Zennio MAXinBOX 24 ZIO-MB24 User manual

➢
MAXinBOX 24
Multifunction Actuator with 24 Outputs
ZIO-MB24
USER MANUAL
Application programme version: [1.1]
User manual edition: [1.1]_a
www.zennio.com

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
2
CONTENTS
Contents ........................................................................................................................................ 2
Document Updates ....................................................................................................................... 3
1 Introduction .......................................................................................................................... 4
1.1 MAXinBOX 24 ................................................................................................................... 4
1.2 Installation........................................................................................................................ 5
1.3 Start-Up and Power Loss.................................................................................................. 6
2 Configuration......................................................................................................................... 7
2.1 General............................................................................................................................. 7
2.2 Outputs............................................................................................................................. 9
2.3 Manual Control .............................................................................................................. 10
2.4 Logic Functions............................................................................................................... 14
2.5 Scene Temporisation...................................................................................................... 15
ANNEX I. Communication Objects............................................................................................... 17

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
3
DOCUMENT UPDATES
Version
Changes
Page(s)
[1.1_a]
Changes in the application program:
•Parameters reorganization.
-

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
4
1INTRODUCTION
1.1 MAXinBOX 24
MAXinBOX 24 from Zennio is a versatile KNX actuator featuring a wide variety of
functions:
24 relay outputs, configurable as:
➢Up to 12 independent shutter channels (with or without slats),
➢Up to 24 individual ON/OFF outputs,
➢Up to 6two-pipe fan coil modules where both the fan speed control and
the valve control are performed through relays,
➢A combination of the above.
30 customisable, multi-operation logic functions.
Scene-triggered action control, with an optional delay in the execution.
Manual operation / supervision of the 24 relay outputs through the on-
board pushbuttons and LEDs.
Relay Switches Counter.
Heartbeat or periodical “still-alive” notification.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
5
1.2 INSTALLATION
MAXinBOX 24 connects to the KNX bus through the on-board KNX connector.
Once the device is provided with power from the KNX bus, both the individual address
and the associated application programme may be downloaded.
This device does not need any additional external power since it is entirely powered
through the KNX bus.
Figure 1. Element Diagram for MAXinBOX 24.
The main elements of the device are described next.
Prog./Test Pushbutton (5): a short press on this button sets the device into
the programming mode, making the associated LED (6) light in red.
Note: if this button is held while plugging the device into the KNX bus, the
device will enter into safe mode. In such case, the LED will blink in red every
0.5 seconds.
Outputs (1 and 2): output ports for the insertion of the stripped cables of the
systems being controlled by the actuator (see section 2.2). Please secure the
connection by means of the on-board screws.
To get detailed information about the technical features of this device, as well as on the
installation and security procedures, please refer to the corresponding Datasheet,
bundled with the original device packaging and also available at www.zennio.com.
1. Outputs.
2. Output status LED.
3. Manual Control Pushbutton
4. Fixing clamp.
5. Prog./Test LED Pushbutton.
6. Prog./Test LED Indicator.
7. KNX Bus Connector.
1
2
3
4
5
6
7

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
6
1.3 START-UP AND POWER LOSS
During the start-up of the device, the Prog./Test LED will blink in blue colour for a few
seconds before the device is ready. External orders will not be executed during this
time, but afterwards.
Depending on the configuration, some specific actions will also be performed during
the start-up. For example, the integrator can set whether the output channels should
switch to a particular state and whether the device should send certain objects to the
bus after the power recovery. Please consult the next sections of this document for
further details.
On the other hand, when a bus power failure takes place, MAXinBOX 24 will interrupt
any pending actions, and will save its state so it can be recovered once the power
supply is restored.
For safety reasons, all shutter channels will be stopped (i.e., the relays will open) if a
power loss takes place, while the individual outputs and fan coil contacts will switch to
the specific state configured in ETS (if any).

