NEVO+1200 Series
INSTALLATION MANUAL
_____________________________________________________________________________________________________
Page 1of 4Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 | www.vox-power.com
DOC-MN-002-05, NEVO+1200 Series Installation Manual
PLEASE READ THIS INSTALLATION MANUAL CAREFULLY BEFORE INSTALLING THIS PRODUCT AND KEEP THIS MANUAL FOR FUTURE REFERENCE.
All specifications are believed to be correct at time of publishing. Vox Power Ltd reserves the right to make changes to any of its products and to change or improve any part of the specification,
electrical or mechanical design or manufacturing process without notice. Vox Power Ltd does not assume any liability arising out of the use or application of any of its products and of any information
to the maximum extent permitted by law. No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted by this document or by any products of Vox Power Ltd.
VOX POWER LTD DISCLAIMS ALL WARRANTIES AND REPRESENTATIONS OF ANY KIND WHETHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF SUITABILITY, FITNESS
FOR PURPOSE, MERCHANTABILITY AND NONINFRINGEMENT.
Please consult your local distributor or Vox Power directly to ensure that you have the latest revision before using the product and refer to the latest relevant user manual for further information relating
to the use of the product. Vox Power Ltd products are not intended for use in connection with life support systems, human implantations, nuclear facilities or systems, aircraft, spacecraft, military or
naval missile, ground support or control equipment used for the purpose of guidance navigation or direction of any aircraft, spacecraft or military or naval missile or any other application where product
failure could lead to loss of life or catastrophic property damage. The user will hold Vox Power Ltd harmless from any loss, cost or damage resulting from its breach of these provisions.
Important installation information
This NEVO+1200 series of configurable power supplies are intended for use within end customer applications which restrict access to un-authorized personnel. The instructions in this manual
and all warning labels on the product must be adhered to carefully.
SAFETY
The NEVO+1200S/SL and NEVO+1200M/ML series are designed in accordance with the relevant safety requirements of IEC/EN/UL/CSA 62368-1, IEC/EN/UL/CSA
60950-1, IEC/EN/UL/CSA 60601-1, Low voltage Directive LVD 2014/35/EU and EMC directive EMC 2014/30/EU. All NEVO+1200 series power supplies must be
installed correctly in a controlled environment which restricts access to any un-authorised personnel. Equipment and system manufacturers must protect
service personnel against unintentional contact with the output terminals.
HAZZARDS
Dangerous voltages are present within the power supply.
It should only be handled by qualified personnel when the power supply has been disconnected from the mains supply voltage for more than 3 minutes.
External surfaces of the power supply may become extremely hot during and after operation. Appropriate care should be taken. If series and/or parallel
combinations of outputs exceed safe voltage and/or energy levels, the final equipment manufacturer must provide the appropriate protection for both users
and service personnel.
DE-RATINGS
Ambient
Temperature
•The input module power must be de-rated by 2.5%/°C above 50°C ambient up to a maximum ambient temperature of 70°C.
Input Voltage
•The input module power must be de-rated by 10W/VRMS below120 VRMS (1200W @ 120 VRMS, 850W @ 85 VRMS)
Remember to take the appropriate de-rating into consideration before specifying any NEVO+1200 power supply for an application.
If in any doubt, please contact Vox Power directly or your local Vox Power representative.
HEALTH AND SAFETY
To comply with section 6 of the health and safety at work act, a label that is clearly visible to service personnel must be placed on the final equipment. These
labels warn that surfaces of the power supply may be hot and should not be touched when the product is operating.
FUSING
The power supply has internal single pole fusing in the L (Live) line.
Fuses are not replaceable.
Damaged units should be returned to Vox Power for analysis and repair.
For Medical (60601-1) installations, the end application should provide an appropriately rated external fuse in the Neutral line.
DC operation is not covered by safety approvals. Contact Vox Power for details.
SERVICING
The power supply contains no user serviceable parts. Repairs must be carried out by authorised personnel only.
