Winland EnviroAlert EA800-ip User manual

Quick Start Guide
Before
Installation
•Local device password is 0800.
•In order to access the device on the Web Portal the device needs to be
communicating with our host server.
•A 30 minute timer starts on the device as soon as power is applied. At
least one (1 sensor must be programmed locally or remotely within the
30 minutes or an alarm will occur. This timer is in place to remind install-
ers the device requires programmed sensors for functionality; it can be
canceled by pressing “timer” (F3 button .
•Wired sensor inputs are numbered 1 - 4. Wireless sensors are in posi-
tions 5-12.
•Wireless output relays are assignable and numbered 1 - 8.
•Wireless sensors must be set up locally at the device to ensure com-
munication.
Device Input Voltage 1 1 to 26VDC @ ≤ 500mA current draw
Wireless Sensor Input Voltage
(EA-WMFS, EA-WTS, EA-WHS
12VDC @ ≤ 100mA current draw via 2.1
mm barrel plug, center positive OR 2 AA
Alkaline Batteries (1.5V Cell
Device Auxiliary
Output Voltage
Equivalent to DC Input Voltage used: 11 to
26VDC. (Maximum output current 0.5A .
Device and Wireless Sensor
Environmental Operating Range
Temperature: 0°C to 50°C (32°F to 122°F .
Not for installation inside coolers or freez-
ers. Humidity: 5% to 95% RH, non-
condensing.
Ambient Environmental Quality Indoor use intended, non-corrosive environ-
ment.
Relay Contact Ratings Max 30VDC @ 1 Amp, resistive
Real-Time Clock Battery CR2032 (3V Cell
Ethernet (wired 10/100BASE-TX/FX; fully compliant to IEEE
802.3u standard
Tech Support 8:00am - 5:00pm Central Time
(800) 635-4 69 www.winland.com
This guide provides basic setup instructions for the EA800-ip
Critical Environment Monitoring System and associated
sensors. Installers should refer to the Installation Manual
(found on-line at www.winland.com) for more
information, specifications, and to become familiar with the
device features. The device allows connection of up to 4 wired
and 8 wireless sensors and has 8 assignable dry contact alarm
loop connections.
Cloud Based Monitoring: The EA800-ip utilizes a cloud
computing architecture, no client software is required.
This version describes features only available on the INSIGHT
system using the firmware version C15f or higher.
S
PECIFICATIONS
©6
RJ
“Hereby Winland Electronics, Inc. declares that this environmental
monitoring equipment is in compliance with the essential
requirements and other relevant provisions of Directives 2014/53/
EU; 2014/30/EU; 2014/35/EU; 2011/65/EU. The declaration of
conformity may be consulted at: https://www.winland.com/
resources/regulatory-compliance/D-037-0010.pdf".

Read
the
Installation Manual
for Details.
Installation Manual can be found online a t w w w . winland.com
•All
power terminals
must
be connected
to a
Class
2
power
limited
circuit
complying
with
National Electrical Code
NFPA 70,
Article 725.
Where
required,
this equipment is to be isolated from
the main supply by a limited power
source
as
specified
in
EN60950
.
•
Batteries
shall not
cause explosion
or
produce
a fire
hazard
as a
result
of
excessive charge or
discharge
.
•
Ensure
all wiring for wired
sensor connections
is
done before
powering on
or programming the
device
.
•
If
the
equipment
is
used
in a
manner
not
specified
by the
manufacturer,
the
protection provided by the equipment may be
impaired.
CAUTION
Wired Sensor Inputs
Relay Outputs
Electronic Serial Number and Key Code
INSTALLATION OVERVIEW
1.
Install EA800-ip Device
Do not connect or disconnect sensors or wiring to a security panel while
power is applied to the device. Connecting and disconnecting the Device
with power connected may damage the Device or result in improper or
unreliable operation.
-Connection of unsuitable loads to the AUX Power Out connection may
damage the power supply and Device, or result in improper or unreliable
operation.
Web Based Monitoring:
To manage or monitor the Device through the
cloud-based software application, it must be connected to a wired
Ethernet connection with Internet access. The Device works in the same
way as a PC with the Device being a client. The Device is hosted on our
customized Web Services Platform. The Device will only connect to this
server. It is not possible to connect to an internal server.
- Location: Device should be installed in a clean, non-condensing
environment.
- Using the terminal block adapter supplied, connect power supply + and
- leads to POWER IN (+ and (- on J5. Observe proper polarity.
- EA800-ip Input Voltage: 11 to 26VDC at ≤ 500mA
Note:
The input
voltage specification does not include requirements for loads connected
to the Aux Power Out.
- When Device is powered, a 30-minute timer starts. The Device will
alarm after this timer expires unless one or more sensors are set-up.
- If Aux Power Out is to be used, connect + and - leads to AUX POWER
OUT (+ and (- on J5 using a terminal block adapter.
