Vigilant T-Gen2 User manual

Ref: PBG0215
9 October 2018
Page 1 of 8
T-GEN2 GRADE 3 BUILDING OCCUPANT WARNING SYSTEM
The VIGILANT T-Gen2 Emergency Warning System is available as two complete
Grade 3 Building Occupant Warning Systems (BOWS) –8U @ 60W and 15U @
120W. New versions approved to AS 4428.16 replace the earlier models.
The VIGILANT T-Gen2 Building Occupant Warning System (BOWS) is a self-contained
AS 4428.16 Alert and Evacuate tone generator, with integral power supply, digitised speech
messages, and PA microphone. It has been designed to connect directly to a fire alarm
panel, and can also be used as a stand-alone unit.
The BOWS units contain a T-Gen2 Grade 3 User Interface, speech microphone, T-Gen2
and PSU, with space for additional modules and batteries.
Non-emergency paging options, IP remote audio compatibility, and multiple audio inputs
make the VIGILANT BOWS a versatile base unit for a variety of applications meeting the
single zone requirements.
FEATURES AND BENEFITS
Self-contained Building Occupant Warning System (BOWS) suits multiple applications
Available in 60W (8U) and 120W (15U) versions
Compliant with AS 4428.16 for Grade 3 applications
Emergency PA microphone, Alert/Evacuate/Speech controls
Zone Paging options –up to 4 separately-selectable speaker areas
4-zone remote paging microphone/console option
Auto/Manual operation
Selectable priority for Paging/Remote/Background Audio inputs
Alarm input and Fault output signals for fire panel connection
Optional High Level Interface with Vigilant MX1, MX4428, F3200 or Simplex 4100ESi
Programmable Alert to Evacuate delay (0-600sec or manual)
Pre-recorded Alert and Evacuate messages, field re-recordable for flexibility
Up to 2A Strobe output per T-Gen2
Integral 14 Amp (peak) Power Supply with fault supervision
Space for 2 x 17Ah (8U) or 2 x 40Ah (15U) batteries
Space for 3 (8U), 6 (15U) x 100V Switching/Splitter Modules for short-circuit isolated
outputs
Space for an additional T-Gen 60 (8U) and T-Gen 120 (15U) for higher loads
Expandable up to 9 synchronized Slaves T-Gens and 10 PSUs
8U 19" rack cabinet: 440mm H x 550mm W x 210mm D (60W)
15U 19” rack cabinet: 750mm H x 550mm W x 210mm D (120W)
8U
15U

Ref: PBG0215 9 October 2018
Page 2 of 8
GENERAL DESCRIPTION
VIGILANT BOWS Functional Block Diagram
The VIGILANT BOWS has a microphone for emergency public address, fault and status
indicators, and manual controls to control its operation. It has audio inputs for background
music, remote non-emergency audio (which can be used when streaming audio over IP
networks), or non-emergency paging (zone-selective with an add-on option). Also included
is a 14A power supply.
It is available in an 8U cabinet (FP1144) and in a 15U cabinet (FP1134).
EXPANSION OF BOWS UNITS
The FP1144 8U cabinet BOWS may be upgraded in the field by adding a second T-Gen 60
(FP1115) to provide a second 100V line output. It also has space for 3 x 100V Switching
Modules (FP1117) for area paging outputs and short-circuit isolation or 100V Splitter
Modules (FP1118) to provide short-circuit isolated outputs only.
With two T-Gen 60s fitted in the 8U FP1144, the PSU and the available battery capacity
(17AHr) can support 60W of 100V audio load on each T-Gen 60, plus a combined 1.5A of
strobe load.
The FP1134 15U cabinet is fitted with one T-Gen 120 and can be expanded with an
additional T-Gen 60 (FP1115) or T-Gen 120 (FP1116) to provide additional power output. It
also has space for 6 x 100V Switching Modules (FP1117) for area paging outputs and short-
circuit isolation or 100V Splitter Modules (FP1118) to provide short-circuit isolated outputs
only.
With two T-Gen 120s the FP1134 14A PSU can support up to 120W load, with no strobe
load on each T-Gen 120, decreasing to a combined 160W load with a total strobe current of
4A.