Contact Vox Power for further information.
APPROVAL
LIMITATIONS
NORTH AMERICA - When this product is used with 180V
AC
–253V
AC
mains where no neutral is present, connect the two live wires to L (Live) and N (Neutral) on the
input connector.
COOLING
For proper cooling of the power supply, the air intake and outlet must not be impeded. Allow 50mm clearance at both ends and position cabling appropriately.
EARTH TERMINAL
MARKING
To comply with the requirements of IEC/EN/UL/CSA 62368-1, IEC/EN/UL/CSA 60950-1 & IEC/EN/UL/CSA 60601-1, where the incoming wiring earth is intended
for connection as the main protective earth conductor and where the terminals for such a connection is not supplied on a component or subassembly, the user
shall add an appropriate label displaying a protective earth symbol in accordance with IEC60417-5019 (2006-08) directly adjacent to the terminal. The label
should be durable and legible and should withstand the 15 second rub test as per UL60950-1 section 1.7.15.
WARRANTY
Contact your sales agent or Vox Power for product repairs. See Vox Power standard terms and conditions for warranty conditions.
PRODUCT LABELS
The external product label contains information relevant to the power system. The label contains input voltage, maximum input current, input frequency,
maximum output power, fuse rating and type, serial number, approvals and product part number in form NEVO+1200x-yyyyyyyy-zzz.
NEVO+ OUTPUT
MODULES
Each output module label contains information relevant to that output. The label contains voltage adjustment range, maximum output current, serial number,
approvals and the part number in format OPx.
OTHER
•
A label warning that external surfaces are hot during operation and that the unit should be allowed to cool down properly should be placed on the unit
where such a label is clearly visible.
•The NEVO+1200 series is designed to comply with EMC standards but it does not imply that the end system will comply.
•To prolong the life of the unit, use in dust free environment.
•Units can sometimes be damaged during transit. In the event of transit damage, DO NOT connect power to the unit. Contact your sales agent or Vox
Power.
•Always use adequately sized cables and ensure good crimp connections. Use cable supports to minimise stress on connectors.
•
Avoid excessive shock or vibration.
Page 2of 4Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 | www.vox-power.com
DOC-MN-002-05, NEVO+1200 Series Installation Manual
Specifications
INPUT MODULE SPECIFICATION SUMMARY
Parameter
Details
Min
Typical
Max
Units
AC Input Voltage
Nominal range is 100V
RMS
to 240V
RMS
85
264
V
RMS
AC Input Frequency
Contact factory for 400Hz operation.
47
50/60
63
Hz
DC Input Voltage
Not covered by safety approvals. Contact Vox Power.
120
370
V
DC
Output Power Rating
Standard & Medical (S/M) - De-rate linearly from 1200Watts at 120V
RMS
to 850Watts at 85V
RMS
Low Noise (SL/ML) - De-rate linearly from 900Watts at 120VRMS to 638Watts at 85VRMS
1200
900 Watts
Input Current
Standard & Medical (S/M) - 1200Watts output at 120Vrms input
Low Noise (SL/ML) - - 900Watts output at 120Vrms input
12
9 Amps
Fusing
Live line fused (5x20 Fast acting)
12
Amps
Power Factor
0.99
Size
154.5 (L) x 152.4 (W) x 41.0 (H) (see diagram for tolerance details)
mm
Weight
720 + 60 per output module
Grams
Note 1.
Note 2.
NEVO+ input modules can only be used with NEVO+ output modules and must not be used for any other purpose.
Only use a power source of the type indicated on the product label.
OUTPUT MODULE SPECIFICATION SUMMARY
MODEL Output Voltage Output
Current
Rated
Power
Peak
Power
Load
Reg.
Line
Reg.
Cross
Reg.
Ripple &
Noise FPMH (1) Feature
Set (2)
Min.
Nom.
Max.
OP1
1.5V
5V
7.5V
25A
125W
187.5W
±50mV
±5mV
±10mV
50mV
PP
0.5
ABCDEFG
OP2
4.5V
12V
15V
15A
150W
225W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFG
OP3
9V
24V
30V
7.5A
150W
225W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFG
OP4
18V
48V
58V
3.75A
150W
217.5W
±300mV
±48mV
±96mV
480mV
PP
0.5
ABCDEFG
OP5
3.3V
12V
15V
5A
2x 75W
2x 75W
±50mV
±12mV
±24mV
240mV
PP
0.75
AFG
OP8
23.2V
24V
24.7V
3.125A
2x 75W
2x 75W
±100mV
±24mV
±48mV
480mV
PP
0.75
AFG
OPA2
4.5V
12V
15V
25A
300W
375W
±100mV
±12mV
±24mV
120mV
PP
0.5
ABCDEFGH
OPA3
9V
24V
30V
15A
300W
450W
±150mV
±24mV
±48mV
240mV
PP
0.5
ABCDEFGH
Note 1.
Output module, 30˚C base, 100% load, SR332 issue 2 Method I, Case 3, Ground, Fixed, Controlled
Note 2.
A = Remote Sense, B = External Voltage control, C = External constant current control, D = Current output signal, E = Current share, F =Over Voltage protection,
G = Over temperature protection, H = Dual Slot module
