Vigilant T-Gen2 User manual

Ref: PBG0214
1 October 2018
Page 1 of 10
T-GEN2 GRADE 2 EMERGENCY WARNING SYSTEM (EWS)
The VIGILANT T-Gen2 Grade 2 Emergency Warning System is available as a
complete 4 Zone Emergency Warning System (EWS) which can be expanded for
larger systems.
The VIGILANT T-Gen2 Grade 2 Emergency Warning System (EWS) is a self-contained
AS 4428.16 Alert and Evacuate tone generator, with integral power supply, digitised speech
messages, and PA microphone. It has been designed to connect directly to a fire alarm
panel, and can also be used as a stand-alone unit.
The EWS contains a 4 zone T-Gen2 Grade 2 User Interface with a speech microphone, T-
Gen120, 14A PSE and 4 x 100V outputs from a Switching Module. It can be expanded up to
20 zones, and additional slave T-Gen2 modules can be added for extra output and
functionality.
Non-emergency paging options, IP remote audio compatibility, and multiple audio inputs
make the VIGILANT EWS a versatile base unit for a variety of applications meeting the multi
zone requirements.
FEATURES AND BENEFITS
Self-contained Emergency Warning System suits multiple applications
Compliant with AS 4428.16 for Grade 2 applications
Emergency PA microphone, Alert/Evacuate/Speech controls
4 zones of control/indication and expandable to 20 zones
Auto/Manual operation
Zone Paging options –up to 20 separately-selectable speaker areas
Selectable priority for Paging/Remote/Background Audio inputs
Alarm inputs and Fault output signals for fire panel connection
Optional High Level Interface with Vigilant MX1, MX4428, F3200 or Simplex 4100ESi
Programmable Alert to Evacuate delay (0-600sec or manual)
Programmable Alert / Evacuate Cascading across all zones.
Pre-recorded Alert and Evacuate messages, field re-recordable for flexibility
Up to 2A Strobe output per T-Gen2
Integral 14 Amp (peak) Power Supply with fault supervision
Space for 2 x 40Ah batteries
Space for 6 x 100V Switching/Splitter Modules for short-circuit isolated outputs
Space for an additional T-Gen 60 or T-Gen 120 for higher loads
Expandable up to 9 synchronized Slaves T-Gens and 9 PSUs
15U 19” rack cabinet: 750mm H x 550mm W x 210mm D (120W)
FP1129

Ref: PBG0214 19 September 2018
Page 2 of 10
GENERAL DESCRIPTION
Figure 1. VIGILANT EWS Functional Block Diagram
The VIGILANT EWS has a microphone for emergency public address, fault and status
indicators, and manual controls to control its operation. It has audio inputs for background
music, remote non-emergency audio (which can be used when streaming audio over IP
networks), or non-emergency paging (zone-selective with an add-on option). Also included
is a 14A power supply.
The base panel (FP1129) and matching expansion cabinet (FP1130) are available as 15U
cabinets.
EXPANSION OF EWS UNITS
The FP1129 15U cabinet is fitted with one T-Gen 120 and one 4-way 100V Switching
Module to provide the four outputs. It can be expanded with an additional T-Gen 60
(FP1115) or T-Gen 120 (FP1116) to provide additional power output. It has space for up to
6 x 100V Switching Modules (FP1117) for zone outputs and short-circuit isolation or 100V
Splitter Modules (FP1118) to provide short-circuit isolated outputs only.
With two T-Gen 120 the FP1129 14A PSU can support up to 240W load, with no strobe load
on each T-Gen 120.
Further expansion can be achieved by using the FP1130 15U expansion cabinet, allowing
additional T-Gen2 (60 or 120W) and switching/splitter modules to be housed adjacent to the
EWS unit.
The T-Gen2 EWS can be expanded up to a total of
10 x T-Gen2 (1 master and 9 slaves)
9 x 14A PSE (monitored)
One User Interface (20 zones max)
10 x 100V Switching Modules
Multiple 100V Splitter Modules per T-Gen2 output.
24V Power Supply
Batteries
2 x 12V 6.5Ah, 12Ah or 17Ah
Emergency
PA Mic
Paging (optional)
100V Speaker Line
Alarm (& fault back)
Remote Audio
Background Music
EOL
EOL
Strobes
Strobes
T-Gen2
Alert and Evacuate Tone Generator(s)
Splitter / Switching Module(s)
100V Speaker Line

