PLEASE READ THIS INSTALLATION MANUAL CAREFULLY BEFORE INSTALLING
THIS PRODUCT AND KEEP THIS MANUAL FOR FUTURE REFERENCE.
HIGH VOLTAGE WARNING:
Dangerous voltages are present within the power supply. Covers may only be removed
by qualified personnel when the power supply has been disconnected from the mains
supply voltage for more than 3 minutes. Covers must be replaced and all screws secured
properly before reconnecting to the mains voltage.
FUSING WARNING:
To ensure continued protection against risk of fire fuses must be replaced with the same
type and rating of fuse. Replacements should be carried out by qualified personnel only.
INPUT ELECTRICAL –NEVO 600
Nominally 100Vrms to 240Vrms
600 watt output at 180Vrms
NOTES:
1. NEVO 600 inputs can only be used with NEVO series output modules and must not be used for any other
purpose.
2. Use only a power source of the type indicated on the product label for the NEVO 600 inputs.
3. For installation relating to UL60601-1 (Medical) a suitable fuse as described above must be provided in line with
the Neutral inlet.
4. The NEVO 600 input module is supplied with an integrated fan. Ensure that the inlet and outlet ventilation holes
are not obstructed. Ensure there is adequate ventilation provided in the enclosure wherein or near which the
power supply is mounted.
NOTES:
1. NEVO output modules can only be used with NEVO 600 input modules and must not be used for any other
purpose.
2. Take care when removing or adding output modules from the NEVO 600 input so that components are not
damaged in the process.
3. When the output voltage is adjusted upwards, the output current must be decreased proportionally so that the
unit does not exceed the Pmax average power rating as stated in the table above.
4. Peak power up to Ppk is available for not more than 5 seconds at a maximum of 50% duty cycle. The maximum
rated average power must not be exceeded. Please refer to the full datasheet and user manual for more
information on using the Ppk feature.
De-rate input and all outputs at 2.5% / °C
3000 bumps at 10G (16ms) half sine wave
1.5G, 10 to 200Hz sine wave, 20G for 15min in 3 axes
Primary to Secondary(Reinforced)
Primary to Chassis (Basic)
Primary to Secondary(Reinforced)
Primary to Chassis (Basic)
Standard: 250Vac, 60Hz, 25 °C
Medical: 250Vac, 60Hz, 25 °C
77.7mm x 129.7mm x 41.0mm
(all external dimensions ± 1.0mm)
360 grams + 60 grams per output module
Bottom or Side mounting (See diagram details)
IMPORTANT INSTALLATION NOTES
This power supply is intended for use within equipment or enclosures which restricts access to
authorized personnel only. The instructions in this manual and all warning labels on the product must
be followed carefully.
SAFETY
The NEVO 600S is designed in accordance with safety requirements for UL60950-1, EN60950-1,
IEC60950-1, CSA22.2 no. 60950-1 and LV Directive 2006/95/EC.
The NEVO 600M is designed in accordance with safety requirements for UL60601-1, EN60601-1,
EN61010-1, IEC60601-1, IEC61010-1, CSA22.2 no 601-1 and LV Directive 2006/95/EC.
All power supplies must be installed correctly in a controlled environment which restricts access to any
unauthorized personnel. Equipment and system manufacturers must protect service personnel against
unintentional contact with the output terminals.
DERATINGS
Temperature - Input and output power must be de-rated by 2.5%/°C above 50°C.
Input Voltage - Input and output power must be de-rated by 0.55% / Vrms below 180Vrms (402W @
120Vrms, 303W @ 90Vrms)
Always remember to take the appropriate deratings into consideration before specifying any power
supply for an application.
HAZZARDS
If series and/or parallel combinations of outputs exceed safe voltage and/or energy levels, the final
equipment manufacturer must provide appropriate protection for both users and service personnel.
HEALTH AND SAFETY
To comply with section 6 of the health and safety at work act, a label that is clearly visible to service
personnel must be placed on the final equipment, which warns that surfaces of the power supply may
be hot and should not be touched when the product is operating.
FUSING
The power supply has internal single pole fusing in the L (Live) line.
SERVICING
The power supply contains no user serviceable parts. Repairs must be carried out by authorised
personnel only.
APPROVAL LIMITATIONS –NORTH AMERICA
When this product is used with 180VAC–253VAC mains where no neutral is present, connect the two
live wires to L (Live) and N (Neutral) on the input connector.
COOLING
For proper cooling of the power supply, the air intake and outlet must not be impeded. Allow 50mm
clearance at both ends and position cabling appropriately.
EARTH TERMINAL MARKING
To comply with the requirements of UL60950-1, EN60950-1, IEC60950-1, CSA22.2 no. 60950-1,
UL60601-1, EN60601-1, EN61010-1, IEC60601-1, IEC61010-1, CSA22.2 no 601-1 where the incoming
wiring earth is intended for connection as the main protective earth conductor and where the
terminals for such a connection is not supplied on a component or subassembly such as a terminal
block, the user shall add an appropriate label displaying a protective earth symbol in accordance with
60417-2-IEC-5019 directly adjacent to the terminal. The label should be durable and legible and should
withstand the 15s rub test as per UL60950-1 section 1.7.15.
WARRANTY
Contact your sales agent or Vox Power for product repairs. See Vox Power standard terms and
conditions for warranty conditions.
PRODUCT LABELS
NEVO 600M and NEVO 600S
The external product label contains information relevant to the power system. The label contains
input voltage, maximum input current, input frequency, maximum output power, fuse rating and type,
serial number, approvals and product part number in format NEVO 600o-oooo-ooo.
NEVO OUTPUT MODULES
Each output module label contains information relevant to that particular output. The label contains
voltage adjustment range, maximum output current, serial number, approvals and part number in
format OP.
OTHER
A label warning that external surfaces are hot during operation and that the unit should be allowed
to cool down properly should be placed on the unit where such a label is clearly visible.
The NEVO 600 range is designed to comply with EMC standards but it does not imply that the end
system will comply.
To prolong the life of the unit use in dust free environment.
Units can be damaged during transit. Contact your sales agent or Vox Power and DO NOT apply
power to the unit in case of transit damage
Always use adequately sized cables and ensure good crimp connections. Use cable supports to
minimise stress on connectors.
Avoid excessive shock or vibration.