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
7
2CONFIGURATION
2.1 GENERAL
After importing the corresponding database in ETS and adding the device into the
topology of the desired project, the configuration process begins by entering the
Parameters tab of the device.
ETS PARAMETERISATION
The first parameterisable screen available by default is General. From this screen it is
possible to activate/deactivate all the required functionality.
Figure 2. General screen.
The Manual Control function is enabled by default. Once activated, Inputs, Outputs,
Logic Functions and Manual Control bring additional tabs to the menu on the left. On
the other hand, the user can also activate the functionalities of Sending of Indication
Objects on Bus Voltage Recovery, Heartbeat and Show Relay Switches Counter
Objects. These functions and their parameters will be explained in later sections of this
document.
Sending of Indication Objects (0 and 1) on Bus Voltage Recovery: this
parameter lets the integrator activate two new communication objects (“Reset
0” and “Reset 1”), which will be sent to the KNX bus with values “0” and “1”

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
8
respectively whenever the device begins operation (for example, after a bus
power failure). It is possible to parameterise a certain delay to this sending (0
to 255 seconds).
Figure 3. Sending of Indication Objects on Bus Voltage Recovery.
Heartbeat (Periodical Alive Notification): incorporates a one-bit object to
the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically
with a value of “1” to notify that the device is still working (still alive)..
Figure 4. Heartbeat (Periodical Alive Notification).
Note: The first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following sendings match
the period set.
Show Relay Switches Counter Objects: enables two communication
objects to keep track of the number of switches performed by each of the
relays ("[Relay X] Number of Switches") and the maximum number of
switches carried out in a minute ("[Relay X] Maximum Switches per
Minute").

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
9
2.2 OUTPUTS
The MAXinBOX 24 actuator incorporates 24 relay outputs, which can be configured
as:
Individual binary outputs, which allows an independent control of loads.
Shutter channels, which allow controlling the motion of shutters or blinds.
Fan Coil modules, which allow the control of the fan and the valve of two-
pipe fan coil units.
In particular:
MAXinBOX 24: the 24 outputs are grouped into two-output channels, which
themselves are grouped into two-channel (or four-output) blocks. Therefore, it
is possible to configure up to 6 fan coil modules, or up to 12 shutter channels,
or up to 24 individual outputs.
For detailed information about the functionality and the configuration of the related
parameters, please refer to the following specific manuals, all of them available within
the MAXinBOX 24 product section at the Zennio website (www.zennio.com):
Individual outputs.
Shutter channels.
‘Relays’ Fan Coil. Note that MAXinBOX 24 is only compatible with two-pipe
fan coils. Therefore, any references to four-pipe fan coils do not apply to this
device.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
10
2.3 MANUAL CONTROL
MAXinBOX 24 allows manually switching the state of its output relays through the
respective pushbuttons on the top of the device. A specific pushbutton is therefore
available per output.
Manual operation can be done in two different ways, named as Test On mode (for
testing purposes during the configuration of the device) and Test Off mode (for a
normal use, anytime). Whether both, only one, or none of these modes should be
accessible needs to be parameterised in ETS. Moreover, it is possible to enable a
specific binary object for locking and unlocking the manual control in runtime.
Notes:
The Test Off mode will be active (unless it has been disabled by parameter)
after a download or a reset with no need of a specific activation –the
pushbuttons will respond to user presses from the start.
On the contrary, switching to the Test On mode (unless disabled by
parameter) needs to be done by long-pressing the Prog/Test button (for at
least three seconds), until the LED is no longer red and turns yellow. From
that moment, once the button is released, the LED light will remain green to
confirm that the device has switched from the Test Off mode to the Test On
mode. After that, an additional press will turn the LED yellow and then off,
once the button is released. This way, the device leaves the Test On mode.
Note that it will also leave this mode if a bus power failure takes place.
Test Off Mode
Under the Test Off Mode, the outputs can be controlled through both their
communication objects and the actual pushbuttons located on the top of the device.
When one of these buttons is pressed, the output will behave as if an order had been
received through the corresponding communication object, depending on whether the
output is configured as either an individual output, as a shutter channel or as a fan coil.
Individual output: asimple press (short or long) will make the output switch
its on-off state, which will be reported to the KNX bus through the