Ref: PBG0214 19 September 2018
Page 3 of 10
The gearplate of the FP1129 15U EWS and the FP1130 Expansion Cabinet supports a
number of combinations of T-Gen2 parts, including:
Up to 3 x T-Gen 60 or T-Gen 120 units
Up to 2 x 14A power supplies
Up to 10 x 100V Switching/Splitter Modules
One HLI module (this can alternatively be mounted on the cabinet RHS wall).
Figure 2 shows the various mounting positions on the gearplate –note some positions
overlap so not everything can be fitted at the same time.
T-Gen2 Modules
100V Switch/Splitter/HLI
Modules
2nd 14A PSE
Figure 2 –15U Gearplate Module Mounting Positions
Expanding the User Interface
The 4 zones of User Interface can be expanded to 12 zones by adding the FP1126 3U 16
zone door (refer to the LT0683 instructions for removing the 3U blank and fitting the FP1126
module). This door has only 8 zones fitted as standard.
An additional 8 zones of User Interface can be added (to make 20 zones in total) by fitting
the FP1128 8 Zone Extender kit to the unfilled area on the FP1126 door. Refer to the
LT0684 instructions for fitting.
Figure 3 –FP1126 3U Door Expansion 16 zones (8 fitted)

Ref: PBG0214 19 September 2018
Page 4 of 10
EWS
Alarm Input(s)
Fault Output
ALM-
Fire Alarm
Panel
Alarm Output zone 1
Alarm Output zone 2
Alarm Output zone …
Fault Input
FLT-
0V
COM
NO
NC
GPInput
GPInput
CONNECTING TO FIRE ALARM PANEL
Basic wiring method:
The EWS has multiple inputs that are normally terminated with an EOL resistor and shorted
by the fire alarm panel(s) to activate the Alert / Evacuation tones for each individual zone.
The EWS has a common Fault output (DEF-) which is normally open-circuit and pulled to 0V
on fault. Voltage-free fault relay contacts (NO, NC, COM) are also provided. One of these is
usually wired to the fire alarm system(s) to indicate a fault condition.
High Level Link:
Two wiring options are available:
1) Direct connection MX1 to T-Gen2 using a 10-way ribbon cable:
This option can be used only when the T-Gen2 and MX1 are mounted in the same
cabinet or in a dual cabinet installation, both adjacent to each other. Connection to
external RZDU devices is not possible and Port 0 on the MX1 must not be used for any
other function.
2) HLI board (Optional module FP1143):
The HLI board allows the T-Gen2 to communicate with the Vigilant MX1, MX4428 and
F3200 fire panels using RZDU protocol.
The HLI board (module) includes a separate short-circuit isolated RZDU connection for
wiring to remote RZDU devices –so that a short circuit in the field wiring does not affect
the T-Gen2’s communication with the fire panel. Up to 32 Zone Alarm states and other
triggers can be sent to the T-Gen2 to activate alarms and playing of messages, while
the T-Gen2 can return its fault state.
Remote Zone
Display Unit
EWS
HLI-Module
RZDU-IN
RZDU-OUT
Fire Alarm
Panel
RZDU

Ref: PBG0214 19 September 2018
Page 5 of 10
The HLI module can also be used with Simplex 4100ESi panels. The T-Gen2 connects onto
the internal 4100Comms bus and appears to the 4100ESi as a slave device having a
number of programmable input and output devices.
When using an HLI board to connect the fire panel and EWS, both the fire panel and EWS
must be located side by side.
The HLI board provides a mechanism to exchange 32 alarm signals generate by the Fire
Panel, which can be Zone Alarms or Logical combinations. Each of the alarms can be
assigned to a specific function within the T-Gen2 using SmartConfig. Eg. No function, Alarm
Trigger, Play Signal, Paging Line 1, Paging Line 2, External Power Fault, External Mains
Fault or External Audio Fault.
AREA MAPPING
The T-Gen2 in combination with one or more Switching Modules allows any source of audio
to be mapped to any area. The routing of these audio signals is fully configurable via the PC
application SmartConfig. FP1129 has a default configuration to address 4 individual areas.
Multiple areas can be combined and PA addressed all at the same time.
AUDIO INPUTS
The EWS has two general purpose line-level (230mV) audio inputs. These can be
configured for different operating modes: “Always On / Music”, “Paging Line”to be used with
a Paging Console, and “GP / HLL Input” to be enabled when a specific GP input is active.
These audio inputs could be used for:
Background Music
The audio input is usually configured as “Always On”, and a music source
connected. A volume control is provided to adjust the output level. Screw
terminals and a 3.5mm audio socket are provided for connecting the
background music source to the EWS.
Remote Audio This mode can be used for connecting to external tone/message
generators, specialist paging systems (e.g., PABX), or voice-over-IP (VoIP)
modules (illustrated). A separate digital input is used to enable the audio
input. A volume control is provided to adjust the output level. The priority
of the audio input (relative to the emergency PA microphone and the zone
paging), and whether the remote audio is to override the Alert/Evacuation
tones is configurable. (Note that this would be non-compliant to
AS4428.16)

