
Screw: Brass UNS-C36000
Painted black for appearance only.
Pip Cap: Copper UNS-C11000 and
Stainless Steel UNS-S30400,Tef-
lon®Coated
ACCESSORIES
Sprinkler Wrenches:
•Standard Wrench: Part No.
05000CW/B
•Wrenchforcoatedandrecessed
Microfast®Sidewall Sprinklers:
Part No. 07398W*
* A ½" ratchet is required (not available from Vi-
king).
Refer to the “SPRINKLER ACCES-
SORIES” section of the Viking Engi-
neering and Design Databook for tech-
nical data on approved escutcheons
and other accessories.
5. AVAILABILITY AND SERVICE
Vikingsprinklersare available through a
network of domestic, Canadian, and in-
ternational distributors. See the Yellow
Pages of the telephone directory (listed
under “Sprinklers-Automatic-Fire”) for a
local distributor, or contact Viking.
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikingcorp.com.
The Web site may include a more recent
edition of this Technical Data page.
6. GUARANTEES
For details of warranty, refer to Viking’s
currentlistpricescheduleorcontactThe
Viking Corporation directly.
7. INSTALLATION
WARNING:Viking sprinklers are manu-
factured and tested to meet the rigid re-
quirements of approving agencies. The
sprinklersare designed tobeinstalledin
accordance with recognized installation
standards.Deviationfromthestandards
or any alteration to the sprinkler after it
leaves the factory including, but not lim-
ited to: painting, plating, coating, or
modification, may render the sprinkler
inoperative and will automatically nullify
the approval and any guarantee made
by The Viking Corporation.
A.Sprinklers aretobeinstalledinaccor-
dance with the latest published stan-
dards of the National Fire Protection
Association, Factory Mutual, Loss
Prevention Council, Assemblee
Pleniere, Verband der
Sachversicherer or other similar or-
ganizations, and also with the provi-
sions of governmental codes, ordi-
nances,andstandardswheneverap-
plicable. The use of quick response
sidewall sprinklers may be limited
due to occupancy and hazard. Refer
to the Authority Having Jurisdiction
prior to installation.
B.Sprinklersmustbehandled withcare.
They must be stored in a cool, dry
place in their original shipping con-
tainer. Never install sprinklers that
have been dropped, damaged in any
way, or exposed to temperatures in
excess of the maximum ambient
temperature allowed. Never install
any glass-bulb sprinkler if the bulb is
cracked or if there is a loss of liquid
fromthebulb.Ifaglassbulblacksthe
appropriate amount of fluid, it should
be set aside and returned to Viking
(or an authorized Viking distributor)
for analysis as soon as possible. If
thesprinkleris not returned toViking,
it should be destroyed immediately.
C. Corrosion-resistant sprinklers must
be installed when subject to corro-
sive atmospheres. When installing
corrosion-resistant sprinklers, take
care not to damage the corro-
sion-resistant coating. Use only the
special wrench designed for install-
ing coated Viking sprinklers (any
otherwrenchmaydamagetheunit).
D. Use care when locating sprinklers
near fixtures that can generate heat.
Do not install sprinklers where they
will be exposed to temperatures that
exceed the maximum recommended
ambient temperature for the temper-
ature rating used.
E. Before installation, be sure to have
the appropriate sprinkler model and
style, with the proper orifice size,
temperature rating, and response
characteristics.
For allowable deflector distance be-
low ceiling of Microfast®Model M /
M-5 Quick Response Horizontal
Sidewall Sprinklers, refer to approval
chart on page 52 c. Align top of hori-
zontal sidewall deflectors parallel to
the ceiling or roof.
Locate deflectors of Microfast®
ModelM/M-5QuickResponseVerti-
cal Sidewall Upright Sprinklers 4" to
6" (102 mm to 152 mm) below the
ceiling (see approval chart).
Locate deflectors of Microfast®
ModelM/M-5QuickResponseVerti-
calSidewallPendentSprinklersupto
6" (152 mm) below the ceiling (see
approval chart).
Installsidewallsprinklers withdeflec-
tors located 4" to 6" (102 mm to 152
mm)fromwalls.Exception:Sidewall
sprinklers may be installed less than
4" (102 mm) from the wall on which
they are mounted.
The sprinklers must be installed after
the piping is in place to prevent me-
chanical damage.
1. Installescutcheon(if used),which
is designed to thread onto the ex-
ternalthreadsofthesprinkler.Re-
fer to the “Sprinkler Accessories”
section of the Viking Engineering
and Design Databook for ap-
proved escutcheons and other
accessories.
2. Apply a small amount of pipe-joint
compound or tape to the external
threads of the sprinkler only, tak-
ing care not to allow a build-up of
compound in the sprinkler inlet.
3. Install the sprinkler on the piping
usingthespecial sprinklerwrench
only, taking care not to
over-tighten or damage the sprin-
kler operating parts. DO NOT use
the deflector to start or thread the
sprinkler into a fitting.
F. After installation, the entire sprinkler
systemmustbetestedinaccordance
with the recognized installation stan-
dards. The test is applied after sprin-
kler installation to ensure that no
damagehasoccurredtothesprinkler
during shipping and installation, and
to make sure the sprinkler has been
properly tightened. If a thread leak
occurs, normally the sprinkler must
be removed, new pipe-joint com-
pound or tape applied, and then rein-
stalled. This is due to the fact that
when the joint seal is damaged, the
sealing compound or tape is washed
out of the joint. Air testing the sprin-
kler piping prior to testing with water
may be considered in areas where
leakage during testing must be pre-
vented.RefertotheInstallationStan-
dardsand theAuthorityHaving Juris-
diction.
G. Sprinklers must be protected from
mechanical damage. Wet-pipe sys-
tems must be provided with ade-
quate heat. When installing quick re-
sponsesprinklersondrysystems,re-
fer to the Installation Standards and
the Authority Having Jurisdiction.
TECHNICAL DATAMicrofast ®MODEL M / M-5
QUICK RESPONSE
SIDEWALL SPRINKLER
Sprinkler 52 bJune 16, 1999