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
11
corresponding status object, if enabled.
Shutter Channel: when the button is pressed, the device will act over the
output according to the length of the button press and to the current state.
➢A long press makes the shutter start moving (upwards or downwards,
depending on the button being pressed). The LED will light in green until
the end of the motion. If the button gets pressed being the shutter already
at the top or bottom positions, nothing will happen (the LED will not light).
➢A short press will make the shutter drive stop (if in motion), as it normally
does when a step/stop order is received from the KNX bus. In case of not
being the shutter in motion, pressing the button does not cause any action,
unless slats/lamellas have been parameterized –in such case, a step
movement (up/down, depending on the button pressed) will take place.
The status objects will be sent to the bus when corresponding.
Fan Coil module: the behaviour will depend on whether a fan-labelled or
a valve-labelled button is pressed:
➢Fan: a short or long press will switch the relays to set the selected speed,
unless it matches the current speed –in such case all the relays will be
opened (speed 0). The associated LEDs will indicate the state of the fan
speed control relays.
Note: the behaviour of the relays will depend on the parameterisation, i.e.,
on the number of fan speeds, on the delay between switches and on
whether the control type is accumulation or switching.
➢Valve: a short or long press will switch the current status of the relay and
therefore of the valve. The LED will show the state of the relay anytime (on
= relay closed; off = relay open).
Disabled output: outputs disabled by parameter will not react to button
presses under the Test Off mode.
Regarding the lock, timer, alarm and scene functions, the device will behave under the
Test Off mode as usual. Button presses during this mode are entirely analogous to the
reception of the corresponding orders from the KNX bus.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
12
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, with independence of the channel or the output they are addressed to.
Depending on whether the output has been parameterized as an individual output or as
part of a shutter channel, the reactions to the button presses will differ.
Individual output: short or long pressing the button will commute the on-off
state of the relay.
Shutter channel: pressing the button will make the shutter drive move
upward or downward (depending on the button) until the button is released
again, thus ignoring the position of the shutter and the parameterized times.
Note: after leaving the Test On mode, the status objects will recover the
values they had prior to entering Test On. As the device is never aware of the
actual position of the shutter (as the shutter drive does not provide any
feedback), these values may not show the real position. This can be solved
by performing a complete move-up or move-down order, or by calibrating the
shutter position in the Test On mode until it matches the status objects.
Fan Coil module: the behaviour is similar to that of the Test Off mode,
although in this case the three fan speeds are supposed available.
Disabled output: short and long presses will switch the state of the
corresponding relay. In case this consists in closing the relay, then the
remaining relays of its block will open, for safety reasons.
The lock, timer, alarm and scene functions, as well as any other orders received from
the bus, will not affect the outputs while the device is under the Test On mode. Status
objects will not be sent to the bus, either.
Important: the device is delivered from factory with all the outputs disabled, and with
both manual modes (Test Off and Test On) enabled.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
13
ETS PARAMETERISATION
The Manual Control is configured from the Configuration tab itself under Manual
Control.
The only two parameters are:
Figure 5. Manual Control
Manual Control [Disabled / Only Test Off Mode / Only Test On Mode / Test
Off Mode + Test On Mode]
1
. Depending on the selection, the device will
permit using the manual control under the Test Off, the Test On, or both
modes. Note that, as stated before, using the Test Off mode does not require
any special action, while switching to the Test On mode does require long-
pressing the Prog/Test button.
Manual Control Lock [enabled/disabled]: unless the above parameter has
been “Disabled”, the Lock Manual Control parameter provides an optional
procedure for locking the manual control in runtime. When this checkbox is
enabled, object “Manual Control Lock” turns visible, as well as two more
parameters:
➢Value [0 = Lock; 1 = Unlock / 0 = Unlock; 1 = Lock]: defines whether the
manual control lock/unlock should take place respectively upon the
reception (through the aforementioned object) of values “0” and “1”, or the
opposite.
➢Initialization [Unlocked / Locked / Last Value]: sets how the lock state of
the manual control should remain after the device start-up (after an ETS
download or a bus power failure). “Last Value” (default; on the very first
start-up, this will be Unlocked.
1
The default values of each parameter will be highlighted in blue in this document, as
follows: [default/rest of options].