Further expansion can be achieved using the FP1130 15U expansion cabinet, allowing
additional T-Gen2 (60 or 120W), PSUs and Switching / Splitter Modules to be housed
adjacent to the BOWS unit. Up to 9 slave T-Gen2 and 10 PSUs in total can be connected to
the Master T-Gen2.
24V Power Supply
Batteries
2 x 12V 6.5Ah, 12Ah or 17Ah
Emergency
PA Mic
Paging (optional)
100V Speaker Line
Alarm (& fault back)
Remote Audio
Background Music
EOL
T-Gen2
Alert and Evacuate Tone Generator
EOL
Strobes

Ref: PBG0215 9 October 2018
Page 3 of 8
CONNECTING TO FIRE ALARM PANEL
Basic wiring method:
The BOWS has an Alarm input (ALM-) which is normally terminated with an EOL resistor
and shorted by the fire alarm panel to activate the Alert / Evacuation tones.
The BOWS has a common Fault output (DEF-) which is normally open-circuit and pulled to
0V on fault. Voltage-free fault relay contacts (NO, NC, COM) are also provided. One of
these is usually wired to the alarm system to indicate a fault condition.
High Level Link:
Two wiring options are available:
1) Direct connection MX1 to T-Gen2 using a 10-way ribbon cable:
This option can be used only when the T-Gen2 and MX1 are mounted in the same
cabinet or in a dual cabinet installation, both adjacent to each other. Connections to
external RZDU devices is not possible and Port 0 on the MX1 must not be used for any
other function.
2) HLI board (Optional module FP1143) is a logical Interface between T-Gen2 and the
RZDU network. This connection method allows one or more external / remote RZDU
devices to be used.
The HLI board (module) includes a separate short-circuit isolated RZDU connection for
wiring to remote RZDU devices –so that a short circuit in the field wiring does not affect
the T-Gen2’s communication with the fire panel. Up to 32 Zones Alarm states and other
triggers can be sent to the T-Gen2 to manage alarms and play of messages, while the
T-Gen2 can return the fault state.
BOWS
Alarm Input
Fault Output
0V
ALM-
FLT-
NC
NO
COM
Fire Alarm
Panel
Alarm Output
Fault Input
Remote Zone
Display Unit
BOWS
HLI-Module
RZDU-IN
RZDU-OUT
Fire Alarm
Panel
RZDU

Ref: PBG0215 9 October 2018
Page 4 of 8
The HLI module can also be used with Simplex 4100ESi panels. The T-Gen2 connects onto
the internal 4100Comms bus and appears to the 4100ESi as a slave device with a number
of programmable input and output devices.
AUDIO INPUTS
The BOWS has two general purpose line-level (150mV) audio inputs. These can be
configured for different operating modes: “Always On / Music”, “Paging Line”to be used with
a Paging Console, and “GP / HLL Input” to be enabled when a specific GP input is active.
These audio inputs could be used for:
Background Music
The audio input is usually configured as “Always On”, and a music source
connected. A volume control is provided to adjust the output level. Screw
terminals and a 3.5mm audio socket are provided for connecting the
background music source to the BOWS.
Remote Audio This mode can be used for connecting to external tone/message
generators, specialist paging systems (e.g., PABX), or voice-over-IP (VoIP)
modules (illustrated). A separate digital input is used to enable the audio
input. A volume control is provided to adjust the output level. The priority
of the audio input (relative to the emergency PA microphone and the zone
paging), and whether the remote audio is to override the Alert/Evacuation
tones is configurable. (Note that this would be non-compliant to
AS4428.16)
ZONE-SELECTABLE PAGING (Two Options)
The BOWS can optionally be fitted with 100V Switching Modules (FP1117) which splits the
single 100V output into four separately selectable 100V line outputs. Each of the 4 outputs
has separate line supervision (o/c & s/c) and the 100V Switching Module will isolate a
shorted output allowing the other outputs to operate. Each output can handle up to 100W
maximum load, but the total load cannot exceed the T-Gen2 rating (or maximum 120W per
Switching Module in total).
