Yudian AI-218 User manual

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
ARTIFICIAL INTELLIGENCE
TEMPERATURE CONTROLLER
AI-218
Operation Manual

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
I. Model Order Code
The type of AI-218 is made up of 4 parts,for example,
AI-218
A1
G
L2
Part 1 (Series)
Part 2 (Size)
Part 3 (Oupt)
Part 4 (AUX)
1. (Part 1) Model Series
AI-218, standard temperature controller , 0.3%FS±1℃accuracy.
Multiple thermocouples and RTDs are selectable
Maximum support two alarms contact output
Universal supply power 100~240VAC, 50Hz/60Hz
2. (Part 2) Front panel dimension
Panel Size
Front Panel
width×height
Cut Out
width×height
Depth Behind Mounting Surface
A1
96×96mm
92×92mm
70mm
B1
160×80mm
152×76mm
70mm
D1
72×72mm
68×68mm
78.5mm
E1
48×96mm vertical
45×92mm
70mm
F1
96×48mm horizontal
92×45mm
70mm
D1
48×48mm
45×45mm
78.5mm
A
96×96mm
92×92mm
100mm
B
160×80mm
152×76mm
100mm
D
72×72mm
68×68mm
95mm
D2
48×48mm
45×45mm
95mm
E
48×96mm
45×92mm
100mm
F
96×48mm
92×45mm
100mm

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
3. (Part 3 and 4) indicate the module installed in OUTP and AUX sockets.
Allowed modules in each socket are as below:
Allowed Type
Module Socket
N
L
L0/L1
L5
G
3. OUTP (main output)
√
√
4. AUX (Auxiliary output)
√
√
√
N (or none) no module installed
LRelay contact output module (Capacity: 5A/250VAC, normal open)
L0/L1 Relay contact output module (Capacity: 2A/250VAC, normal open/normal close, spark
absorption at normal open, supportAU1 alarm output)
L5 Dual relay output module Output module (Capacity: 2A/250VAC, normal open, supportAU1 and
AU2 alarm output)
GSSR voltage output module (30mA/5VDC)
* D1-sized controller is fixed to relay output (L) or SSR output (G) and no module option provided.
II. TECHNICAL SPECIFICATION
1. Input type : K, S, R, E, J, N (thermocouples); Pt100 (resistance temperature detector)
2. Instrument Input range : K (0~1300℃), S (0~1700℃) , R (0~1600℃), E (0~1000℃), J (0~1200℃),
N (0~1300℃), Pt100 (-200 ~ +800)℃
3. Measurement accuracy : 0.3%FS±1℃or 0.3%FS±0.1℃
4. Control mode:
On-off control mode, or
PID control with auto-tuning.
5. Type of Alarm: High limit alarm, Lower limit alarm, Deviation High Alarm and Deviation Low Alarm
6. Power supply voltage rating: 100-240VAC, -15%, +10% / 50-60Hz.
7. Power consumption: ≤3W
8. Ambient temperature: -10~+60℃, Humidity: 0~90%RH