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
14
2.4 LOGIC FUNCTIONS
This module makes it possible to perform numeric and binary operations to incoming
values received from the KNX bus, and to send the results through other
communication objects specifically enabled for this purpose.
MAXinBOX 24 can implement up to 30 different and independent functions, each of
them entirely customisable and consisting in up to 4 consecutive operations each
one.
The execution of each function can depend on a configurable condition, which will be
evaluated every time the function is triggered through specific, parameterisable
communication objects. The result after executing the operations of the function can
also be evaluated according to certain conditions and afterwards sent (or not) to the
KNX bus, which can be done every time the function is executed, periodically or only
when the result differs from the last one.
Please refer to the “Logic Functions”user manual, available within the MAXinBOX 24
product section at the Zennio homepage, www.zennio.com, for detailed information
about the functionality and the configuration of the related parameters.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
15
2.5 SCENE TEMPORISATION
The scene temporisation allows imposing delays over the scenes of the outputs.
These delays are defined in parameters, and can be applied to the execution of one or
more scenes that may have been configured.
Please bear in mind that, as multiple delayed scenes can be configured for each
individual output / shutter channel / fan coil module, in case of receiving an order to
execute one of them when a previous temporisation is still pending for that output /
channel / module, such temporisation will be interrupted and only the delay and the
action of the new scene will be executed.
ETS PARAMETERISATION
Prior to setting the scene temporisation, it is necessary to have one or more scenes
configured in some of the outputs. When entering the Configuration window under
Scene Temporization, all configured scenes will be listed, together with a few
checkboxes to select which of them need to be temporised, as shown in Figure 66.
Figure 6. Scene Temporisation
Enabling a certain scene number n brings a new tab with such name to the menu on
the left, from which it is possible to configure the temporisation of that scene for each of
the outputs where it has been configured.

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
16
Figure 7. Configuration of Scene Temporization.
Therefore, parameter “Scene m. Z Delay” [0…3600 [s] / 0…1440 [min] / 0…24 [h]]
defines the delay that will be applied to the action defined in Z for the execution of
scene m (where Z may be a specific individual output, shutter channel or fan coil
module).

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
17
ANNEX I. COMMUNICATION OBJECTS
“Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning
because of the specifications or restrictions from both the KNX standard or the application programme itself.
Number
Size
I/O
Flags
Data Type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - - W -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - - W -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5, 16, 27, 38, 49, 60,
71, 82, 93, 104, 115,
126, 137, 148, 159, 170,
181, 192, 203, 214, 225,
236, 247, 258
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Ox] Scenes
0-63 (Execute 1-64); 128-191 (Save 1-64)
6, 17, 28, 39, 50, 61,
72, 83, 94, 105, 116,
127, 138, 149, 160, 171,
182, 193, 204, 215, 226,
237, 248, 259
1 Bit
I
C - - W -
DPT_BinaryValue
0/1
[Ox] On/Off
N.O. (0=Open Relay; 1=Close Relay)
1 Bit
I
C - - W -
DPT_BinaryValue
0/1
[Ox] On/Off
N.C. (0=Close Relay; 1= Open Relay)
7, 18, 29, 40, 51, 62,
73, 84, 95, 106, 117,
128, 139, 150, 161, 172,
183, 194, 205, 216, 227,
238, 249, 260
1 Bit
O
C T R - -
DPT_BinaryValue
0/1
[Ox] On/Off (Status)
0=Output Off; 1=Output On
8, 19, 30, 41, 52, 63,
74, 85, 96, 107, 118,
129, 140, 151, 162, 173,
184, 195, 206, 217, 228,
239, 250, 261
1 Bit
I
C - - W -
DPT_Enable
0/1
[Ox] Lock
0=Unlock; 1=Lock
9, 20, 31, 42, 53, 64,
75, 86, 97, 108, 119,
130, 141, 152, 163, 174,
185, 196, 207, 218, 229,
240, 251, 262
1 Bit
I
C - - W -
DPT_Start
0/1
[Ox] Timer
0=Switch Off; 1=Switch On

