Wine Master SP40DUPRO User manual

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
Installation and user manual
(please keep this document carefully)
INDICATIONS STATED ON THE NAMEPLATE OF THE UNIT
oModel :
………………………………..
oSerial N° :
…………………………..
oPurchase date :
………………………...
UTILISATION
WINESP40DUPRO
Page 2
Installation and user manual
(please keep this document carefully)
SP40DUPRO
INDICATIONS STATED ON THE NAMEPLATE OF THE UNIT
:
………………………………..
…………………………..
………………………...
(please keep this document carefully)

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 3
User manual
Table of contents
.
TECHNICAL DATAS .................................................................................... 5
2.
EQUIPMENT ............................................................................................... 7
2.1.
Outside unit ....................................................................................................................7
2.2.
Inside unit.......................................................................................................................7
2.3.
Thermostat......................................................................................................................7
2.4.
Connection box..............................................................................................................7
2.5.
Connection drawing.....................................................................................................7
2.6.
Cellar insulation ............................................................................................................8
2.6.1.
Insulation of walls, ceiling and floor..............................................................................................9
2.6.2.
The door ......................................................................................................................................................9
2.6.3.
Insulation of other elements ..............................................................................................................9
3.
INSTALLATION OF THE AIR CONDITIONER WINEMASTER
®
..................... 0
3. .
List of required material .......................................................................... 0
3.2.1.
Wall drilling..............................................................................................................................................10
3.2.2.
Brackets installation ............................................................................................................................10
3.2.3.
Fixing the outside unit.........................................................................................................................10
3.2.4.
Air flow ......................................................................................................................................................10
3.3.
Installation of the inside unit ..................................................................
3.4
Ducting connection .................................................................................. 2
3.5
Electric connection .................................................................................. 2
3.5.
Connection of outside unit.................................................................................................................12
3.5.2
Connection of inside unit....................................................................................................................12
3.5.3
Plugging ....................................................................................................................................................12
3.5.4
Wiring drawing .......................................................................................................................................13
3.6
Installation of the water drain system .................................................... 4
4.
PLUGGING THE AIR CONDITIONER WINEMASTER
®
................................. 4
4. .
Connecting the air conditioner ................................................................ 4
4.2.
Start up ................................................................................................... 5
4.2.1.
Temperature setting.............................................................................................................................15
4.2.2.
Standby mode .........................................................................................................................................15
4.2.3.
Automatic defrost..................................................................................................................................15
5.
MAINTENANCE OF THE AIR CONDITIONER WINEMASTER
®
..................... 6
5. .
Filter and outside unit cleaning ............................................................... 6
5.2.
Condensates drain ................................................................................... 6
6.
EXAMPLE OF INSIDE UNIT INSTALLATION .............................................. 7
6.
Installation above the air conditioned room ............................................ 7
6.2
Installation beside the air conditioned room ........................................... 7
7.
Warranty ................................................................................................. 8
7. Legal warranty .......................................................................................... 8
7. 2 years contractual warranty ....................................................................... 8
7.3
Warranty conditions ................................................................................ 8
7.4
Exclusions and limitations of warranty .................................................... 8
GB

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 4
Introduction
You purchased an air conditioner W NEMASTER
®
and we thank you for your confidence.
From conception to marketing, everything has been implemented to offer an
exclusive and high quality product. Brainchild of a team who find in this a motivation to
ever satisfy you, we hope that your wine conditioning unit W NEMASTER
®
will bring you
great storage conditions and best wines aging for an incomparable pleasure.
Because the customer is at the heart of all our thoughts, we want to support you in your
first steps and lead you towards the best use of your air conditioner every day. Thus,
you will find in this manual technical information and practical advice to help you to deal
with the essential steps to installation and use.
n order that your wine tasting remains moments to share, W NEMASTER guarantees
you a sincere engagement, dedicated expertise and ongoing follow-up at your service!
W NEMASTER.