2. Test Network Connection
Connect the Device Ethernet cable to a laptop computer that is set for
a
wired
Internet connection. Browse
to a
reliable website
to
validate
I
nternet
connectivity
.
3. Connect Wired Et ernet to Device
The Device requires a wired 10/100BASE-TX/FX Ethernet connection to
communicate with the cloud application and is conforms to IEEE 802.3u
standards.
4. Verify Network Connectivity
Device Network Settings: Unless a static IP address is needed, you will
not need to modify the Device’s
network settings.
On power-up the Device first automatically attempts to obtain an IP
address using DHCP. It will then attempt to contact a DNS server to get
the host IP address. Then it will contact out Host Server.
To verify Internet connection, troubleshoot connection, or to manually
assign the Device’s IP settings, navigate to the Network menu. The
Device must first be unlocked to access this menu. (Press F1 and enter
password.
5. Verify t e Internet Connection
When successfully connected to the Host Server, the “DIAGNOSTICS”
screen should look similar to this:
A “IP-^:” (Host Server address must
be present for the Device to communi-
cate with the Host Server (the actual
address may be different than the
illustration .
Information for Network Administrators
The device needs to be able to make a DNS query. It also needs to make an
outbound TCP/HTTP or HTTPS connection to the host using a URL
programmed into the firmware, on port 443.
DNS: If DHCP is enabled, the device makes a DNS query to the DNS server
based on assigned network settings. If DHCP is disabled (i.e. static IP is
enabled it will use the DNS server at the specified IP address. DNS uses UDP
and connects to the DNS server on port 53. There are situations where the
DNS may get reissued using TCP on port 53.
Once installed and configured the EA800-ip communicates to the Host System
on a 30-second interval. It does not accept any inbound connections.
Attention:
Experience has shown that some firewall rules may consider this
frequent traffic as abnormal and cause the connection to be shut down. To
avoid connection trouble, check with your network administrator.
FIGURE 1: Device Connec7ons Shown From Back

INSTALL OVERVIEW (continued)
6. Troubles oot Internet Connection
If no “IP-^:” address is present, do the following checks:
- Ensure the “CLOUD” setting is selected in the CLIENT MODE screen.
Then go back to Step 2 “Test Network Connection.”
The Device is designed for plug-and-play functionality. If the Device does
not connect after above steps have been taken, it may be necessary to
obtain help from a network technician to perform the following steps:
- Go to “About EA800” screen, press F2 to Select “ENET” screen, then
press F2 again for the “MORE” Screen. Check that the “IP”, “Subnet” and
“Gateway” addresses are appropriate for your network.
- Using a PC on the same local network as the Device, try to ping the “IP”
address. Failure indicates the local network is not connecting.
- If your network requires a static IP address, go to the NETWORK
screen, Select “CLIENT MODE” then select “CLOUD” then “DISABLED.”
You will be prompted to enter the Static IP address, Subnet address,
Gateway address and DNS address. You will be prompted to press “OK”
to reboot.
Note: Once your account has been activated, the Device can be config-
ured using Winland’s secure online web service.
Note: If configuring online, ensure the NO SENSORS INSTALLED timer
is canceled after powering the Device. ( Wireless sensors must be con-
figured at the keypad.
7.
Place and Connect Wired Sensors
Place wired probes and connect cables to Device. Sensor cables may be
extended up to 1,000’ (305 m using 22 AWG twisted pair. Wired input
terminals 1 - 4 are located at the top of the Device ( see Figure 1 . Wire
alarm loops to relay output terminals located at the bottom of the Device
( see Figure 1 . It would be best to determine ahead of time which relay
will be assigned to which sensor.
8.
Unlocking/Locking Device
Press F1 to unlock Device. The default password is 0800.
See Installation/Owner’s Manual to
customize password.
To enter password, press F3 (Next to move
the cursor one digit to the right.
Use the arrow keys to change the numeric
value to 0800, then press
.
The Device is now unlocked.
After completion of set-up, press F1 to lock
the Device, if desired.
The Device locks automatically if no keys are
pressed within 30 minutes.
9.
Set Date and Time
NOTE:
When connected to the Winland Web Servce, the Date and Time
are set automatically and cannot be changed. To manually set the Date
and Time when not using INSIGHT, the “Cloud” setting in the
“CLIENT MODE” menu must be set to: DISABLED.
To set time and date format: The defaults are
24-hour clock (military time and mm/dd/yyyy
format. To change to 12-hour clock or dd/mm/
yyyy format if desired, go to MAIN MENU,
select SYSTEM:
; select Configuration:
; select Date Format or Time Format
;
then select the preferred configuration. Press F3 (OK to set.
To set time and date: go to MAIN MENU, select System, 8 ; select Set
Date or Set Time, 8 ; follow menu prompts and use PREV and NEXT soft
keys to select the desired values. Press F3 (OK to set.
