MIRAGE®STANDARD
AND QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK461 (K2.8)
TECHNICAL DATA
Page 4 of 7
Form No. F_091506 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
T
elephone:
269-945-9501
T
echnical
Services:
877-384-5464
Fax:
269-818-1680
Email:
[email protected]Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart 1 (UL)
Mirage® Quick Response Concealed Pendent Sprinkler VK461
For Light Hazard Occupancies Only
Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part
Number1
SIN NPT Thread Size Nominal K-Factor Overall Length
(Sprinkler Body)
Listings and Approvals3
(Refer also to Design Criteria below.)
Inch mm U.S. metric2Inches mm cULus4NYC5VdS LPCB
13831A VK461 1/2” 15 2.8 40.3 2-3/16” 56 AW1, BX1 AW1, BX1 -- -- -- --
Sprinkler Temperature Ratings
A - 155°F (68°C)
B - 175°F (79°C) and 200°F (93°C)
Cover Plate Assembly Temperature Ratings6
W - 135°F (57°C) cULus Listed cover 23190 or 23447, 23174
23463 (large diameter), or 23179 or 23482 (square cover
plate) FM Approved as
139°F (59°C)
X - 165°F (74°C) cover 23190, 23447 or 23174, 23463 (large
diameter)
Finishes of the Cover Plate Assembly7
1 - Polished Chrome, Brushed Chrome,
Bright Brass, Antique Brass, Brushed
Brass, Brushed Copper, Painted White,
Painted Ivory, or Painted Black
Footnotes
1Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2Metric K-factor measurement is shown in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
4Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
5Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 38.
6The 135/139°F cover has an orange label. The 165°F cover has a white label.
7Standard painted finishes consist of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint
colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements: Mirage®Concealed Pendent Sprinkler VK461 is cULus Listed as a quick response sprinkler for installation in accor-
dance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below:
• Limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only.
• Maximum spacing allowed is 15 ft. (4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
• Venting is required.
• Concealed sprinklers must NOT be installed in positive pressure plenums.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation. Also refer to
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the
latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also
with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential
sprinkler installations must be obtained from the Authorities Having Jurisdiction.