Ref: PBG0214 19 September 2018
Page 6 of 10
AREA-SELECTABLE PAGING (Two Options)
The EWS can optionally be fitted with up to 6 100V Switching Modules (FP1117), each splits
a single 100V output into four separately selectable 100V line outputs. Each of the 4 outputs
has separate line supervision (o/c & s/c) and the 100V Switching Module will isolate a
shorted output allowing the other outputs to operate. Each output can handle up to 100W
maximum load, but the total load per module cannot exceed the T-Gen2 rating (or maximum
120W per Switching Module in total).
EWS fitted with one 4-way 100V Switching Module
The 100V Switching Modules allow the T-Gen2 to control which outputs receive the 100V
audio signal from the T-Gen2 –making area-specific paging and background music
possible.
USING AN EXTERNAL PAGING CONSOLE
Up to two external 4-zone paging consoles (SU0360) can be combined with an SU0361
Audio Switcher to create a 4-area paging system for the T-Gen2 EWS. The SU0361 Audio
Switcher is mounted in the EWS and wired to 4 GP Inputs to indicate when each area is
active. The Paging Consoles are located where needed and connect to the Audio Switcher
using RJ45 cable.
SU0360 Paging Microphone
SU0361 Audio Switcher
The paging consoles offer a pre-announcement chime which can play a chime signal when
the microphone PTT is activated.
The priority of the paging function compared to the other audio inputs, user functions and
emergency functions is configurable.
EWS
60W or
120W
100V Switching
Module
T-Gen2
Speaker Line/Area 1
Speaker Line/Area 2
Speaker Line/Area 3
Speaker Line/Area 4
EOLR
EOLR
EOLR
EOLR
100V In
100V Out
1
100V Out
2
100V Out
3
100V Out
4

Ref: PBG0214 19 September 2018
Page 7 of 10
LAN
EWS
Master
Annuncicom
EWS
Slave
Annuncicom or
Exstreamer
EWS
Slave
Annuncicom or
Exstreamer
If more than 4 areas of paging are required then the Redback A 4585 16 zone Audio
switcher with up to four A 4586 16 zone paging consoles can be used. The Audio Switcher
may be mounted in the EWS rack cabinet if the depth allows, and is wired to the digital
inputs on the T-Gen2 modules.
The paging consoles are mounted remotely and connect to the Audio Switcher using RJ45
cables.
IP NETWORKING
The EWS supports streaming audio over IP Networks using the BARIX range of Audio-over-
IP modules. There are many possible configurations that can be used, depending on the
application (see LT0561 for more details).
One typical application is to use the BARIX modules to allow a master EWS to make paging
announcements to multiple slave EWS units connected together on a LAN. For this
application, an Annuncicom 200 may be used in the master EWS and either an Annuncicom
200 or Exstreamer 100 at each slave EWS.
When the paging microphone is activated, this is signalled to each slave unit, which in turn
receives streaming audio from the master and broadcasts it over the loudspeakers.
The Barix PS16 Paging Console may also be used to broadcast messages over a LAN to
one or more EWS. The console has 16 buttons which can be configured to select individual
EWS units for paging.
CONFIGURATION
The EWS units come pre-configured with the FP1129_Grade2 configuration. This enables
basic operation on the Grade 2 User Interface, an alarm input, Audio 1 as Always ON and
the 4 x 100V output operate as 4 zones and areas.
Any other configuration, e.g., changing the basic operation, adding Slave T-Gen2 or other
modules, or assign speech, input functions or change the User Interface operation will
require a configuration to be prepared and downloaded using the Windows SmartConfig
application.
LAN
EWS
Annuncicom or
Exstreamer
EWS
Annuncicom or
Exstreamer

