STANDARD AND
QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK4621 (K5.6)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
T
elephone:
269-945-9501
T
echnical
Services:
877-384-5464
Fax:
269-818-1680
Email:
[email protected]Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 4 of 8
Form No. F_092121 Rev 01 April 2023
Approval Chart
Concealed Pendent Sprinkler VK4621
Sprinkler
Base Part
No.1
SIN
Thread Size Nominal K-factor Maximum
Water Working Pressure
Listings and Approvals3
(Refer also to Design Criteria)
NPT BSPT U.S. metric2cULus FM cULus4FM
Standard Response Applications
24682A VK4621 1/2” -- 5.6 80.6 -- 175 psi (12 bar) -- AV1, BX1, AS2, BT2
24682JN7,8 VK4621 1/2” -- 5.6 80.6 -- 175 psi (12 bar) -- AV1, BX1, AS2, BT2
22962A VK4621 -- 1/2” 5.6 80.6 -- 175 psi (12 bar) -- AV1, BX1, AS2, BT2
22962JN7,8 VK4621 -- 1/2” 5.6 80.6 -- 175 psi (12 bar) -- AV1, BX1, AS2, BT2
Quick Response Applications
24682A VK4621 1/2” -- 5.6 80.6 250 psi (17.2 bar) -- AV1, BX1, AS2, BT2, AY3, BZ3 --
24682JN7,8 VK4621 1/2” -- 5.6 80.6 250 psi (17.2 bar) -- AV1, BX1, AS2, BT2, AY3, BZ3 --
22962A VK4621 -- 1/2” 5.6 80.6 250 psi (17.2 bar) -- AV1, BX1, AS2, BT2, AY3, BZ3 --
22962JN7,8 VK4621 -- 1/2” 5.6 80.6 250 psi (17.2 bar) -- AV1, BX1, AS2, BT2, AY3, BZ3 --
Sprinkler Temperature Ratings Cover Plate Assembly Temperature Ratings5Cover Plate Assembly
Finishes
A = 155 °F (68 °C)
B = 175 °F (79 °C) and 200 °F (93 °C)
S - 135 °F (57 °C) cULus Listed or 139 °F (59 °C) FM Approved Stainless Steel
cover 23193 and 23455, or 23183 and 23473 (large diameter)
T - 165 °F (74 °C) Stainless Steel cover 23193 and 23455 or 23183 and 23473
(large diameter)
V - 135 °F (57 °C) cULus Listed or 139 °F (59 °C) FM Approved cover 23190
and 23447, 23174 and 23463 (large diameter), or 23179 and 23482 (square
cover plate)
X - 165 °F (74 °C) cover 23190 and 23447, or 23174 and 23463 (large diameter)
Y - 135 °F (57 °C) Clean Room Cover 23174A-/CR and 23463A-/CR or
135 °F (57 °C) Stainless Steel Clean Room Cover 23183A/CR and
23473A/CR
Z - 165 °F (74 °C) Clean Room Cover 23174C-/CR and 23463C-/CR
1 - Polished Chrome,
Brushed Chrome,
Bright Brass, Antique
Brass, Brushed Brass,
Brushed Copper,
Painted6White,
Painted6Ivory, or
Painted6Black
2 - Stainless Steel
3 - Polished Chrome,
Painted White, Painted
Ivory, or Painted Black
Footnotes
1. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
4. Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
5. The 135 °F (57 °C) [139 °F (59 °C)] covers have an orange label. The 165 °F (74 °C) covers have a white label.
6. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information.
7. cULus Listed as corrosion resistant.
8. FM Approved as a decorative finish.
NOTE:Custom colors are indicated on a label inside the cover assembly. Refer to Figure 2.