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
III. FRONT PANEL AND OPERATION
①Process Value(PV), or parameter code
②Set Value(SV), alarming code, or value of a parameter
③Setup key, accessing parameter table, and confirming change.
④Data shift key, also for activating auto turning
⑤Data decrease key
⑥Data increase key
⑦Status display LED,
OP1 –Output
AU1 –Alarm 1
AU2 –Alarm 2
RUN –Controlling process running
Default display status:
When power is on, the process value (PV) and the set value (SV) are shown. lf the input signal is out of the measurable range (for example,
the thermocouple or RTD circuit is break or input specification is not correctly set), the upper display will blink “orA”and high limit or low
limit of specified input. The instrument will automatically stop the output.
IV. OPERATION DESCRIPTION
●Set Value Setting:
During default display status, if the parameter lock “Loc” isn't locked, user can set setpoint (SV) by pressing keys. Press
key to decrease the value, key to increase the value, and key to move to the dot to the desiired digit (acting as a pointer). Keep
pressing or will speed up value change. The range of setpoint is limited by parameter SPH with default range 0 to 400.
●Parameter Setting:
During default display status, press and hold for 2 seconds will access Field Parameter Table (See V. PARAMETER AND
SETTING). Press to proceed to the next parameter. If parameter table have not been locked, press will change the
parameter. Press and hold for 2 second returns to the preceding parameter. Press (don't release) and then press
simultaneously jumps out from parameter setting to the default status. The instrument will also jumps out auomatically from the
parameter table if no key is pressed in 30 seconds. Setting Loc=808 and then press will access System Parameter Table (See V.
PARAMETER AND SETTING)
●AI artificial intelligence control and auto tuning
When AI artificial intelligence control algorithm is selected (CrL=AI), the P,I, and D parameters can be calculated automatically by
auto-tuning. In default display status, press and hold for 2 seconds, “At” auto-tuning parameter will show. Press to change the
value of “At” from “oFF” to “on”, then press to activate the auto-tuning. During auto-tuning, the instrument runs on-off control for two
cycles. The instrument will calculate the optimal P, I and D control parameter values and returns to default display. If user want to
interrupt the auto tuning process, press and hold the for 2 seconds. Change “At” from “on” to “oFF” and press to confirm. The
auto-tuning process will be cancelled and new P, I and D values will be calculated.
Note 1: The P, I and D parameters obtained from auto-tuning are dependent to the set value. It is recommended to set a set value to an
often-used value or mean value to perform auto-tuning. For the ovens with good heat preservation, the set value can be set at
the highest applicable temperature. Depending on hardware setup, the auto-tuning may take from a few seconds to a few hours.
Note 2: Parameter Ctl (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning. Generally, the smaller the
value of Ctl, the higher the precision of auto tuning. But Ctl parameter value should be large enough to prevent the instrument
from error action around set value due to the oscillation of input. Ctl is recommended to be 2.0.
Note 3: Self-learning function enables the instrument to control better and better after time.
AI
MAN
RUN
COM
MIO
AL1
AL2
OP1
OP2
A/M
RUN/HOLD
A
I
AU2
STOP
AU1
①
②
③
④
⑤
⑥
⑥
⑦
⑥
PV
SV
信
号
输
入,
I4模
块
可
支
持
0-2
0m
A及
4-2
0m
A输
入,
并
可
直
接
输
入2
线
制
变
送
器
(9
接
正,
7接
负
)。
注:
依
据
安
装

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
V. PARAMETER AND SETTING
Parameter
Title
Description
Range
Default
Field Parameter Table (Press and hold for 2 seconds to access)
HIAL
High limit alarm
Alarm on when PV (Process Value) >HIA;
alarm off when PV<HIA-AHY
-999 ~
+3000
3000
LoAL
Lower limit alarm
Alarm on when PV (Process Value) < LoA;
alarm off when PV > LoA+AHY
-999
HdAL
Deviation high
alarm
Alarm on when PV-SV>HdA;
alarm off when PV-SV<HdA-AHY
3000
LdAL
Deviation low
alarm
Alarm on when PV-SV<LdA;
alarm off when PV-SV>LdA+AHY
-999
Loc
Parameter lock
Loc=0: Allowed to change field parameters, SV and activate AT
function.
Loc=1: Allowed to change field parameters, SV but no AT activation.
Loc=2: Allowed to change field parameters but not allowed to set SV
nor AT.
Loc=4~255: NOT allowed to change any parameters nor SV.
Loc=808, Set to 808 and press to unlock the System Parameter Table.
0~255
0
System Parameter Table (Loc=808 to unlock)
AHYS
Alarm Hysteresis
Avoid frequent alarm on-off action because of the fluctuation of PV
AHY=2 by default.
0~200
2
AoP
Alarm output
assignment
Example:
AOP = 040 3
LdAL HdAL LoAL HIAL
It shows that HIAL is sent to AU1, HdAL to AU2, LoAL and LdAL has no
output.
Alarm
Output to
LdAL
(x 1000)
HdAL
(x100)
LoAL
(x10)
HIAL
(x1)
None
0
0
0
0
AL1
1
1
1
1
AL2
2
2
2
2
AU1
3
3
3
3
AU2
4
4
4
4
0~4444
Depend
on
module
CtrL
Control mode
onF : ON-OFF control. When PV>SV, output stops and heating
stops. When PV<SV-AHY, output resumes.
AI : AI-PID control. The output time proportion can adjusted by
parameter Ctl
onoF/API
d
APId
Act
Acting method
rE: Reverse acting. Increase in measured variable causes a decrease
in the output, such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in
the output, such as refrigerating control.
rEb: Reverse acting with low limit alarm and deviation low alarm
blocking at the beginning of power on.
drb: Direct acting with high limit alarm and deviation high alarm blocking
rE , dr ,
rEb, drb
rE

