TS21I_ELE_O2 User Manual
Page 13 of 14
Do’s and Don’ts when gas leak occurs
Do’s:
•If there is low oxygen level than required value (20.9%), keep the doors/windows for
proper ventilation
Routine Check for TrueSafe TS21I_ELE_O2
•To ensure that TS21I_ELE_O2 is in working condition, it is necessary to check working
of Gas LED by manual testing.
•For checking unit’s sensing capability, it is necessary to check the unit once in a month.
Maintenance
Maintenance Guidelines:
• The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from
purchase date.
• Calibrate the detector at least once every 6 months.
• Calibration should be performed with certified calibration gas. Calibration kits and replacement
cylinders are available from Calibration Technologies.
• All tests and calibrations must be logged.
• Always disconnect power at the controller before performing any wiring at the sensor.
Sensor Life:
These electrochemical cells are extremely reliable, but several things can cause the cell chemicals
to become depleted including:
• a period of time
• Exposure to high temperatures
• Continuous, long term exposure to ammonia
When the cell becomes depleted, the unit will give no indication of failure other
than that the sensor will not respond. For this reason, it is absolutely essential that these sensors
be calibrated on a regular basis. Typical sensor life will be two years. The new sensor can be span-
calibrated immediately; however, an 8-hour warm-up period is required before zeroing, if
necessary.
Disclaimer for TrueSafe
All statements, technical information and recommendations contained herein are based
on available scientific and technical know how, which we believe are true and reliable.
However, neither the manufacturer nor the seller shall be liable for any loss, injury,
earth, damage direct or consequential arising out of the use of or the inability to use the
product. The purchaser and or user shall determine the suitability of the product for his
intended use and user assumes all risk and liability, whatsoever, in connection there
with. No statement or recommendation contained herein shall have force or effect
unless in an agreement signed by officers of manufacturer or seller. Seller's and
manufacturer's only obligation shall be limited to replace the product which is proved to
be having manufacturing defect and returned with in the warranty period.
Terms Of Warranty
1. All models of TrueSafe detectors are warranted against any manufacturing defects for a
period of Twelve months from the date of purchase. The company shall repair/replace only
the part or a part which proves to be defective due to faulty material or workmanship.