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 5
1. TECHNICAL DATAS
WINESP40DUPRO
Outside unit nside unit
Weight of units 35 kg 26 kg
Dimensions H x L x D 408 x 633 x 415 317 x 638 x 546
Temperature setting
Preset at 12°C, adjustable between 4 & 15°C
*
Maximum outside temperature.
40°C
**
Cooling power
900 W at 15°C
**
Electricity supply 230/240V-50 Hz
Cooling power 600 W
Heating power 500 W
Gas R404A
The circuit breaker must be at least 6 Amps.
* The insulation has to be in accordance with the volume of the cellar and the set temperature.
** The cooling performance is dependant from the outside temperature. Therefore, the set temperature
of 12°C for the cellar cannot be maintained if the outside temperature reaches the 40°C.
f the thermal safety functions to often, there is a risk for the compressor to be damaged. n all cases, it
must be avoid that the outside temperature remains at 40°C, this high temperature should be limited
to the summer period.
VENTILATED COLD OR « NO FROST »
The advantages of « ventilated cold »:
- No frost other than on the evaporator.
- Automatic defrosting and maximized refrigeration efficiency.
- Cold distribution improved by a permanent air circulation (without air stratification).
The circulation of air allows maintaining the pre-selected temperature throughout the cellar
- .

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 6
Technical drawing
•Outside unit
•nside unit
•Thermostat
•Wiring brox

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
2. EQUIPMENT
The air conditioner is composed of 2 separate units, of a thermostat and a wiring box. They must be
connected by frigorific ducting pipes and electric connections.
The ducting pipes length between both unit
2.1.Outside unit
The unit must be installed outside or in a room.
f the unit is installed outside:
-
Place the unit in order the air suction and air rejection are not disturbed
-
Encourage the installation in open areas and sheltered from
-
Be cautious to the noise to the neighborhood
-Raise the unit to prevent
from
f the unit is installed in a room :
-
Place the unit in order the air suction and air rejection are not disturbed
-Ensure there is a good ve
ntilation
-Maximum temperature
and non permanent
-deal temperature ≈ 20°C.
2.2.Inside unit
The inside unit is
designed to be installed with
2.3.Thermostat
The thermostat can be installed either inside or
The probe must always be placed in the air conditioned room. The supplied sensor has a length of 1,5m.
t can be extended using insulated flexible cable with 2 conductors of 0.5mm² minimum section.
2.4.Connection box
The
connection box can be installed too either inside or outside the wine cabinet.
into consideration the cable length ( 2 m)
2.5.Connection drawing
TAKE INTO CONSIDERAT
OUTS DE UN T
NO CABLE SUPPL ED
UTILISATION
WINESP40DUPRO
Page 7
The air conditioner is composed of 2 separate units, of a thermostat and a wiring box. They must be
connected by frigorific ducting pipes and electric connections.
The ducting pipes length between both unit
should not exceed 20m.
The unit must be installed outside or in a room.
Place the unit in order the air suction and air rejection are not disturbed
Encourage the installation in open areas and sheltered from
the sun
Be cautious to the noise to the neighborhood
from
accumulation of water and snow
Place the unit in order the air suction and air rejection are not disturbed
ntilation
and non permanent
≤ 40°C
designed to be installed with
a duct
system. t has to be placed inside the house
The thermostat can be installed either inside or
outside the air
conditioned room
The probe must always be placed in the air conditioned room. The supplied sensor has a length of 1,5m.
t can be extended using insulated flexible cable with 2 conductors of 0.5mm² minimum section.
connection box can be installed too either inside or outside the wine cabinet.
into consideration the cable length ( 2 m)
TAKE INTO CONSIDERAT
ION THE CABLE LENGTH
S BETWEEN THE
CONNECTION BOX AND THE UNITS
THERMOSTAT
CABLE LENGTH 2M
MA N CONNECT ON
NO CABLE SUPPL ED
VERS AL MENTAT ON GENERAL
The air conditioner is composed of 2 separate units, of a thermostat and a wiring box. They must be
system. t has to be placed inside the house
conditioned room
.
The probe must always be placed in the air conditioned room. The supplied sensor has a length of 1,5m.
t can be extended using insulated flexible cable with 2 conductors of 0.5mm² minimum section.
.
connection box can be installed too either inside or outside the wine cabinet.
f installed outside, take
S BETWEEN THE
NS DE UN T
CABLE LENGTH 2M