BOWS fitted with a 4-way 100V Switching Module
The 100V Switching Modules allow the T-Gen2 to control which outputs receive the 100V
audio signal from the T-Gen2 –making area-specific paging options possible. Two options
for area paging are available (can be combined).
BOWS
60W or
120W
100V Switching
Module
T-Gen2
Speaker Line/Area 1
Speaker Line/Area 2
Speaker Line/Area 3
Speaker Line/Area 4
EOLR
EOLR
EOLR
EOLR
100V In
100V Out
1
100V Out
2
100V Out
3
100V Out
4

Ref: PBG0215 9 October 2018
Page 5 of 8
LAN
BOWS
Master
Annuncicom
BOWS
Slave
Annuncicom or
Exstreamer
BOWS
Slave
Annuncicom or
Exstreamer
1 USING GRADE 3 USER INTERFACE
The Grade 3 User Interface has 4 Area PA/Paging pushbuttons that when pressed will direct
the voice announcements from the front panel microphone to specific areas. Each output of
the 100V Switching Modules can be configured to belong to a specific area, no area, or all
areas. This allows various paging arrangements to be constructed.
2 USING AN EXTERNAL PAGING CONSOLE
Up to two external 4-zone paging consoles (SU0360) can be combined with an SU0361
Audio Switcher to create remote paging units for the T-Gen2 BOWS. The SU0361 Audio
Switcher is mounted in the BOWS and wired to 4 GP Inputs to indicate when each area is
active. The Paging Consoles are located where needed and connect to the Audio Switcher
using RJ45 cable.
SU0360 Paging Microphone
SU0361 Audio Switcher
Both paging solutions offer a pre-announcement chime which can play a chime signal when
the microphone PTT is activated.
The priority of the paging function compared to the other audio inputs, user functions and
emergency functions is configurable.
IP NETWORKING
The BOWS supports streaming audio over IP Networks using the BARIX range of Audio-
over-IP modules. There are many possible configurations that can be used, depending on
the application (see LT0561 for more details).
One typical application is to use the BARIX modules to allow a master BOWS to make
paging announcements to multiple slave BOWS units connected together on a LAN. For this
application, an Annuncicom 200 may be used in the master BOWS and either an
Annuncicom 200 or Exstreamer 100 at each slave BOWS.
When the paging microphone is activated, this is signalled to each slave unit, which in turn
receives streaming audio from the master and broadcasts it over the loudspeakers.

Ref: PBG0215 9 October 2018
Page 6 of 8
LAN
BOWS
Annuncicom or
Exstreamer
BOWS
Annuncicom or
Exstreamer
The Barix PS16 Paging Console may also be used to broadcast messages over a LAN to
one or more BOWS. The console has 16 buttons which can be configured to select
individual BOWS units for paging.
CONFIGURATION
The BOWS units come pre-configured with the BOWS_AS4428 configuration. This enables
basic operation on the User Interface, an alarm input, Audio 1 as Always ON and Audio 2
activated by GP1 input.
The BOWS_AS2220 configuration can be selected from the T-Gen2 OLED display and
buttons to use AS2220 style tones (not AS4428.16 ones).
Any other configuration –e.g., enable area paging using a Switching Module, Slave T-Gen2,
or assign speech, input functions or change the User Interface operation will require a
configuration to be prepared and downloaded using the Windows SmartConfig application.
FURTHER INFORMATION
Details on the various T-Gen2 modules can be found in the latest issue of product bulletin
PBG0203.
