TEACHING THE SWITCHING OUTPUT
Teach-In of P2 (SP2 position):
Connect the Teach-In line with GND until the P2 and Echo LEDs start blinking with a 2 Hz frequency.
First P1 and Echo LEDs will be blinking but it is important to wait to reach P2. The sensor is now in
Teach-In mode for P2: P1 LED blinks with 1 Hz frequency now. The Echo LED returns to normal function
(alignment LED). There is a time window of 30 s to do the programming of P2. Place target to the new
position P2. Contact and release the Teach-In line with GND: P2 is now programmed. Sensor returns
into normal function with new value for P2.
Switching output characteristics:
The output characteristics can be selected during Teach-In of the set points P1 and P2. For each set
point and during the teaching procedure, when the LED is ON when contacting and releasing the
Teach-In line to GND, the switching output will have NO characteristics, when doing this when the LED
is it OFF, the switching output will have NC characteristics.
NO characteristic (opener)
NC characteristic (closer)
Window function / Hysteresis adjustment
Connect the Teach-In line with GND until P1, P2 and Echo LEDs start blinking with a 2 Hz frequency.
Before reaching the hysteresis Teach-In mode, the sensor will go through the P1 and P2 teaching
sequence. Keep the Teach-In line connected to the GND until reaching the point when all LEDs are
blinking with a 2 Hz frequency. Release the Teach-In line contact. The sensor is now in Teach-In mode
for window function/ hysteresis adjustment: P1+P2 LEDs are blinking with a 1 Hz frequency. The Echo
LED returns to its normal function (alignment LED). There is a time window of 30 s to complete the
programming. Contact and release the Teach-In line with GND.
Pay attention to P1 and P2:
If P1+P2 LEDs are OFF during the contact
with the Teach-In line, the sensor will operate
the in window function: If there is an object
between P1 and P2, SP1 will switch ON and
SP2 will switch OFF. If there is no object
between P1 and P2, SP1 will switch OFF and
SP2 will switch ON.
If P1+P2 LEDs are ON during contact, the
sensor will operate in hysteresis mode: The
switching output SP1 will be (NO) at P1 with
hysteresis P1-P2 and switching output SP2
will be (NC), also at P1 with hysteresis P1-P2.