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
18
10, 21, 32, 43, 54, 65,
76, 87, 98, 109, 120,
131, 142, 153, 164, 175,
186, 197, 208, 219, 230,
241, 252, 263
1 Bit
I
C - - W -
DPT_Start
0/1
[Ox] Flashing
0=Stop; 1=Start
11, 22, 33, 44, 55, 66,
77, 88, 99, 110, 121,
132, 143, 154, 165, 176,
187, 198, 209, 220, 231,
242, 253, 264
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Ox] Alarm
0=Normal; 1=Alarm
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Ox] Alarm
0=Alarm; 1=Normal
12, 23, 34, 45, 56, 67,
78, 89, 100, 111, 122,
133, 144, 155, 166, 177,
188, 199, 210, 221, 232,
243, 254, 265
1 Bit
I
C - - W -
DPT_Ack
0/1
[Ox] Unfreeze Alarm
Alarm=0 + Unfreeze=1 => End Alarm
13, 24, 35, 46, 57, 68,
79, 90, 101, 112, 123,
134, 145, 156, 167, 178,
189, 200, 211, 222, 233,
244, 255, 266
1 Bit
O
C T R - -
DPT_State
0/1
[Ox] Warning Time (Status)
0=Normal; 1=Warning
14, 25, 36, 47, 58, 69,
80, 91, 102, 113, 124,
135, 146, 157, 168, 179,
190, 201, 212, 223, 234,
245, 256, 267
4 Bytes
I/O
C T R W -
DPT_LongDeltaTimeSec
0 - 2147483647
[Ox] Operating Time (s)
Time in Seconds
15, 26, 37, 48, 59, 70,
81, 92, 103, 114, 125,
136, 147, 158, 169, 180,
191, 202, 213, 224, 235,
246, 257, 268
2 Bytes
I/O
C T R W -
DPT_TimePeriodHrs
0 - 65535
[Ox] Operating Time (h)
Time in Hours
269
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Shutter] Scenes
0-63 (Execute 1-64); 128-191 (Save 1-64)
270, 298, 326, 354, 382,
410, 438, 466, 494, 522,
550, 578
1 Bit
I
C - - W -
DPT_UpDown
0/1
[Cx] Move
0=Raise; 1=Lower
271, 299, 327, 355, 383,
411, 439, 467, 495, 523,
551, 579
1 Bit
I
C - - W -
DPT_Step
0/1
[Cx] Stop/Step
0=Stop/StepUp; 1=Stop/StepDown
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Cx] Stop
0=Stop; 1=Stop
272, 300, 328, 356, 384,
412, 440, 468, 496, 524,
552, 580
1 Bit
I
C - - W -
DPT_Enable
0/1
[Cx] Lock
0=Unlock; 1=Lock
273, 301, 329, 357, 385,
413, 441, 469,497, 525,
553, 581
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Cx] Shutter Positioning
0%=Top; 100%=Bottom

