1300
1182
867
NXA15006A0T02WF
CH64
1500
1364
1000
NXA17006A0T02WF
CH64
1700
1545
1133

10 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.5 690VacunitsLiquid Cooled,640-1200 Vdc
Code
Chassis
Ith [A]
Il [A]
Ih [A]
NXA01708A0T02WFA1A2
CH61
170
155
113,0
NXA02088A0T02WFA1A2
CH61
208
189
139,0
NXA02618A0T02WFA1A2
CH61
261
237
174,0
NXA03258A0T02WFA1A2
CH62
325
295
217,0
NXA03858A0T02WFA1A2
CH62
385
350
257,0
NXA04168A0T02WFA1A2
CH62
416
378
277,0
NXA04608A0T02WFA1A2
CH62
460
418
307,0
NXA05028A0T02WFA1A2
CH62
502
456
335,0
NXA05908A0T02WFA1A2
CH63
590
536
393,0
NXA06508A0T02WFA1A2
CH63
650
591
433,0
NXA07508A0T02WFA1A2
CH63
750
682
500,0
NXA08208A0T02WFA1A2
CH64
820
745
547,0
NXA09208A0T02WFA1A2
CH64
920
836
613,0
NXA10308A0T02WFA1A2
CH64
1030
936
687,0
NXA11808A0T02WFA1A2
CH64
1180
1073
787,0
NXA13008A0T02WFA1A2
CH64
1300
1182
867,0
NXA15008A0T02WFA1A2
CH64
1500
1364
1000,0
NXA17008A0T02WFA1A2
CH64
1700
1545
1133,0

Arfiff05 Standard AFE-II vacon • 11
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3. OPERATION
3.1 ChargingofDC
This AFE application has own charging control, P2.4.1.9 DC Charge (24 Vdc required for control
board) level
within set time P2.7.1.5 Charge Max Time (provided that DC Voltage reach at least drive under
voltagefaultlevel).
Charging function is activated when P2.4.1.9 DC Charge is A.1 or higher. When control place is IO,
KeypadorNCDrivechargingisstarted fromstartcommand.
Chargingis notstarted if:
-Driveisin fault state.
-P2.3.1.2 Enable MCB Close is FALSE
-P2.3.1.6 RunEnable isFALSE
-P2.3.1.7 QuickStopisFALSE
Chargingis alsostopped if aboveconditionshappens during charging orstart commandis removed.
For fieldbus control charging is started with B0 of FB Control Word on supporting FB profiles.
Chargingis alsostopped if B0 goeslow asis MCB opened if already closed.
DC Charge (F80)is givenif 85 %of DC Nominalis not reached withinP2.7.1.5 ChargeMax Time and
charging is stopped.
DC Chargingis stoppedwhendrivereceivesfeedback fromP2.3.1.5 MCB Status.
Note! Use suitably sized DC Charging resistor by checking Pulse loadability for time duration set in
forMax ChargeTimeparameter
3.2 Main Circuitbreaker control(MCBcontrol)
The AFE applicationcontrols the MCB of the systemwithRelay Output RO2. Whencharging ofthe DC
bus is ready the MCB will be closed. The status of the MCB is monitored via digital input P2.3.1.5
MCB Status(Default isDigIn: A.4). MCB feedback isrequiredforcorrect AFE functionality,
NOTE! MCBfeedbackisrequired forcorrect AFE functionality.
OverCurrent(F1), HardwareIGBT(F31)and SoftwareIGBT(F41)faultswillopen MCBimmediately.
Some fault can be programmed to openMCB if needed.
NOTE! For correct operation of AFE system, AFE unit needs to be in control of charging circuit and
MainCircuitBreaker(MCB).