SALES DRAWINGS
1986-36 FP1134, FP, 120W T-Gen2 BUILDING OWS, 15U CAB
1986-37 FP1144, FP, 60W T-Gen2 BUILDING OWS, 8U TITANIA CAB
1956-19 FP1116, FP, T-Gen 120, 24V, C/W INSTALL LIT & MTG
1956-21 FP1117, FP, 100V SWITCHING MODULE, C/W LIT, LOOMS & MTG BRK
1956-22 FP1118, FP, 100V SPLITTER MODULE, C/W LIT, LOOMS & MTG BRKT
1992-16 FP1122, FP, GRADE 3 EWS UI 3U DOOR, C/W LOOM & MIC, GREY
1956-17 FP1143, FP, T-GEN2 HLI BOARD
ORDERING CODES
FP1144 FP, 60W T-Gen2 BUILDING OWS, 8U TITANIA CAB
A complete Building Occupant Warning System (BOWS) including a T-Gen 60, 14A PSU,
3U 19” rack mounting door with Grade 3 User Interface and microphone mounted in a
titania-coloured 8U cabinet. Space for an additional T-Gen 60, batteries, and 3 x 100V
Switching or 100V Splitter modules is available. The optional FP1143 (HLI) can be fitted for
linking to a compatible fire panel.

Ref: PBG0215 9 October 2018
Page 7 of 8
FP1134 FP, 120W T-Gen2 BUILDING OWS, 15U CAB
A complete BOWS including a T-Gen 120, 14A PSU, 3U 19” rack mounting door with Grade
3 User Interface and microphone, all mounted in a 15U x 200 deep rack cabinet. Space for
an additional T-Gen 120, batteries, and up to 6 x 100V Switching or 100V Splitter modules is
available. The optional FP1143 (HLI) can be fitted for linking to a compatible fire panel.
FP1130 FP, T-Gen2 EXP CAB, C/W 14A PSU, 15U, BLANK DR
A 15U x 200 deep 19” cabinet to be installed adjacent to the BOWS to allow further
expansion to be made. Includes a 14A Power Supply, to mount 2 x 120W T-Gen2s and 6
Switching or Splitter Modules a gearplate and up to 40Ahr of batteries to give maximum
flexibility to the system. The cabinet has a blank outer door.
FP1115, FP, T-Gen 60, 24V, C/W INSTALL LIT & MTG
T-Gen 60 model of T-Gen2 able to drive a speaker load up to 60W. Supports two non-
emergency audio inputs (BGM, paging), a microphone audio input (Speech or Paging), 6
supervised inputs (Alarm, Fault, Paging), 4 open-collector outputs, normally-energised Fault
relay, supervised single polarity strobe output, and 100V speaker output. Able to fit to
FP1144 as a spare part or Slave T-Gen2.
FP1116, FP, T-Gen 120, 24V, C/W INSTALL LIT & MTG
T-Gen 120 model of T-Gen2 able to drive a speaker load up to 120W. Able to fit to FP1134
as a spare part or Slave T-Gen2.
FP1117 FP, 100V SWITCHING MODULE, C/W LIT, LOOMS & MTG BRK
Provides 4 supervised, short-circuit isolated 100V outputs (each rated at up to 100W) from
the T-Gen2’s 100V output, along with control of each output by the T-Gen2 to provide area
paging. A QBus slave module. Supplied on MX1-style mounting bracket with cables and
EOLs.
FP1118 FP, 100V SPLITTER MODULE, C/W LIT, LOOMS & MTG BRKT
Provides 4 supervised, short-circuit isolated 100V outputs (each rated at up to 100W) from
the T-Gen2’s 100V output. No control of the outputs is available. Signals fault to the
T-Gen2 by superimposing a fault on the T-Gen2’s 100V input. Standalone operation (not a
QBus slave). Supplied on MX1-style mounting bracket with cables and EOLs.
FP1122 FP, GRADE 3 EWS UI 3U DOOR, C/W LOOM & MIC, GREY
A grey 3U 19” rack mounting door complete with a Grade 3 user interface and PA
microphone ready for connection to a T-Gen 60 or T-Gen 120 mounted inside the cabinet. A
1.5m power loom and microphone extension loom are included. Suitable as a spare part for
FP1144 and FP1134.
FP1139, FP, PSE GEARPLATE MTG, 24V, 14A, SPARE
Replacement or expansion 14A PSE for the BOWS.
FP1143 FP, T-Gen2 HLI BOARD C/W LIT, LOOMS & MTG BRKT
Provides a high-level link between the RZDU port of the Vigilant MX1, MX4428 and F3200
fire panels, or the internal 4100Comms port of a Simplex 4100ESi, and the T-Gen2.
