6 DeviceNet Option Drive Parameters
YASKAWA ELECTRIC SIEP C730600 28B V1000 Option SI-N3/V Technical Manual 19
F6-55
(3C6)
<6>
Baud rate from Network
(Read only)
DeviceNet actual communication speed
0: 125 k bit/s
1: 250 k bit/s
2: 500 k bit/s
Note: Used in the DeviceNet Object
Default: 0
Range: 0 to 2
F6-56
(3D7) Speed Scaling
Sets the scaling factor for the Speed Monitor in the DeviceNet
Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-57
(3D8) Current Scaling
Sets the scaling factor for the Output Current Monitor in the
DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-58
(3D9) Torque Scaling
Sets the scaling factor for the Torque Monitor in the DeviceNet
Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-59
(3DA) Power Scaling
Sets the scaling factor for the Power Monitor in the DeviceNet
Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-60
(3DB) Voltage Scaling
Sets the scaling factor for the Voltage Monitor in the DeviceNet
Object Class 2A
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-61
(3DC) Time Scaling
Sets the scaling factor for the Time Monitor in the DeviceNet
Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-62
(3DD) Heart Beat Sets the heartbeat interval
Note: Used in the Identity Object
Default: 0
Min: 0
Max: 10
F6-63
(3DE)
<6>
MAC ID from Network
(Read only)
Actual MAC address
Note: Used in the DeviceNet Object
Default: 0
Min: 0
Max: 63
F6-64
(3DF)
<9>
Dynamic Output Assembly 109
Programmable Output 1 (DOA109 1)
The data in configurable output 1 is written to the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-65
(3E0)
<9>
Dynamic Output Assembly 109
Programmable Output 2 (DOA109 2)
The data in configurable output 2 is written to the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-66
(3E1)
<9>
Dynamic Output Assembly 109
Programmable Output 3 (DOA109 3)
The data in configurable output 3 is written to the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-67
(3E2)
<9>
Dynamic Output Assembly 109
Programmable Output 4 (DOA109 4)
The data in configurable output 4 is written to the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-68
(3E3)
<9>
Dynamic Input Assembly 159
Programmable Input 1 (DIA159 1)
The data in configurable input 1 is read from the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-69
(3E4)
<9>
Dynamic Input Assembly 159
Programmable Input 2 (DIA159 2)
The data in configurable input 2 is read from the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-70
(3E5)
<9>
Dynamic Input Assembly 159
Programmable Input 3 (DIA159 3)
The data in configurable input 3 is read from the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
F6-71
(3E6)
<9>
Dynamic Input Assembly 159
Programmable Input 4 (DIA159 4)
The data in configurable input 4 is read from the MEMOBUS/
Modbus address defined by this parameter.
Default: 0x0000
Min: 0x0000
Max: 0xFFFF
No.
(Addr.
Hex)
Name Description Values