12 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.3 QuickStartinstructions
NOTE! Beforetakingany commissioning actions readcarefully thesafety instructions in VaconNX
User's Manual, chapter1.
1. Connectthe unitaccording tothe Figure1.
2. Powerup the control unit.
3. Set parametersin G2.1 BasicParameters.
4. Check that digital input parameters (G2.3.1) have been set according to connections. Note
that P2.3.1.5 MCB Statusinput isneededfor correct operationof AFE unit.
5. Checkthe control placeaccordingly provesrequirements (P3.1 ControlPlace).
6. ChargeDC.
In case of parallel AFE:
1. Set Parallel AFE parameter (P2.1.5) = YES (in every AFE). (This will set also DC Drooping to
4,00%
2. Set StartUp Delay inAFEunits so thatstarting isin sequence with differentintervals.
Time * 100 ms
Stop
AFE 1
Run
Stop
AFE 2
Run
Stop
AFE 3
Run
Stop
AFE 4
Run

Arfiff05 Standard AFE-II vacon • 13
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.4 StartSequence
Init
Ready to
switch on
DC > 85 %
Close MCB
MCB close
enable
MCB Closed
Start
Command
Synchronized Trials >= 5
Modulating F10: LineSynch
No
Yes
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
F64 A2
(Delayed)
Figure 0-2.AFE start sequence

14 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.5 StopSequence
Modulating
MCB Closed
No
F64 A4
Open MCB No
Yes
Yes
Stop Modulation
(If Run State)
Open MCB
Stop Request MCB Closed No F64 A2
(If DC > 75 %)
(Delayed)
Yes
MCB Closed
No
Yes F64 A3
(Delayed)
End
Figure 0-3.AFE stop sequence

Arfiff05 Standard AFE-II vacon • 15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.6 StartStoptimingdiagram
DC Voltage
Charge Control
MCB Feedback
MCB Close Control
MCB Close level
Stable DC
Ready
IO Start
Run
FB CW.B00
Control in
FB Control
FB CW.B03
Contro in
IO Control
P. Start Delay
IO MCB Open
Command
is likein IOControl.

16 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4. CONTROLIO
NXOPTA1
Terminal
Signal
Description
1
+10Vref
Referencevoltageoutput
Voltage for potentiometer,etc.
2
AI1+
Analogue input 1.
Range0-10V,Ri=200
Range0-20 mARi=250
Analogue input 1
Input range selected byjumpers.
Default range:Voltage 0 10 V
3
AI1-
I/OGround
Groundfor reference andcontrols
4
AI2+
Analogue input 2.
Range0-10V,Ri=200
Range0-20 mARi=250
Analogue input 2
Input range selected byjumpers.
Default range:Current 0 20 mA
5
AI2-
6
+24V
Controlvoltage output
Voltage for switches,etc. max0.1 A
7
GND
I/Oground
Groundfor reference andcontrols
8
DIN1
Start Request
Programmable G2.3.1
Contact closed = Start Request
9
DIN2
Programmable G2.3.1
No functiondefined at default
10
DIN3
Fault Reset
Programmable G2.3.1
Contact closed= Fault Reset
11
CMA
Commonfor DIN1 DIN 3
Connect to GNDor +24V
12
+24V
Controlvoltage output
Voltage for switches(see #6)
13
GND
I/Oground
Groundfor reference andcontrols
14
DIN4
MCBfeedback
Contact open= MCBopen
Contact closed =MCBClosed
15
DIN5
Programmable G2.3.1
No functiondefined at default
16
DIN6
ProgrammableG2.2.1
17
CMB
Commonfor DIN4 DIN6
Connect to GNDor +24V
18
AOA1+
Analogue output 1
ProgrammableP2.3.1.2
Output rangeselected byjumpers.
Range0 20mA.RL,max.500
Range0 10 V.RL> 1k
19
AOA1-
20
DOA1
Digitaloutput
Ready/ Warning(Blinking)
Programmable
Opencollector,I50mA,U48 VDC
NXOPTA2
21
RO1
Relay output 1
ProgrammableG2.4.1
Switchingcapacity
24 VCD/ 8 A
250 VAC/8 A
125 VDC/0.4 A
22
RO1
23
RO1
24
RO2
Relayoutput 2
MCBContl
Cannot be reprogrammed
Fixedto MCBcontrol.
Closes whenDCat 85 %of nominalDC.
OpenswhenDC below 75%of nominalDC
25
RO2
26
RO2
Table 5-2. Default I/O configuration.
220
VAC
mA
K1
Q1