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 8
2.6.Cellar insulation
Insulation is essential for an efficient functioning of the W NEMASTER
®
. An appropriate insulation
enables to maintain a stable temperature and humidity level. The chart on the next page will allow
you to determine the type and thickness of insulation needed in relation to the exterior volume of the
cellar and the model of the W NEMASTER
®
, for an inside temperature of 12°C.
Insulation complement
The insulating elements should be preferably installed:
- By “tongue and groove “ panels or
- By fused together panels
IMPORTANT : Avoid heat and humidity intrusion which can alter their regulation
View
1. WALL
2. NSULAT ON MATER AL
3. GROUND LEVEL
4. FLOOR
5. CE L NG
6. NSULATED DOOR
IMPORTANT
The W NEMASTER
®
warranty is only valid if the insulation is in compliance with the board « nsulation
selection » requirements for the whole cellar (walls, floor, door and ceiling) with perfect continuity of
insulation.
Insulation selection
Volume of
the cellar
(m³)
Polystyrene
expanded = 0,044
W/m°C
(mm)
Polystyrene
extruded
= 0,030 W/m°C
(mm)
Polyurethane foam
= 0,025 W/m°C
(mm)
4 20 10 10
8 30 20 20
12 50 30 30
16 60 40 40
20 80 50 50
24 90 60 50
28 100 70 60
32 120 80 70
36 140 90 80
40 150 100 90
f implementation of glass walls, the Ug value of the glazing should be a maximum of 1.0 W / m²K. n
addition, the glass surface cannot be greater than 50% of the total wall area of the air-conditioned room.
2

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 9
2.6.1.
Insulation of walls, ceiling and floor
Type of insulation panels
You can select among the following type of panels:
- Usual panels,
- « Complex panels »: insulation is covered with a with a cover material (plaster, mineral …..)
- « Sandwich panels »: insulation is covered on each side with a wooden panel or plaster board.
mportant: The covering of the panels protects the insulation against damage and guarantees its
longevity. Avoid using mineral fibres insulation (glasswool, rockwool, etc…) as they may
accumulate moisture and lose their insulation power and avoid also thin film insulation
that are not
effective for cold.
DO YOU KNOW THAT ?
Some insulating materials are damaged by rodents. f necessary, cover the insulation with a protective
lining on the inside of the cellar to avoid presence of mouse or rats.
Polyurethane is an insulator that, due to its chemical composition, is not attacked by the
rodents.
Floor insulation
The floor of the cellar must be able to support the shelves and the stored wine. Thus, it’s necessary to
choose insulation with adequate compression strength.
mprove the load capacity of the insulation (particularly under the shelve legs) by using :
- « Complex » insulation panels covered by panels of higher load capacity.
- Cover the insulation panel with a wooden panel (at least 15 mm thickness), or every other
appropriated material.
2.6.2.
The door
Door improves the insulation. Two solutions are possible:
- Insulate an existing door with the same insulation materials used for the walls of the
cellar. Provide a tight seal between the door frame and all sides of the door with a strip of foam
rubber for example.
Use a specially design WINEMASTER isothermal door with polyurethane and a sealing foam
View
1. NSULATED DOOR
2. NSULAT ON
3. SEAL NG TAPE
2.6.3.
Insulation of other elements
Avoid placing a wine cabinet or freezer who generates heat into the cellar. The central heating pipes
should be re-insulated during their passage through the cellar.

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
3.
INSTALLATION OF THE AIR CONDITIONER WINEMASTER
3.1.List
of required material
-
A cord 4G1.5mm² for outside unit connection
-
A cord 3G1.5mm² for the connection of wiring box
-
Copper pipes 1/4" & 3/8" for the cooling connection
3.2.
Screws and tools for fixing the outside unit
3.2.1.
Wall drilling
3.2.2.
Brackets installation
3.2.3.
Fix
ing the outside unit
3.2.4.
Air flow
-
BLOW NG
UTILISATION
WINESP40DUPRO
Page 10
INSTALLATION OF THE AIR CONDITIONER WINEMASTER
of required material
A cord 4G1.5mm² for outside unit connection
A cord 3G1.5mm² for the connection of wiring box
Copper pipes 1/4" & 3/8" for the cooling connection
Screws and tools for fixing the outside unit
nstallation of the outside unit
-
Trace and drill the holes
Brackets installation
-
Unfold the brackets and fi
the supplied parts
ing the outside unit
-
Screw the 4 anti
-
Place the air conditioner on the brackets
-
Screw the 4 screw
key of 10
-
Visser les 4 plots anti
SUCT ON
INSTALLATION OF THE AIR CONDITIONER WINEMASTER
®
nstallation of the outside unit
Trace and drill the holes
locations as
indicated
Unfold the brackets and fi
x them with
the supplied parts
Screw the 4 anti
-vibration pins on the unit
Place the air conditioner on the brackets
Screw the 4 screw
-washer M6 using a
Visser les 4 plots anti
-vibrations (fournis)
SUCT ON