SAFETY SPECIFICATIONS
Parameter Details Max Units
Isolation Voltages
Input to Output (2 MOPP). Do not perform test on assembled unit(1)
4000
V
AC
Input to Chassis (1 MOPP)
1500
V
AC
Global signals (J2) to Output/Chassis
250
V
DC
Output to Output/Chassis (Standard modules)
250
V
DC
Earth Leakage Current
INDUSTRIAL: Normal condition, 264Vac, 63Hz, 25°C
1500
uA
MEDICAL: Normal condition, 264Vac, 63Hz, 25°C
300
uA
Touch Leakage Current
Standard modules NC/SFC
20/200
uA
Patient Leakage Current
Standard modules 264Vac, 63Hz, 25°C NC/SFC
(2)
-----
uA
Note 1. Testing an assembled unit to 4000V
AC
may cause damage. Please refer to application note (APN-002) on Vox Power website or contact Vox Power representative.
Note 2. Not Applicable
INSTALLATION SPECIFICATIONS
Parameter Details Parameter Details
Equipment class
I
Flammability Rating
94V-2
Overvoltage category
II
Ingress protection rating
IP10
Material Group
IIIb (indoor use only)
ROHS compliance
2011/65/EU
Pollution degree
2
Intended usage environment
Home Healthcare (M/ML)/ Industrial (S/SL)
ENVIRONMENTAL SPECIFICATIONS
Parameter Details Non-Operational Operational Units
Min Max Min Max
Air Temperature
Operational limits subject to appropriate de-ratings
-40
+85
-20
70(1)
°C
Humidity
Relative, non-condensing
5
95
5
95
%
Altitude
-200
5000
-200
5000(2)
m
Air Pressure
52
104
52(2)
104
kPa
Noise Level
Standard Versions (S/M) - Variable. Measured 1m from fan intake.
Low Noise Versions (SL/ML) - Variable. Measured 1m from fan intake.
42
24
61
42 dBA
Shock
3000 bumps at 10G (16mS) half sine wave
Vibration
1.5G, 10 – 200Hz sine wave, 20G for 15min in 3 axes.
Notes
1. Derate input and all outputs at 2.5%/°C above 50°C.
2. 3000m & 68kPa for IEC/UL60601-1.
Page 3of 4Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 | www.vox-power.com
DOC-MN-002-05, NEVO+1200 Series Installation Manual
Mechanical Dimensions and Mounting
MECHANICAL DIMENSIONS AND MOUNTING
SCREWS
LOCATION
DETAILS
PENETRATION
TIGHTENING
MOUNTING M4
4mm max, including chassis
0.5 NM
OUTPUT MODULES M3 x 5, Countersink Posi, 16 Places Defined by screw 0.5 NM
CHASSIS LID AND FACEPLATE
M3 x 5, Countersink Posi, 9 Places
M3 x 30, Countersink Posi, 2 Places
Defined by screw 0.5 NM
Torque settings are for general reference only. The torque settings shown are the insert manufacturers recommended values.
Page 4of 4Vox Power Limited | Unit 2, Red Cow Interchange Estate, Ballymount, Dublin 22, D22 Y8H2, Ireland | T +353 1 4591161 | www.vox-power.com
DOC-MN-002-05, NEVO+1200 Series Installation Manual
Connector details
PINOUTS
Circuit
Details
J1 – Mains Input
1
Live
2
Earth
3
Neutral
J2a/b – Global Signals
1
Slot A/E - Power Good
2
Slot A/E - Inhibit
3
Slot B/F - Power Good
4
Slot B/F - Inhibit
5
Slot C/G - Power Good
6
Slot C/G - Inhibit
7
Slot D/H - Power Good
8
Slot D/H - Inhibit
9
Global Inhibit [A-D]/[E-H](GINH)
10
AC OK
11
+5V (Bias Supply 1A)
12
COM
J6 -Input Signals
1
Common
2
+5V 0.5A Bias (Always on)
3
Shut Down
4
Reserved
5
Reserved
6
Reserved
MATING CONNECTORS
Ref.
Details
Manufacturer
Housing
Terminal
J1 - Mains Input
3 Pin, Barrier, 6-32 steel Screws, 0.8NM or 7 Lb-In Torque
(1)
J2a/b - Global Signals 12 Pin, 2mm, 24-30 AWG, WIRE TO BOARD MOLEX(3) 0511101251 0503948051
Output Power(2)
Faston/Quick-Connect Tab – Size 6.35x0.8mm
VARIOUS(3)
VARIOUS
J6 - Input Signals
6 Pin, 1.25mm, with Friction Lock, 28-30AWG
MOLEX(3)
1510210600
50058800
Notes
1. Cable 14-18AWG, 300V, 16A, 105°C, use appropriately rated crimp terminal.
2. Terminal and wire current rating must exceed maximum short circuit output current. Eg. Output 1 = 25A*1.25 = 31.25A.
3. Direct equivalents may be used for any connector parts.
4.
All cables must be rated 105°C min, equivalent to UL1015.
PART NUMBERS AND ORDERING INFORMATION
NEVO Power Series
NEVO+1200 S L - 1 1 2 2 3 3 4 4 - 0 0 0
Factory Use
Leakage Current
USE '0' for unused
slots. Blanking
plates will be
inserted at factory.
M = Medical,
S = Industrial
Fan
Blank = Standard,
L = Low Noise
Slot A - Output #
Slot H - Output #
Slot B - Output #
Slot G - Output #
Slot C - Output #
Slot F - Output #
Slot D - Output #
Slot E - Output #
Industrial input module has ITE approvals (IEC60950 & IEC62368), Medical input module has medical approvals (IEC60601)
Contact your Distributor or Vox Power for special configuration requirements. The factory may allocate a 3 digit suffix to identify such requirements.
When ordering an input unit with no outputs inserted, use NEVO+1200M/ML or NEVO+1200S/SL.
Unless stated otherwise, all dimensions are in millimetres and in accordance with DIN2768-1/2 CLASS C