Arfiff05 Standard AFE-II vacon • 17
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5. AFEAPPLICATION MONITORINGVALUES
Onthe next pagesyouwill findthe lists of parameterswithintherespective parametergroups.
Column explanations:
Code = Location indication on the keypad; Shows the operator the present parameter
number
Parameter = Nameof parameter
Min = Minimumvalue of parameter
Max = Maximumvalue of parameter
Unit = Unit of parametervalue;Givenif available
Default = Value presetby factory
Cust =
ID = ID number of the parameter
_____ = Onparametercode: Parametervaluecan only bechanged afterthe Drive has been
stopped.
_____ = Monitoringvalueis possible to control fromfieldbus by ID number
The manual presents signals thatare notnormally visibleformonitoring.i.e.is nota parameteror
standard monitoringsignal. Thesesignals arepresentedwith [Letter]. e.g.
[FW]MotorRegulatorStatus
[V] Normalmonitoringsignal
[P] Normalparameterin application.
[FW] Firmwaresignal,CanbemonitoredwithNCDrive whensignal typeisselected Firmware
[A] Applicationsignal, can bemonitoredwithNCDrive whensignal typeisselected Application.
[R] Referencetypeparameteronkeypad.
[F] Function. Signalis received asa output of function.
[DI]Digitalinput signal.
CB CircuitBreaker
MCB MainCircuitBreaker= AFEcontroller CircuitBreaker

18 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.1 Monitoringvalues
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoringvaluescannot beedited.
5.1.1
Monitoring1
Code
Signal
Unit
ID
Description
V1.1.1
DC-Link Voltage
Vdc
1108
Measured DC Link voltage in Volts, filtered.
V1.1.2
DC-Link Ref.
Vdc
25
DC VoltageReference in Vdc
V1.1.3
DC VoltageRef.
%
1200
Used DC VoltageReference
V1.1.4
DC VoltageAct.
%
7
Actual DC Voltage
V1.1.5
Total Current
A
3
Total current of the regenerative unit in
Amperes.
V1.1.6
Active Current
%
1125
Avtive current of the regenerative drivein % of
Rated Line Current.
> 0 power fromAC side to DC side
< 0 power fromDC side to AC side
V1.1.7
Reactive Current
%
1157
Reactive current of the regenerative drivein % of
Rated Line Current.
> 0 Inductive current
< 0 Capacitive current
V1.1.8
SupplyFrequency
Hz
1
Supply frequency in ##.## Hz .The sign indicates
the phase order.
V1.1.9
SupplyVoltage
V
6
InputAC voltage, RMS lineto lineVolts.
V1.1.10
Unit Temperature
°C
8
Heat sing temperature
V1.1.11
Status Word
43
V1.1.12
DIN 645. 321
15
V1.1.13
Analogue Input1
%
13
V1.1.14
Analogue Input2
%
14
V1.1.15
Analogue Out1
%
26
V1.1.16
Operation Hours
h
1856
5.1.2
FieldBusMonitoringvalues
Code
Signal
Unit
ID
Description
V1.2.1
FB Control Word
1160
Control wordfrom fieldbus
V1.2.2
FB Status Word
68
Status word to fieldbus
V1.2.3
Fault Word 1
1172
V1.2.4
Fault Word 2
1173
V1.2.5
DIN Status Word 1
56
V1.2.6
DIN Status Word 2
57
V1.2.7
Warning Word 1
1174
V1.2.8
DC Voltage
44
Unfiltered DC-Link voltage
V1.2.9
Current
1113
Unfiltered total current
V1.2.10
Drive Power
kW
1508
Electrical AFE terminal power
V1.2.11
Fault History
37
V1.2.12
Final DCRef
%
1131
V1.2.13
CabinState Word
1884
5.1.3
LineMonitorOPT-D7
Code
Signal
Unit
ID
Description
V1.3.1
Line Voltage
V
1650
V1.3.2
Line Frequency
Hz
1654
V1.3.3
Synch Error D7
1659
V1.3.4
Line Voltage THD
1670
V1.3.5
Line Voltage HF rms
1671