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
at the beginning of power on.
P
Proportion band
Proportion band in PID with unit ℃or ℉but not the percentage of the
input scale.
1~999
30
I
Time of integral
Time of integral in PID. No integral effect when I=0
0~9999
sec
100
d
Time of derivative
Time of derivative in PID with unit 0.1 second. No derivative effect when
d=0
0~9999
sec
50.0
Ctl
Control period
Smaller value will result in higher control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 seconds, because small value will
cause the frequent On-Off of mechanical switch and shorten its service
life. Ctl is recommended to be 1/4 –1/10 of derivative time. When
control under on-off control, Ctl is used as delay time to restart to
protect the compressor.
0.5-300
sec
CHYS
Control
hysteresis
To avoid frequent relay on-off action, in ON-OFF control mode.
PV > SV, Output turns OFF (Relay opens)
PV < SV-CHY, Output turns ON (Relay closes)
0~200
InP
Input
specification
Thermocouples & RTD
0
K
1
S
2
R
4
E
5
J
7
N
21
Pt100
0~21
0
dPt
Resolution
0 or 0.0 selectable. 0.0 is valid for 0~99.9 ℃/ ℉display
0/0.0
0.0
Scb
Input shift
Scb is used to make input shift to compensate the error produced by
sensor or input signal.
PV after compensation= PV before compensation + Scb.
-200~
+400
0
FILt
PV input filter
Higher degree of FIL gives more powerful noise filtering.
Large FIL value stabilized the input signal but the system response
speed will be slow. Generally speaking, 1 to 3 will be used.
If great interference exists, FIL can be gradually increase to limit the
momentary fluctuation among 2 to 5 unit.
When the instrument is being metrological verified, FIL should be set to
0 or 1 to minimize the response time.
0~40
1
Fru
Selection of
power frequency
and temperature
scale
50C: 50Hz, ℃
50F: 50Hz, ℉
60C: 60Hz, ℃
60F: 60Hz, ℉
50C
SPL
Lower limit of SV
Minimum value that SV allowed to be.
When SPH=0, the SV range will 0~400℃
-999 ~
+3000
0
SPH
Upper limit of SV
Maximum value that SV allowed to be.
When SPH=400, the SV range will 0~400℃
400

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
VI. INSTRUMENT INSTALLATION AND WIRING DIAGRAM
Panel dimension A1, B1, E1 or F1 Panel dimension A, B, E or F
The diagram illustrated is for upright panel dimension A/A1/E/E1.
For panel dimension B/B1/F/F1, please rotate the diagram clockwise by 90 degree.
Panel dimension D (72 x 72mm)Panel dimension D1/D2 (48 x 48mm)
Remarks
1. Thermocouples compensate wires should be directly screwed to the back of the instrument. No extension by normal
conducting wire should be used. Please pay attention to the polarity of the compensate wires.
2. The solid-state relay (SSR) externally connected should provide 2300 V isolation between input/output-to-power line.
(CE requirement)
Main Output
Alarm Output
Main Output
Alarm Output
Table of contents
Other Yudian Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

West Control Solutions
West Control Solutions Pro-EC44 user guide

Elko
Elko iNels RFTC-10/G manual

Siemens
Siemens RDF30U Technical instructions

Automationdirect.com
Automationdirect.com Solo user manual

Bticino
Bticino HS 4695 installation manual

IFM Electronic
IFM Electronic efector 600 TN21 Series operating instructions