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 11
3.3.Installation of the inside unit
Due to the diversity of wine cabinets and the type of locations, each installer must adapt to the
constraints of its installation.
- Use insulated ducting Ø125mm
- Make sure to choose the perfect place to
have a length of the shortest ducting
possible (14m max / reduce 1 m by
number of elbow)
- Radius elbow ≥ 175 mm
- Do not reduce the duct section
- The suction and blowing should in no way be
even partially obstructed
- The blowing and suction should be
separated to avoid a resumption of the air
supply, even partially (for checking, the
suction temperature should be the same
as the room temperature when the unit
produces cold)
- Provide openings on the bottom for
suction and blowing
- Provide space for refrigeration and
electrical connections and the passage of
the condensate drain
Two decoration grids are supplied with the unit. These grids are adapted to the air flow .
SUCT ON
BLOW NG

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
3.4 Ducting connection
THE PIPE CONNECTION
Both units are loaded with an inert
gas (nitrogen). Connect the 2 units by a copper line 1/4" for the la
liquid line and 3/8" for the gas
line. The nuts are provided. Put them on the copper rigid pipe before
performing the extender.
The maximum length is of 20 m,
the
must not exceed 10.
Lenghts
0-5 m
5 to 10 m
10 to 15 m
15 to 20 m
When all is working properly,
before disconnecting the
Disconnect then the pipes and
replace
3.5 Electric connection
3.5.
Connection of outside unit
-
Unscrew and remove the cover from outside unit
-
Unscrew the cover from the waterproof box
-
Connect the box and the outside unit via the
(§3.4.5)
- Close the waterproof box
- Close the outside unit
3.5.2
Connection of inside unit
-
Unscrew and remove the front cover
-
Plug the power cord, as per wiring drawing (§3.4.5)
- Close the cover
3.5.3 Plugging
The connecting box has to be connected
30mA - 230V - 16A.
THE UNIT HAS TO BE
UTILISATION
WINESP40DUPRO
Page 12
THE PIPE CONNECTION
HAS TO BE
UNDERTAKEN BY A PROF
gas (nitrogen). Connect the 2 units by a copper line 1/4" for the la
line. The nuts are provided. Put them on the copper rigid pipe before
maximum elevation is 10 meters.
The number of bends
Gas loading (R404A)
900 g
1000 g
1100 g
1200 g
before disconnecting the
pipes
, unscrew fully the valves
replace
the gaps on the valves.
Connection of outside unit
Unscrew and remove the cover from outside unit
Unscrew the cover from the waterproof box
Connect the box and the outside unit via the
4G1.5 cord (not supplied
)
Connection of inside unit
Unscrew and remove the front cover
Plug the power cord, as per wiring drawing (§3.4.5)
The connecting box has to be connected
to a single phase power line protected by a circuit breaker
THE UNIT HAS TO BE
INSTALLED RESPECTING THE NATIONAL RULES OF ELECTRIC
INSTALLATIONS.
UNDERTAKEN BY A PROF
ESSIONNAL.
gas (nitrogen). Connect the 2 units by a copper line 1/4" for the la
line. The nuts are provided. Put them on the copper rigid pipe before
The number of bends
per link
, unscrew fully the valves
.
)
as per wiring drawing
to a single phase power line protected by a circuit breaker
INSTALLED RESPECTING THE NATIONAL RULES OF ELECTRIC