Arfiff05 Standard AFE-II vacon • 19
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.1.4
MasterFollower
Code
Parameter
Unit
Form.
ID
Description
V1.4.1
SB SystemStatus
1601
V1.42
Master CW
93
5.1.5
Monitoringvalues2
Code
Signal
Unit
ID
Description
V1.5.1
Measured temperature 1
Cº
50
4 s filtering.
V1.5.2
Measured temperature 2
Cº
51
4 s filtering.
V1.5.3
Measured temperature 3
Cº
52
4 s filtering.
V1.5.4
Measured temperature 4
Cº
69
4 s filtering.
V1.5.5
Measured temperature 5
Cº
70
4 s filtering.
V1.5.6
Measured temperature 6
Cº
71
4 s filtering.
V.1.5.7
PT-100 Temperature
Cº
42
Highest temperature of OPTB8/OPTBH board. 4 s
filtering.
5.2
MonitoringValuesdescription
5.2.1
Monitoring1 values
V1.1.1 DC-Link Voltage Vdc ID44
Measured DC voltage, filtered.
V1.1.2 DC-Link Ref. Vdc ID25
DC-LinkvoltagereferenceinVdc.
V1.1.3 DC VoltageRef. % ID1200
Used DC Voltagereferencein %
V1.1.4 DC VoltageAct. % ID7
Actual DC Voltage in %
V1.1.5 Total Current A ID3
Totalcurrent of theregenerative unit in Amperes,filtered
V1.1.6 Active Current % ID1125
Active current in % of SystemRatedCurrent.
Negative valuemeansthatcurrent is flowingto AC side fromDC side i.e.regenerating.
V1.1.7 Reactive Current % ID1157
Reactive current of the regenerative drive in%of SystemRated Current.
Positive isInductive current.
Negativeiscapacitive current.
V1.1.8 Supply Frequency Hz ID1
Supply frequency in##.## Hz .The signindicates thephase order.Updatedwhen drivein
run state.Updatedalso in stopstate whenOPT-D7is used or RegenOptionsB9 is
activated.

20 • Vacon arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.1.9 Supply Voltage V ID6
Input AC voltage,RMSlineto lineVolts. Updatedwhen drive inrun state.
Updatesalso when OPT-D7 is used.
V1.1.10 UnitTemperature °C ID8
Temperatureof the unit in degreesCelsius
V1.1.11 Status Word ID43
ApplicationStatusWord combinesdifferentdrive statusesto onedata word.
Application Status Word ID43
FALSE
TRUE
b0
b1
Not in Ready state
Ready
b2
Not Running
Running
b3
No Fault
Fault
b4
b5
Quick Stop Active
Quick Stop Not Active
b6
RunDisabled
RunEnable
b7
No Warning
Warning
b8
Charging Switchclosed (internal)
b9
MCBControl (DO Final)
b10
MCBFeedback
b11
DO ChargingActive
b12
No Run Request
RunRequest
b13
b14
b15
V1.1.12 DIN 645. 321 ID15
DIN1/DIN2/DIN3 status
B0
DIN1
B1
DIN2
B2
DIN3
B3
DIN4
B4
DIN5
B5
DIN6
V1.1.13 Analogue Input1 % ID13
V1.1.14 Analogue Input2 % ID14
Unfilteredanalogue inputlevel.
0% = 0 mA/ 0 V, -100 % = -10 V, 100 %= 20 mA/ 10 V.
Monitoring scaling is determined by the optionboardparameter.
V1.1.15 Analogue Out 1 % ID26
Analogue Output value0 % = 0mA / 0 V, 100 % =20 mA / 10 V
Table of contents
Other Vacon Controllers manuals

Vacon
Vacon optc3 User manual

Vacon
Vacon NX User manual

Vacon
Vacon 100 flow User manual

Vacon
Vacon optbj User guide

Vacon
Vacon 20 X User manual

Vacon
Vacon nxs User manual

Vacon
Vacon 100 flow Instructions for use

Vacon
Vacon 100 HVAC Instructions for use

Vacon
Vacon 100 INDUSTRIAL User manual

Vacon
Vacon 100X series User manual

Vacon
Vacon NX User manual

Vacon
Vacon NXP series User manual

Vacon
Vacon 100 INDUSTRIAL User manual

Vacon
Vacon 100 flow User manual

Vacon
Vacon 100 INDUSTRIAL User manual

Vacon
Vacon NXP User manual

Vacon
Vacon NX Active Front End User manual

Vacon
Vacon NX OPTCJ User manual

Vacon
Vacon 20 CP/X Instructions for use

Vacon
Vacon nxsp User manual