INSTALLATION GUIDE
Magnetostrictive Sensor Series MSB
For more information please see the data sheet at www.waycon.biz/products/magnetostrictive-transducers/
ELECTRICAL CONNECTION
ELECTRICAL CONNECTION MSB...N/K/E-F1
MSB...N-F1 MSB...K-F1 MSB...E-F1 Cable
0.1...10.1 V 0.1...5.1 V yellow
Output GND Output GND Output GND pink
Pow er Supply + Pow er Supply + Pow er Supply + brow n
Pow er Supply GND Pow er Supply GND Pow er Supply GND blue
4...20 mA
- The transducer must be installed in a grounded metallic cylinder.
- The braiding of the shielded transducer connection cable must be connected to the case of the female
connector so that the shielding is connected to the transducer case.
- The cable shielding on PL side must be isolated.
- If the transducer is installed in a cylinder isolated from the ground, the cable shielding on PL side must
be grounded.
- The transducer must be installed away from sources of magnetic fields, both static and 50 Hz (electric
motors, solenoids, etc.).
- The 24 VD feed must be dedicated to the transducers or must be drawn directly from the power
terminals and as near as possible.
- The sensors must be powered with non-distributed networks and always at lengths of less than 30 m.
- The magnetic cursor must be installed by placing a non-magnetic spacer (made of brass, aluminium,
stainless steel or plastic) between the piston surface and the cursor.
MSB
Standard Installation (recommended)