
UPS module failure
In case of inverter failure and output fuse blowout, the load will automatically transfer to the bypass, and the output power
supply will not be interrupted. In this situation, please contact the local customer service center of Vertiv for technical support.
(Parallel System) In the event of a fault in a UPS module, it will automatically exit from the parallel system. If the system is still
capable of providing the required load, the remaining modules will continue to supply the load with no interruption. If the
remaining modules are no longer capable of fulfilling the power requirements, the load will automatically transfer to the
bypass.
Overload
If the inverter is overloaded or the inverter current remains outside the specifications (refer to Table 12.6 on page175) longer
than the specified time, the load will automatically transfer to the bypass without power interruption. If both the overload and
the current are reduced to a level within the specified range, then the load will be transferred back to the inverter. In case of
output short circuit, the load will be transferred to the bypass, and the inverter will shut down. Five minutes later, the inverter
will start up automatically. If the short circuit is removed at this point, the load will be transferred back to the inverter. The
transfer is determined first of all by the features of the protective device of the system.
In the above two situations, the UPS touch screen will display alarm messages.
(Parallel System) The control logic system constantly monitors load requirements and controls the power supplied by each
UPS module. In the event that an overload condition is sustained for greater than a preset time, the load will transfer to the
bypass, when the number of active modules is unable to satisfy load requirements. The load returns to the inverter if the
power is reduced to a value that can be sustained by the number of active modules in the system.
Maintenance bypass
The UPS has a second bypass circuit, i.e. maintenance bypass (without switch excluded), which provides a safe working
environment for the engineers to provide regular maintenance or repair to the UPS system and at the same time provide
unregulated mains supply to the loads. The maintenance bypass can be manually selected through the maintenance bypass
switch, and it can be disconnected by turning the switch to OFF.
W A R N IN G ! If th e U P S s ys tem c on sists of tw o o r m o re U P S m o du le s a nd w h en th e loa d
cap acity exceeds the sing le m odu le cap ac ity, d o not use the interna l m ainte nan ce bypass
sw itch .
2.2.4 UPS Power Supply Switch Configuration
The UPS equipped with four switches: rectifier input switch Q1, bypass input switch Q2, maintenance bypass switch Q3, and
output switch Q5. Note that switches Q1, Q2, and Q5 are options of switch group, and the switch group does not support single
switch installation.
Figure 2.2 on the facing page describes the block diagram of the UPS module. The UPS has split bypass configuration (that is,
the bypass adopts independent mains input) and common input configuration. In split bypass configuration, the static bypass
and maintenance bypass share the same independent bypass power supply. Where a separate power source is not available,
the input supply connections of the bypass input switch (Q2) and rectifier input switch (Q1) would be linked together (split
bypass configuration for delivery) to make the bypass input and rectifier input use mains power of the same route.
During the normal operation of the UPS, except for the maintenance bypass switch Q3, other switches shall be closed.
2 Overview
5
Vertiv™ Liebert® APM Plus User Manual