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
3.5.4 Wiring drawing
UTILISATION
WINESP40DUPRO
Page 13

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
3.6
Installation of the water drain system
THE TUBE DRA N SHOULD NOT BE
The condensate
bucket may overflow if the drain is not directed downwards
4.
PLUGGING THE AIR CONDITIONER WINEMASTER
The thermostat indicates the temperature in the wine cellar with a precision of 2°C. A temperature
variation of the air doesn’t mean the same variation of the liquid due to the thermal capacity of the liquid.
The thermostat is set at 12°C in the factory. D
controlled and adjusted as indicated
(§4.2.1).
4.1.
Connecting the air conditioner
When you plug the unit to the electric socket, the display indicates the temperature of the wine
cabinet :
- f the temperatu
re is over the thermostat setting: the air conditioner starts running after 2
minutes.
-
f the temperature is under the thermostat setting: the compressor doesn’t start.
ventilator of inside unit works.
2
UTILISATION
WINESP40DUPRO
Page 14
Installation of the water drain system
-
The evacuation of the condensate is ma
drain pipe supplied with the unit
-Fit the drain pipe on the
bracket
supplied with the unit
-
The flow is done by gravity and must be connected to a
sewage or bucket that must regularly be emptied
THE TUBE DRA N SHOULD NOT BE
CLOOGED OR DO LOOP UP!
bucket may overflow if the drain is not directed downwards
PLUGGING THE AIR CONDITIONER WINEMASTER
The thermostat indicates the temperature in the wine cellar with a precision of 2°C. A temperature
variation of the air doesn’t mean the same variation of the liquid due to the thermal capacity of the liquid.
The thermostat is set at 12°C in the factory. D
uring the installation, the set temperature must be
(§4.2.1).
Connecting the air conditioner
When you plug the unit to the electric socket, the display indicates the temperature of the wine
re is over the thermostat setting: the air conditioner starts running after 2
f the temperature is under the thermostat setting: the compressor doesn’t start.
ventilator of inside unit works.
The evacuation of the condensate is ma
de through a
drain pipe supplied with the unit
bracket
(1) with a clamp (2)
The flow is done by gravity and must be connected to a
sewage or bucket that must regularly be emptied
bucket may overflow if the drain is not directed downwards
PLUGGING THE AIR CONDITIONER WINEMASTER
®
The thermostat indicates the temperature in the wine cellar with a precision of 2°C. A temperature
variation of the air doesn’t mean the same variation of the liquid due to the thermal capacity of the liquid.
uring the installation, the set temperature must be
When you plug the unit to the electric socket, the display indicates the temperature of the wine
re is over the thermostat setting: the air conditioner starts running after 2
f the temperature is under the thermostat setting: the compressor doesn’t start.
Only the

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 15
4.2.
Start up
4.2.1.
Temperature setting
The setting of the targeted temperature is made on the thermostat:
- Press on one second until the targeted temperature is blinking.
- Use to increase the temperature.
- Use to lower the temperature.
-
Once the right temperature is set, press on again to confirm.
Explanations on the main display symbols: :
Red light = cold more engaged (compressor working)
Red light = cooling fan on high speed
Red light = defrost
Red light = heating mode engaged (resistance)
4.2.2.
Standby mode
- Standby mode: maintain 3 seconds on button 1. The compressor stops
and the fan turns at low speed.
- The thermostat indicates « OFF » and also the cellar temperature.
- To come back, maintain again a 3 seconds pressure on button 1.
- The thermostat indicates « ON » during 1 second
-
4.2.3.
Automatic defrost
The program of the thermostat will run an automatic defrost time several times a day. During this
operation, the compressor is stopped, only the fan is functioning at low speed. The condensate water
produced during this period will be evacuated through the tube drain.

