DIMinBOX 2CH
DIMinBOX 2CH. Two channel universal DIMMING actuator for lighting control
ZDI-DB2C Technical Documentation
© Zennio Avance y Tecnología S.L. Draft Edition Further information www.zennio.com Page 1/ 4
Technical Documentation
FEATURES
Size: 80 x 90 x 60mm (4.5 DIN rail units).
2 Channel 310W (230VAC) or 160W (110VAC) for R L C loads
or 125W (230VAC) or 65W (110VAC) for dimmable CFL and
LED lamps @ 25ºC (50-60Hz).
Automatic detection of R L C load type.
Dimming pattern manual selection for CFL and LED lamps.
Optional dimming manual control.
2 analog/digital inputs.
KNX BCU integrated.
Independent control assembly, to be mounted in electrical
panels with DIN rails.
Total data saving when power failure occurs.
CE directive compliant.
Electric operation control device
KNX supply
Typical bus connector TP1, 0,50 mm² section
R L C Loads: 310W (230VAC) or 160W (110VAC) @ 25ºC; CFL and
LED lamps 125W (230VAC) or 65W (110VAC) @ 25ºC (depending
on manufacturer and model)
5W R L C loads; 5W (230VAC) or 3W (110VAC) CFL and LED lamps
Electrical solicitations period
30 to 85% RH (no condensation)
Storage humidity (relative)
30 to 85% RH (no condensation)
Assembly
Independent control assembly to be mounted inside distribution
boxes or electrical panels
Operation indicator
Programming LED (red) ON when pushing the programming button.
Test LED (green) ON when device is in Test mode
PC+ABS FR V0, halogen free
1. Terminal block (neutral and
phase) 2. KNX bus
connection 3. Programming/Test LED 4. Programming/Test push
button
5. Analog/Digital inputs 6. Output LED
indicator 7. Manual Control push
button 8. Output channels
Programming/test button: push the button to set the PROGRAMMING MODE. If this button is held while plugging the device into
the KNX bus, it goes into secure mode. If this button is held more than 3 seconds, the device goes into TEST MODE.
Programming LED: lighting red = programming mode; blinking red = safe mode; lighting green = test mode.
Output LED indicators: lighting during a press button with manual control enabled. Moreover, it indicates the error present in the
outputs. For further information, consult the “error notifications” section.