10. Add Sensors
At device, press Menu key, then
, use
arrow keys to select SENSORS and press:
. Select ADD NEW SENSOR, and press:
. Follow procedure 10a if adding a wired
sensor and procedure 10b if adding a wireless
sensor.
Note: Wired sensors can be programmed at the Device or via web. Wireless
sensors must be programmed at the Device to ensure connection.
10a. Add Wired Sensors
Wired Sensors can be programmed locally. Wired Sensors can also be
programmed via Insight account before or after being connected to
Device.
If wired Sensors were programmed via
Insight, and wired correctly before
Device site installation, the timer does
not apply.
Select Wired,
. Next select the output
relay you wish to use for this sensor (1-8 or
Aux only . Select the type of sensor being connected. You can opt to select
from a list of Common names or create a Custom name (16 characters or
less . After assigning a name, continue to follow the on-screen prompts to
complete the sensor programming. See Installation/Owner’s Manual for
details. Repeat setup for each additional wired sensor. The steps may vary
depending on the sensor type being added.
Note:
A single relay can be
assigned to more than one sensor.
Note: For detailed information on configuring a 4-20mA sensor, please refer to
the Installation/Owner’s Manual.
Non-Internet Connected Installations: Disable the Internet functionality by
going to the NETWORK screen, select “CLIENT MODE” then select
“DISABLED.” You will be prompted to press “OK” to reboot.

INSTALL OVERVIEW (continued)
10b. Add Wireless Sensors
Remove cover from wireless sensors until setup is complete. On Device, se-
lect Wireless, press
. The Device begins searching for a connection with
the wireless sensor. With the wireless sensor unmounted and located near the
Device, apply power to the sensor using remote power supply or 2 AA
batteries. It is recommended that power is applied to one sensor at a time, and
that the setup is completed for that sensor before adding subsequent wireless
sensors. The search may take a few minutes.
Note: Press the Reset Button on the sensor to restart the search process if
necessary. Verify the number shown on the Device screen matches the
number on the sensor’s PC board. Press:
. If the list the screen does not
contain the number found on the sensor’s PC board, press F1 (Cancel to
continue the search process. Select the output relay to which the wireless
sensor is to be assigned, (1-8 or Aux only then press:
. Continue the
setup based upon the type of wireless sensor being added.
Note:
A single relay can be assigned to more than one sensor.
Wireless Multi-Function Sensor (EA-WMFS)
Wireless multi-function sensors provide a wireless transmitter for
connection to a wired probe. Select the type of probe to be connected to the
wireless multi-function sensor, then press:
.
Assign a Common name or Custom name to the probe, and continue to follow
on-screen prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Note: The Wireless Multi-Function Sensor (EA-WMFS supports the following
probe types:
White Temperature Probe (TEMP-UL-S
Blue Temperature Probe (TEMP-L-W and TEMP-L-S
Red Temperature Probe (TEMP-H-W and TEMP-H-S
Supervised WaterBug® Sensor (W-S-S and W-UC-S
Contact Sensors (N.O. and N.C.
Wireless Temperature Sensor (EA-WTS)
Assign a Common name or Custom name to the sensor, and continue to
follow on-screen prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Wireless Humidity Sensor (EA-WHS)
Assign a Common name or Custom name to the sensor, and continue to
follow on-screen prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Repeat setup for each additional wireless sensor. The steps will vary
depending on the type of sensor being added.
Verifying Signal Strengt
After temporarily mounting the wireless sensors in the desired location,
verify the signal strength at the Device by pressing MENU, select Sen-
sors, select Performance, then select the wireless sensor to
be checked, It may take as long
as 30 seconds to acquire the current
signal strength.
If “No Data” is displayed in place of
bars, it indicates that recent signal
strength information has not been re-
ceived. If this persists for 1-2 minutes without displaying any perfor-
mance bars, it is a strong indication that your Sensor is placed out of
range with the Device.
If fewer than two bars are shown, first try a different wireless channel
setting (see note below . Otherwise, the wireless transmitter should be
relocated to obtain a better signal. Refer to the instruction sheet included
with the wireless sensor for details on ensuring optimum signal strength.
NOTE:
If drop-outs occur or signal strength remains low it is recommend-
ed that the RF Channel be set to 25, or 26 ( preferred or at least 5
channels above or below the currently selected channel.
11.
Advanced Settings
Refer to the Installation Manual found online at www.winland.com for
configuring the following advanced EA800-ip settings:
Configure Relays
Pause Monitoring
Replace a Sensor
Editing Sensor Parameters
Change Sensor Data Collection Frequency
Change the Buzzer Setting
Clear the Alarm/Sensor Logs
Save or Load Configuration Settings
Export Stored Logs
Other manuals for EnviroAlert EA800-ip
2
Table of contents
Other Winland Security System manuals