Wolf ATEX LL-260 Troubleshooting guide

LL-1148 Issue 6
DF461
Wolf ATEX Splitter Box
Operation and Maintenance Instructions
Please Retain – Read Before Use
Models
LL-260/(suffixes define enclosure, cable, plug, socket and fuse options)
The Wolf ATEX splitter box meets all relevant provisions of the 2014/34/EU
Explosive Atmospheres (ATEX Equipment) Directive by virtue of the issued
EU type examination certificate, and subsequent review confirming
compliance with all relevant harmonised standards and essential health and
safety requirements.
The Wolf ATEX Splitter Box range use GRP and 316 stainless steel
enclosures protected with a 316 Stainless Steel Skid. The splitter box is
approved as Group II, equipment for use in zone 1 & 2 potentially explosive
gases, vapours, mists and where a T5 temperature class is permitted and in
zone 21 & 22 dusts where the surface temperature T90ºC permits. ATX,
CEAG, STAHL or Marechal sockets may be fitted. SY, SB and HOFR can be
used when connecting into the splitter box via approved glands.
CERTIFICATION/APPROVAL CODE
II 2 GD*
Ex d e IIC T5 Gb
Ta
-
20ºC**
to +50ºC***
Ex tb IIIC T90ºC Db
IP66***
*
*When CEAG GHG 54.. range of sockets are used the splitter box is limited
to Gas only atmospheres.
**When SY cable is used, T amb min =
-
15ºC
.
*** When total input current ≤10A T amb max = +55ºC (CEAG, STAHL,
MARECHAL sockets only)
.
**** When CEAG GHG 5118.. range of sockets are used the splitter box is
IP64 rated and when CEAG GHG 54 range of sockets are used the splitter
box is IP54 rated
,
Check product label for specific voltage information, approval codes,
certification, IP and fuse ratings.
CERTIFICATION (see product label for code).
EU Type examination certificate: Baseefa12ATEX0268X
Notified Body Baseefa Limited Rockhead Business Park
Staden Lane Buxton Derbyshire
SK17 9RZ
Notified body number: 1180
Specific Conditions For Use (‘X’ Conditions)
1. Unused terminals are to be tightened to values below –
Din Rail
-
0.6Nm
ATX Socke
t
–
2Nm
CEAG
Socke
t
–
2.5Nm
STAHL Socket – 1.2Nm Marechal Socket – 2Nm
2. Only one conductor per terminal.
3. The uninsulated part of the conductor must not extend beyond the
terminal throat.
Harmonised standards applied:
EN60079
-
0: 2012
+
A11:
2013
EN60079
-
1: 20
14
EN60079
-
7: 20
15
EN60079
-
31: 20
14
Alex Jackson – Managing Director
Wolf Safety Lamp Company Ltd.
IECEx Scheme Certification
Certificate Number: IECEx BAS 16.0073X
II 2 GD*
Ex d e IIC T5 Gb
Ta
-
20ºC**
to +50ºC***
Ex tb IIIC T90ºC Db
IP66***
*
*When CEAG GHG 54.. range of sockets are used the splitter box is limited
to Gas only atmospheres.
**When SY cable is used, T amb min =
-
15ºC
*** When total input current
≤10A T amb max =
+55ºC
**** When CEAG GHG 5118.. range of sockets are used the splitter box is
IP64 rated and When CEAG GHG 54 range of sockets are used the splitter
box is IP54 rated
,
IECEx scheme certification only covers Splitter boxes fitted with
CEAG, STAHL, MARECHAL sockets only
IEC60079
-
0: 2011
IEC60079
-
1: 2007
IEC60079
-
7:
2006
IEC60079
-
31: 2008
European Design No001 425 201
UK Patent 2 526 256 B
IMPORTANT
1. Read the instruction leaflet carefully before commencing to use the
splitter box and retain it for future use.
2. Check the rating label to ensure the splitter box is suitable for the
supply voltage, T class, ambient temperature present and IP rating.
3. Splitter boxes constructed from GRP (Glass Reinforced Polyester)
and their mounted sockets are plastic, the end user must ensure that
these materials are suitable for the atmosphere the splitter box will be
used in. Excessive force should not be used on plastic components.
4. The Splitter box must not be opened when energised and if fitted with
a fuse, a delay of 5 mins after disconnection from the mains supply
must be observed before opening.
USER GUIDANCE FOR WOLF SPLITTER BOXES
1. It is the user's responsibility to ensure there is no potential difference
between the earth supply to the splitter box and the earth where it is
sited. Where this is not possible the splitter box should also be locally
earth bonded. A flexible cable with a conductor area of 6mm2
minimum which is no longer than two metres is recommended for
this. The splitter box must be de-energised during connection or
disconnection of the local earth bond.
2. The user must consider the effect of voltage losses on the input cable
to the splitter box, to ensure that products connected to the splitter
box are operating within their specified voltage tolerance.
3. The supply cable must be inspected on a regular basis to ensure
there is no damage to the cable.
4. Splitter boxes have terminal blocks suitable for up to 4mm2live,
neutral and earth.
5. Approved cable glands must be used and be suitable for the type of
cable used and the environment to be used in.
6. Do not overload the source supply. It is the user's responsibility to
ensure products connected to the splitter box do not exceed the 15A
maximum input current rating of the splitter box.
7. If the Wolf Splitter Box is fitted with a fuse, it will be an IEC 60269,
80kA breaking capacity cartridge fuse. The fuse type and maximum
value must not be exceeded. Replace with like for like fuse and
secure the screwed cover on fully.
Details of the fuse fitted is found on the splitter model
identification label which is attached to the lid
Replacing these with fuses of a different type or of a higher rating
could result in an unsafe condition occurring in the safe or hazardous
area. To prevent nuisance tripping, the total power of apparatus
operated from the splitter box should not exceed the rated maximum
amperage of the fuse. Where apparatus other than Wolf lighting
products are connected, its load should be checked to ensure it is
suitable for use with type gG (general) fuses.
8. Where the splitter box is connected to a Wolf Safety ATEX
transformer, ensure that the connected circuits do not exceed total
maximum loading and maximum cable lengths permissible (see
transformer instructions for details). When calculating the maximum
cable length, the total must include the length of the splitter box input
cable. Where cables with different conductor areas are combined, the
maximum cable length should be selected based on the smallest
conductor area. Exceeding recommended cable lengths could result
in an unsafe condition in the safe or hazardous area in the event of a
fault occurring.
For additional advice regarding the permissible maximum cable
lengths Suggested lighting layouts for splitter e-mail
info@wolfsafety.com
MAINTENANCE
1. Disconnect the splitter box from the mains before carrying out any
maintenance.
2. It is essential that the splitter is maintained in accordance with the
requirements of EN60079-17
3. A visual check should be carried out to ensure all internal cables are
in good condition, and not suffering any sign of damage or
degradation. All internal connections should be checked to ensure
that they are correctly secured.
4. The splitter box input cable and any attached cables should be
inspected before each use. Any damaged cables should be replaced
immediately.
5. The condition of the gaskets on the enclosure and sockets should be
inspected to ensure there is no breakdown in the units IP rating.
6. IMPORTANT. No modifications are permitted to the splitter box or
sockets.
7. IMPORTANT. Use only genuine Wolf replacement parts.
The Wolf Safety Lamp Co. Ltd has a policy of continuous product
improvement. Changes in design details may be made without prior
notice.
E-mail: info@wolfsafety.com Website: www.wolfsafety.com
LL-1148 Issue 6
DF461
Splitter Box Spares.
WARNING: USE ONLY GENUINE WOLF REPLACEMENT PARTS.
Wolf Part
No Part Description Wolf Part
No
LL-378 ATX 24V Socket LL-1218 arechal 110V Socket
LL-1092 ATX 110V Socket LL-1054 arechal 230V Socket
LL-1087 ATX 230V Socket LL-1276 2A gG Fuse
LL-1050 CEAG 24V Socket LL-1007 4A gG Fuse
LL-387 CEAG 110V Socket LL-1016 6A gG Fuse
LL-1048 CEAG 230V Socket LL-1024 8A gG Fuse
LL-1352 STAHL 24V Socket LL-1110 10A gG Fuse
LL-1350 STAHL 110V Socket LL-1067 12A Gg Fuse
LL-1351 STAHL 230V Socket LL-379 16A Gg Fuse
LL-1052 arechal 24V Socket LL-1252 Label Cover