This manual suits for next models

2

Other Vox Power Power Supply manuals

Vox Power VCCM600S Series User manual

Vox Power

Vox Power VCCM600S Series User manual

Vox Power NEVO+1200S Guide

Vox Power

Vox Power NEVO+1200S Guide

Vox Power NEVO+ Series User manual

Vox Power

Vox Power NEVO+ Series User manual

Vox Power NEVO Plus 1200 Series User manual

Vox Power

Vox Power NEVO Plus 1200 Series User manual

Vox Power Nevo+ 1200 series User manual

Vox Power

Vox Power Nevo+ 1200 series User manual

Vox Power VCCM600 Series User manual

Vox Power

Vox Power VCCM600 Series User manual

Vox Power VCCM600 Series User manual

Vox Power

Vox Power VCCM600 Series User manual

Vox Power NEVO+600 Series User manual

Vox Power

Vox Power NEVO+600 Series User manual

Vox Power VCCS300 Series User manual

Vox Power

Vox Power VCCS300 Series User manual

Vox Power NEVO+600 Series User manual

Vox Power

Vox Power NEVO+600 Series User manual

Vox Power VCCM600S Series User manual

Vox Power

Vox Power VCCM600S Series User manual

Vox Power VCCR300 Series User manual

Vox Power

Vox Power VCCR300 Series User manual

Vox Power NEVO 600S Series User manual

Vox Power

Vox Power NEVO 600S Series User manual

Vox Power NEVO+ 600M User manual

Vox Power

Vox Power NEVO+ 600M User manual

Popular Power Supply manuals by other brands

StarTech.com ATXPOWER400 Instruction guide

StarTech.com

StarTech.com ATXPOWER400 Instruction guide

Puls QT40.481 installation manual

Puls

Puls QT40.481 installation manual

V-TAC VT-303 instruction manual

V-TAC

V-TAC VT-303 instruction manual

Owon OWP H Series user manual

Owon

Owon OWP H Series user manual

SDC 602RF installation instructions

SDC

SDC 602RF installation instructions

Pulsar HPSBOC 1824B manual

Pulsar

Pulsar HPSBOC 1824B manual

Ganz GH Series instruction manual

Ganz

Ganz GH Series instruction manual

Puls QTD20.241 instruction manual

Puls

Puls QTD20.241 instruction manual

Niko 10-801 instructions

Niko

Niko 10-801 instructions

Joy-it JT-RD6006 manual

Joy-it

Joy-it JT-RD6006 manual

Sadelta SPS-3036D user manual

Sadelta

Sadelta SPS-3036D user manual

Global Specialties 1403 user manual

Global Specialties

Global Specialties 1403 user manual

Pepe Tools IPS Series user manual

Pepe Tools

Pepe Tools IPS Series user manual

Delta Electronics DPS-350PB-2 Specifications

Delta Electronics

Delta Electronics DPS-350PB-2 Specifications

TDK-Lambda ZWP350-1000 Series instruction manual

TDK-Lambda

TDK-Lambda ZWP350-1000 Series instruction manual

HP 6012A Operating and service manual

HP

HP 6012A Operating and service manual

BASETech BT-155 operating instructions

BASETech

BASETech BT-155 operating instructions

Ryobi RP4900 Operator's manual

Ryobi

Ryobi RP4900 Operator's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.