Supplied on an MX-style mounting bracket the same as Switching/Splitter Modules.
SU0360 A 4488 4 Zone Paging Console
A 4 zone paging console with microphone and chime option that can be used with the
SU0361 A 4489 Audio Switcher to achieve 4 area paging from remote locations. Up to two
paging consoles can be connected to the SU0361 Audio Switch.

Ref: PBG0215 9 October 2018
Page 8 of 8
SU0361 A 4489 Audio Switcher
Used with the A 4488 4 zone paging console to provide relay outputs. Able to be mounted
inside the BOWS cabinet.
Literature Items (available electronically)
LT0667 T-Gen2 INSTALLATION GUIDE
LT0673 T-Gen2 Grade 3 USER INTERFACE OPERATOR MANUAL
LT0693 T-Gen2 Grade 3 BOWS INSTALLATION INSTRUCTIONS
SPECIFICATIONS
FP1144 (8U)
FP1134 (15U)
Weight
17.5kg
26kg
Size (WxHxD)
550 x 440 x 210mm
550 x 750 x 210mm
PSU Output Current (Peak)
14A
14A
DC Supply Voltage
19.2Vmin - 28.8Vmax
19.2Vmin - 28.8Vmax
Operating Temperature Range
-5C to +45C
-5C to +45C
Relative Humidity
0 to 95% non-condensing
0 to 95% non-condensing
Storage Temperature Range
-20C to +70C
-20C to +70C
Quiescent Current
Audio enabled but idle (no signal)
290mA
290mA
Active Current - 27Vdc (excl. Strobe)
3.1A @ 60W
6.1A @ 120W
100V Output
Line Voltage - AC (Tones)
100Vrms
100Vrms
Line Power - Tones
60W
120W
- Audio
60W
120W
Maximum line capacitance
200nF
200nF
Audio Frequency range
+/- 1dB
260Hz –3800Hz
260Hz –3800Hz
+/- 3dB
215Hz –8400Hz
215Hz –8400Hz
THD (Audio Input 1kHz)
< 0.25%
< 0.25%
SNR (Audio Input 1kHz)
> 75 dB(A)
> 75 dB(A)
100V Speaker Line Supervision
ELD - 1 Branch
56k 0.4W
56k 0.4W
- 2 Branches
100k 0.4W
100k 0.4W
Strobe Output
ELD - 1 to 3 branches
1x10k - 3 x 27k 0.4W
1x10k - 3 x 27k 0.4W
Current rating
Max 2.0A
Max 2.0A
Audio Inputs
Audio 1 & Audio 2
230mVrms (min) into 5k
isolated for full power
230mVrms (min) into 5k
isolated for full power
Microphone - Input Level
3mVrms-100mVrms, PTT driven,
supervised
3mVrms-100mVrms, PTT driven,
supervised
Digital Inputs
Alarm, AIE, GP1-4
2k7 EOL, <3.5V Active
2k7 EOL, <3.5V Active
Open Collector O/Ps
OC1 & OC2
<1V @ 100mA, 30Vdc
Optionally Load Supervised (fault <12V)
<1V @ 100mA, 30Vdc
Optionally Load Supervised (fault <12V)
OC3 & OC4
<1V @ 100mA, 30Vdc
<1V @ 100mA, 30Vdc
Interfaces
OLED, 4 button menu structured
For operation and configuration
For operation and configuration
QBus compliant
Master / Slave operation, User Interface,
14A PSE and 100V Switching Module
Master / Slave operation, User Interface,
14A PSE and 100V Switching Module
Slave T-Gen2
RJ45 Cable-In Cabinet
RJ45 Cable-In Cabinet
On-board Storage
4Mbyte (configuration and audio files)
4Mbyte (configuration and audio files)
Micro-SD Card - max size
32GB FAT32 support (card not provided)
32GB FAT32 support (card not provided)
Headphone Output (internal) - Load
impedance
8min 6mW
8min 6mW
Audio Output Level
1.30Vrms
1.30Vrms
© 2018. Johnson Controls. All rights reserved. All specifications and other information shown were current as of
document revision date and are subject to change without notice.