OPTIONAL DUAL-POINT SUPPLIES WITH SEPARATE SYSTEM CIRCUIT BREAKERS
(Each Power Supply Individually Protected with Factory-Mounted Circuit Breakers)
NOTES for Electrical Data:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system #1
MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps (Add these values to
system #3 for YCAS 310 - 380 and YDAS models also).
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit,
per N.E.C. 440-12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). Minimum
fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan FLA).
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2. Minimum
circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per U.L.
1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), (3) or (4) preceding
the wire range indicates the number of termination points available per phase of the wire range specified. The (1-2), (1-3), or (1-4) preceding the
wire range indicates that a single multi-termination lug is available per phase that can accept two (1-2) to four (1-4) wires of the wire range
specified. (1) #1-600MCM or (2) #1-250MCM indicates that a single lug is supplied and it will accept a single wire up to 600MCM or 2 wires up
to 250MCM. Actual wire size and number of wires per phase must be determined based on ampacity and job requirements using N.E.C. wire
sizing information. The above recommendations are based on the National Electrical Code and using copper connectors only. Field wiring must
also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a Disconnecting Means as defined in N.E.C. 100.B, and is intended for isolating the unit from the available power
supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
SYSTEM 3 & 4 FIELD-SUPPLIED WIRING
MODEL VOLTS MCA1MIN NF D.E. FU C.B.
DISC SW2MIN.3MAX.4MIN.5MAX.6WIRE RANGE7 (LUGS)
200 986 1200 1200 1200 1200 1200 (3) 3/0-500
230 883 1000 1000 1200 1000 1200 (3) 3/0-500
YDAS410 380 538 600 600 700 600 700 (3) 3/0-500
460 432 600 500 600 500 600 (1) #1-600 or (2) #1-250
575 353 400 400 450 400 450 (1) #1-600 or (2) #1-250
380 645 800 800 800 800 800 (3) 3/0-500
YDAS440 460 518 600 600 700 600 700 (3) 3/0-500
575 420 600 500 600 500 600 (1) #1-600 or (2) #1-250
380 708 800 800 1000 800 1000 (3) 3/0-500
YDAS470 460 569 600 700 800 700 800 (3) 3/0-500
575 459 600 600 600 600 600 (1) #1-600 or (2) #1-250
380 748 800 1000 1000 1000 1000 (3) 3/0-500
YDAS490 460 601 800 700 800 700 800 (3) 3/0-500
575 485 600 600 600 600 600 (1) #1-600 or (2) #1-250
SYSTEM 1 & 2 FIELD-SUPPLIED WIRING
MODEL VOLTS MCA1MIN NF D.E. FU C.B.
DISC SW2MIN.3MAX.4MIN.5MAX.6WIRE RANGE7(LUGS)
380 645 800 800 800 800 800 (3) 3/0-500
YDAS410 460 518 600 600 700 600 700 (3) 3/0-500
575 420 600 500 600 500 600 (1) #1-600 or (2) #1-250
380 645 800 800 800 800 800 (3) 3/0-500
YDAS440 460 518 600 600 700 600 700 (3) 3/0-500
575 420 600 500 600 500 600 (1) #1-600 or (2) #1-250
380 708 800 800 1000 800 1000 (3) 3/0-500
YDAS470 460 569 600 700 800 700 800 (3) 3/0-500
575 459 600 600 600 600 600 (1) #1-600 or (2) #1-250
380 748 800 1000 1000 1000 1000 (3) 3/0-500
YDAS490 460 601 800 700 800 700 800 (3) 3/0-500
575 485 600 600 600 600 600 (1) #1-600 or (2) #1-250
LEGEND
ACR-LINE ACROSS THE LINE START
CB CIRCUIT BREAKER
DE FU DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT MOUNT CB FACTORY-MOUNTED CIRCUIT BREAKER
FACT MOUNT FUSE FACTORY-MOUNTED FUSES
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON-FUSED
RLA RUNNING LOAD AMPS
S.P. WIRE SINGLE-POINT WIRING
UNIT MTD SERV SW UNIT-MOUNTED SERVICE (NON-FUSED
DISCONNECT SWITCH)
WYE-DELTA WYE-DELTA START
XLRA ACROSS-THE-LINE INRUSH LOCKED
ROTOR AMPS
YLRA WYE-DELTA INRUSH LOCKED
ROTOR AMPS