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
5.
MAINTENANCE OF THE AIR CONDITIONER WINEMASTER
5.1.
F
ilter and outside unit
T
he outside unit is equipped with a washabl
CHECK AND
CLEAN THE FILTER REGULARLY
DUSTED FILTER = DAMAG
CHECK AND CLEAR THE OPENINGS
CLOGGED AIR INLET = DAMAGED AIR CONDITIONER
5.2.
Condensates drain
Check and clean the drain once a year.
UTILISATION
WINESP40DUPRO
Page 16
MAINTENANCE OF THE AIR CONDITIONER WINEMASTER
ilter and outside unit
cleaning
he outside unit is equipped with a washabl
e and reusable filter.
Unscrew the 2 plastic screws (1)
Remove the filter cover (2)
Take the filter out (3)
Wash the filter with warm water
Once the filter cleaned and drained,
replace the filter back and close the cover
CLEAN THE FILTER REGULARLY
DUSTED FILTER = DAMAG
E ON THE AIR CONDITIONER
CHECK AND CLEAR THE OPENINGS
REGULARLY
CLOGGED AIR INLET = DAMAGED AIR CONDITIONER
Check and clean the drain once a year.
MAINTENANCE OF THE AIR CONDITIONER WINEMASTER
®
Unscrew the 2 plastic screws (1)
Remove the filter cover (2)
Take the filter out (3)
Wash the filter with warm water
Once the filter cleaned and drained,
replace the filter back and close the cover
E ON THE AIR CONDITIONER

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
6.
EXAMPLE OF INSIDE
6.
Installation above the air conditioned room
6.2
Installation beside the air conditioned room
UTILISATION
WINESP40DUPRO
Page 17
EXAMPLE OF INSIDE
UNIT INSTALLATION
Installation above the air conditioned room
Installation beside the air conditioned room

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 18
7. Warranty
The contractual warranty is not exclusive, earnings for the benefit of the purchaser profit of the legal
warranty against defects or hidden defects that applies under the conditions of article 1641 and following
from the civil code.
7. Legal warranty
The contractual warranty is not exclusive, earnings for the benefit of the purchaser profit of the legal
warranty against defects or hidden defects that applies under the conditions of article 1641 and following
from the civil code.
7. 2 years contractual warranty
W NEMASTER offers a
2 years warranty against any manufactured defect.
During this period of contractual warranty, W NEMASTER will replace any acknowledge defective part.
n case of electric failure, W NEMASTER reserves the right to check the appliance before replacing any
defective parts.
n case of refrigeration failure, W NEMASTER may require that the appliance is returned to the factory for
repair. Any interventions will take place according to the guidelines set in the ‘after sale service
document’.
Interventions and returns can only be done after written agreement from WINEMASTER after
sale service.
7.3 Warranty conditions
The contractual warranty applies to all appliance installed and used in conformity with this «user
manual ». His application is conditioned by the presentation of the purchase invoice or for lack of its
copy.
7.4 Exclusions and limitations of warranty
The warranty can be refused in following cases:
- nsulation of the cellar or installation of the appliance not in compliance with the instructions of this
guide.
- Damages due to negligence, lack of maintenance or incorrect use of the air conditioner
W NEMASTER
®
(particularly clogged filters.
- Exchange of parts or repair under warranty will not extend the 2 years warranty period.
W NEMASTER SAS cannot, in any case, be held liable for any direct or indirect damages resulting from
the failure of the air conditioner. The warranty is exclusively limited to the product itself.
The European Community is attaching a great importance to the environment and
the waste process, set up by a instruction N° 2002/96/CE relating to the electric and
electronic component waste (DEEE).
n accordance with this standard, the logo « crossed dustbin » is obligatory.
This logo means that the appliance may not under any circumstances be
thrown in the household garbage. t must be handed over to the appropriate
collection point for its treatment, recovery and recycling of wasted electric and
electronic components.
Acting like that, you make a gesture for the environment and contribute to the
safeguard of the natural resources as well as to the protection of human health.

G
UIDE D
'
INSTALLATION ET D
’
UTILISATION
WINESP40DUPRO
Page 19
Table of contents
Other Wine Master Wine Cooler manuals

Wine Master
Wine Master WineC25 User manual

Wine Master
Wine Master Wine C50S User manual

Wine Master
Wine Master Hygromaster User manual

Wine Master
Wine Master SP40DU4 User manual

Wine Master
Wine Master WineARM15 User manual

Wine Master
Wine Master C50 IN User manual

Wine Master
Wine Master WinePC15 User manual

Wine Master
Wine Master WineIN50+ User manual

Wine Master
Wine Master Wine C18 User manual