Ref: PBG0214 19 September 2018
Page 8 of 10
FURTHER INFORMATION
Details on the various T-Gen2 modules can be found in the latest issue of product bulletin
PBG0203.
SALES DRAWINGS
1992-34 FP1129, FP, T-GEN 2 EWS, GRADE 2 4Z, 15U
1992-37 FP1130, FP, T-GEN 2 EXP CAB, C/W 14A PSU, 15U, BLANK DR
1956-19 FP1116, FP, T-Gen 120, 24V, C/W INSTALL LIT & MTG
1956-21 FP1117, FP, 100V SWITCHING MODULE, C/W LIT, LOOMS & MTG BRK
1956-22 FP1118, FP, 100V SPLITTER MODULE, C/W LIT, LOOMS & MTG BRKT
1992-17 FP1124, FP, GRADE 2 EWS UI 3U DOOR, C/W LOOM & MIC, GREY
1992-29 FP1126, FP, T-GEN 2 GRADE 2, 16Z EWS EXTENDER, 3U DOOR
1956-17 FP1143, FP, T-GEN2 HLI BOARD
PART NUMBERS
FP1115, FP, T-Gen 60, 24V, C/W INSTALL LIT & MTG
T-Gen 60 model of T-Gen2 able to drive a speaker load up to 60W. Supports two non-
emergency audio inputs (BGM, paging), a microphone audio input (Speech or Paging), 6
supervised inputs (Alarm, Fault, Paging), 4 open-collector outputs, normally-energised Fault
relay, supervised single polarity strobe output, and 100V speaker output. Able to fit to
FP1129 or FP1130 as a spare part or Slave T-Gen2.
FP1116, FP, T-Gen 120, 24V, C/W INSTALL LIT & MTG
T-Gen 120 model of T-Gen2 able to drive a speaker load up to 120W. Able to fit to FP1129/
FP1130 as a spare part or Slave T-Gen2.
FP1117, FP, 100V SWITCHING MODULE, C/W LIT, LOOMS & MTG BRK
Provides 4 supervised, short-circuit isolated 100V outputs (each rated at 100W) from the T-
Gen2’s 100V output, along with control of each output by the T-Gen2 to provide area paging.
A QBus slave module. Supplied on MX1-style mounting bracket with cables and EOLs.
Mounts in the EWS cabinet. Can be used as a spare part or expansion module.
FP1118, FP, 100V SPLITTER MODULE, C/W LIT, LOOMS & MTG BRKT
Provides 4 supervised, short-circuit isolated 100V outputs (each rated at 100W) from the T-
Gen2’s 100V output. No control of the outputs is available. Signals fault to the T-Gen2 by
superimposing a fault on the T-Gen2’s 100V input. Standalone operation (not a QBus
slave). Supplied on MX1-style mounting bracket with cables and EOLs. Can be used as an
expansion module.
FP1124 FP, GRADE 2 EWS UI 3U DOOR, C/W LOOM & MIC, GREY
The grey 3U 19” rack mounting door complete with the 4 Zone Grade 2 User Interface and
PA microphone. A 1.5m power loom and microphone extension lead are included to allow
connection to a T-Gen2 mounted in the back of the cabinet. Can be used as a spare part for
the User Interface in FP1129, or for adding to a T-Gen2 in a rack cabinet.
FP1126 FP, GRADE 2 16Z EWS EXTENDER, 3U 19" DOOR, GREY
A grey 3U 19” rack mounting door complete with a 16 Zone Grade 2 User Interface –but
only 8 zones fitted. Connects to FP1124 to expand the capacity from 4 zones to 12 zones.
Add an FP1128 8 Zone Expansion Module to expand to the full T-Gen2 capacity of 20
zones.