This manual suits for next models

1

Other Wolf Lighting Equipment manuals

Wolf LinkEx LL-500 Manual

Wolf

Wolf LinkEx LL-500 Manual

Wolf HL-95 Manual

Wolf

Wolf HL-95 Manual

Wolf ATEX TURBOLITE A-TL44C Instruction Manual

Wolf

Wolf ATEX TURBOLITE A-TL44C Instruction Manual

Wolf ATEX TURBOLITE Series Troubleshooting guide

Wolf

Wolf ATEX TURBOLITE Series Troubleshooting guide

Wolf LINKEX WF-300 XL Manual

Wolf

Wolf LINKEX WF-300 XL Manual

Wolf WL-240BF User manual

Wolf

Wolf WL-240BF User manual

Wolf LinkEx LL-500 Manual

Wolf

Wolf LinkEx LL-500 Manual

Popular Lighting Equipment manuals by other brands

Emos ZR2212 quick start guide

Emos

Emos ZR2212 quick start guide

Phantom 60 Series user manual

Phantom

Phantom 60 Series user manual

Aervoe 1197 operating instructions

Aervoe

Aervoe 1197 operating instructions

Stoane Lighting 50mm ADL CP.X Installation and maintenance instructions

Stoane Lighting

Stoane Lighting 50mm ADL CP.X Installation and maintenance instructions

olympia electronics GR-415/4P quick guide

olympia electronics

olympia electronics GR-415/4P quick guide

Situ Lighting LightBob manual

Situ Lighting

Situ Lighting LightBob manual

Platinum PT-CFLS8621 quick start guide

Platinum

Platinum PT-CFLS8621 quick start guide

Chauvet Colorado 1-Quad Tour user manual

Chauvet

Chauvet Colorado 1-Quad Tour user manual

PXF Lighting Bari II DL 195 installation manual

PXF Lighting

PXF Lighting Bari II DL 195 installation manual

Atex GL10 installation manual

Atex

Atex GL10 installation manual

Facom 779.EYE instruction manual

Facom

Facom 779.EYE instruction manual

Merlin myQ 827AU quick start guide

Merlin

Merlin myQ 827AU quick start guide

Flash EVENT Series user manual

Flash

Flash EVENT Series user manual

Blizzard Lighting REANIMATOR quick start guide

Blizzard Lighting

Blizzard Lighting REANIMATOR quick start guide

Lightolier ProSpec 28B10E specification

Lightolier

Lightolier ProSpec 28B10E specification

HEPER GOLEDO LT2037.760-US Installation & maintenance instructions

HEPER

HEPER GOLEDO LT2037.760-US Installation & maintenance instructions

Sygonix 1290407 operating instructions

Sygonix

Sygonix 1290407 operating instructions

Hayward Pro-Grid DE2420EURO user guide

Hayward

Hayward Pro-Grid DE2420EURO user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.