SAFETY INSTRUCTIONS ANDADDITIONAL NOTES
•Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
•Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire KNX system. The
facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other accessories, in case of being
installed.
•Once the device is installed (in the panel or box), it must not be accessible from outside.
•Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material while in use.
•The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
https://www.zennio.com/en/legal/weee-regulation.
OUTPUTS SPECIFICATIONS AND CONNECTIONS
Potential-free outputs through bistable relays
with tungsten pre-contact / Micro-disconnection
AC 16(6)A @ 250VAC (4000VA)
DC 7A @ 30VDC (210W)
Connections in adjacent outputs
Possibility of connecting different phases. It is
not allowed to connect power supplies of
different order, SELV with NO SELV, in the
same block
Maximum current per block
1.5-4mm² (IEC) / 26-10AWG (UL)
Mechanical lifetime (min. cycles)
Electrical lifetime (min. cycles)1
100000 @ 8A / 25000 @ 16A (VAC)
¹ Lifetime values could change depending on the load type.
0-10V OUPUT SPECIFICATIONS AND CONNECTIONS
0.5-2.5mm² (IEC) / 26-12AWG (UL)
INPUTS SPECIFICATIONS AND CONNECTIONS
Dry voltage contacts between input and
common
0.5-2.5mm² (IEC) / 26-12AWG (UL)
1.5m (extensible up to 30m)
⚠In order to ensure the expected status of the relays,
please check thatthe device is connectedto the KNX bus
before energizing the power circuit.
Figure 2: (From up to down and from left to right)
Terminal block 1 and 0-10V outputs wiring examples
for two valves, two fans, one valve and one fan.
Attaching MAXinBOX FC 0-10V FAN to DIN rail:
Removing MAXinBOX FC 0-10V FAN from DIN rail:
* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in Type B position.
Any combination of the following accessories is allowed in the inputs:
Zennio temperature
probe.
can be plugged into the
same device input (parallel
Switch/Sensor/
Push button
Commons of different devices
must not be connected together.