Ref: PBG0214 19 September 2018
Page 9 of 10
FP1128 FP, GRADE 2 8Z EXPANSION BRD, C/W LOOM & MTG
An 8 Zone Expansion Module for providing 8 zones of evacuation control and indication. Fits
onto FP1126 to expand to 20 zones, or can be used as a replacement for the 8 Zone Module
already fitted.
FP1130, FP, T-GEN2 EXP CAB, C/W 14A PSU, 15U, BLANK DR
15U titania-coloured cabinet with a blank outer door and a 15U EWS gearplate mounted
inside with a mains GPO and 14A PSE fitted. Suitable for add-on T-Gen2, 100V Switching
Modules, 100V Splitter Modules and up to 40AHr batteries.
FP1139, FP, PSE GEARPLATE MTG, 24V, 14A, SPARE
Replacement 14A PSE for the PSU in the EWS. This can also be used as an expansion
PSU for larger systems.
FP1143, FP, T-GEN2 HLI BOARD
High Level Link Interface module allows an adjacent Vigilant MX1, MX4428 or F3200 fire
panel using RZDU or Simplex 4100ESi fire panel using internal 4100Comms to be
connected to the master T-Gen2 to transmit alarm information (up to 32 fire zones to trigger
EWS) and monitor the EWS fault status.
ME0490 MECH ASSY, 1955-44, T-GEN50, DYNAMIC MICROPHONE
A noise-cancelling dynamic microphone suitable for plugging onto the T-Gen2 to provide
emergency PA or for field recording of the digitised speech message(s). Includes a 1m
extension lead. Suitable as a spare part for the microphone in the EWS.
SU0360 A 4488 4 ZONE PAGING CONSOLE
A 4 zone paging console with microphone and chime option that can be used with the
SU0361 A 4489 Audio Switcher to achieve 4 area paging from remote locations. Up to two
paging consoles can be connected to the SU0361 Audio Switch.
SU0361 A 4489 AUDIO SWITCHER
Used with the A 4428 4 zone paging console to provide relay outputs. Able to be mounted
inside the EWS cabinet.
A 4585 16 ZONE AUDIO SWITCHER
A 16 zone audio switcher that can be used with up to four A 4586 paging consoles to provide
up to 16 zones of paging. May be mounted in 15U cabinets if depth available.
A 4586 16 ZONE PAGING CONSOLE
Used with a A 4585 audio switcher to provide 16 zone of paging. Mounts externally and
connects to the A 4585 using RJ45 cable.
LITERATURE ITEMS
LT0667 T-GEN2 INSTALLATION GUIDE
LT0668 100V SWITCHING MODULE INSTALL INSTRUCTIONS
LT0681 T-GEN2 GRADE 2 UI INSTALL GUIDE
LT0682 T-GEN2 GRADE 2 UI OPERATOR MANUAL
LT0683 T-GEN2 GRADE 2 16Z EXTENDER DOOR INSTALL INSTRUCTIONS
LT0684 T-GEN2 GRADE 2 8Z EXPANDER BOARD INSTALL INSTRUCTIONS
LT0685 T-GEN2 14A PSE INSTALL INSTRUCTIONS
LT0687 T-GEN2 15U EWS INSTALL INSTRUCTIONS
LT0691 T-GEN2 HIGH LEVEL INTERFACE HLI INSTALL INSTRUCTIONS

Ref: PBG0214 19 September 2018
Page 10 of 10
SPECIFICATIONS
FP1129 (15U)
FP1130 (15U)
Weight
26kg
21kg
Size (WxHxD)
550 x 750 x 210mm
550 x 750 x 210mm
PSU Output Current (Peak)
14A
14A
DC Supply Voltage
19.2Vmin - 28.8Vmax
19.2Vmin - 28.8Vmax
Operating Temperature Range
-5C to +45C
-5C to +45C
Relative Humidity
0 to 95% non-condensing
0 to 95% non-condensing
Storage Temperature Range
-20C to +70C
-20C to +70C
Quiescent Current
Audio enabled but idle (no signal)
300mA
Active Current - 27Vdc (excl. Strobe)
6.1A @ 120W
100V Audio
Line Voltage - AC (Tones)
100Vrms
- DC (Supervision)
2.5V (56k ELD 5.0V (O/C))
Line Power - Tones
120W
- Audio
120W
Maximum line capacitance
200nF
Audio Frequency range
+/- 1dB
260Hz –3800Hz
+/- 3dB
215Hz –8400Hz
SNR (Audio Input 1kHz)
> 75 dB(A)
THD (Audio Input 1kHz)
< 0.25%
100V Speaker Line Supervision
ELD - 1 Branch
56k 0.4W
- 2 Branches
100k 0.4W
Strobe Output
ELD - 1 to 3 branches
1x10k - 3 x 27k 0.4W
Current rating
Max 2.0A
Audio Inputs
Audio 1 & Audio 2
230mVrms (min) into 5k
isolated for full power
Microphone - Input Level
3mVrms-100mVrms, PTT driven,
supervised
Digital Inputs
Alarm, AIE, GP1-4
2k7 EOL, <3.5V Active
Open Collector O/Ps
OC1 & OC2
<1V @ 100mA, 30Vdc
Optionally Load Supervised (fault <12V)
OC3 & OC4
<1V @ 100mA, 30Vdc
Interfaces
OLED, 4 button menu structured
For operation and configuration
QBus compliant
Master / Slave operation, User Interface,
14A PSE and 100V Switching Module
Slave T-Gen2
RJ45 Cable-In Cabinet
On-board Storage
4Mbyte (configuration and audio files)
Micro-SD Card - max size
32GB FAT32 support (card not provided)
Headphone Output
Load impedance
8min 6mW
Audio Output
1.30Vrms
© 2018. Johnson Controls. All rights reserved. All specifications and other information shown were current as of
document revision date and are subject to change without notice.