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
19
274, 302, 330, 358, 386,
414, 442, 470, 498, 526,
554, 582
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Cx] Shutter Position (Status)
0%=Top; 100%=Bottom
275, 303, 331, 359, 387,
415, 443, 471, 499, 527,
555, 583
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Cx] Slats Positioning
0%=Open; 100%=Closed
276, 304, 332, 360, 388,
416, 444, 472, 500, 528,
556, 584
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Cx] Slats Position (Status)
0%=Open; 100%=Closed
277, 305, 333, 361, 389,
417, 445, 473, 501, 529,
557, 585
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] Rising Relay (Status)
0=Open; 1=Closed
278, 306, 334, 362, 390,
418, 446, 474, 502, 530,
558, 586
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] Lowering Relay (Status)
0=Open; 1=Closed
279, 307, 335, 363, 391,
419, 447, 475, 503, 531,
559, 587
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] Movement (Status)
0=Stopped; 1=Moving
280, 308, 336, 364, 392,
420, 448, 476, 504, 532,
560, 588
1 Bit
O
C T R - -
DPT_UpDown
0/1
[Cx] Movement Direction (Status)
0=Upward; 1=Downward
281, 309, 337, 365, 393,
421, 449, 477, 505, 533,
561, 589
1 Bit
I
C - - W -
DPT_Switch
0/1
[Cx] Auto: On/Off
0=On; 1=Off
1 Bit
I
C - - W -
DPT_Switch
0/1
[Cx] Auto: On/Off
0=Off; 1=On
282, 310, 338, 366, 394,
422, 450, 478, 506, 534,
562, 590
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] Auto: On/Off (Status)
0=On; 1=Off
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] Auto: On/Off (Status)
0=Off; 1=On
283, 311, 339, 367, 395,
423, 451, 479, 507, 535,
563, 591
1 Bit
I
C - - W -
DPT_UpDown
0/1
[Cx] Auto: Move
0=Raise; 1=Lower
284, 312, 340, 368, 396,
424, 452, 480, 508, 536,
564, 592
1 Bit
I
C - - W -
DPT_Step
0/1
[Cx] Auto: Stop/Step
0=Stop/StepUp; 1=Stop/StepDown
1 Bit
I
C - - W -
DPT_Step
0/1
[Cx] Auto: Stop
0=Stop; 1=Stop
285, 313, 341, 369, 397,
425, 453, 481, 509, 537,
565, 593
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Cx] Auto: Shutter Positioning
0%=Top; 100%=Bottom
286, 314, 342, 370, 398,
426, 454, 482, 510, 538,
566, 594
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Cx] Auto: Slats Positioning
0%=Open; 100%=Closed
287, 315, 343, 371, 399,
427, 455, 483, 511, 539,
567, 595
1 Bit
I
C T - W U
DPT_Scene_AB
0/1
[Cx] Sunshine/Shadow
0=Sunshine; 1=Shadow
1 Bit
I
C T - W U
DPT_Scene_AB
0/1
[Cx] Sunshine/Shadow
0=Shadow; 1=Sunshine

MAXinBOX 24
http://www.zennio.com Technical Support: http://support.zennio.com
20
288, 316, 344, 372, 400,
428, 456, 484, 512, 540,
568, 596
1 Bit
I
C T - W U
DPT_Heat_Cool
0/1
[Cx] Cooling/Heating
0=Heating; 1=Cooling
1 Bit
I
C T - W U
DPT_Heat_Cool
0/1
[Cx] Cooling/Heating
0=Cooling; 1=Heating
289, 317, 345, 373, 401,
429, 457, 485, 513, 541,
569, 597
1 Bit
I
C T - W U
DPT_Occupancy
0/1
[Cx] Presence/No Presence
0=Presence; 1=No Presence
1 Bit
I
C T - W U
DPT_Occupancy
0/1
[Cx] Presence/No Presence
0=No Presence; 1=Presence
290, 318, 346, 374, 402,
430, 458, 486, 514, 542,
570, 598
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Cx] Alarm 1
0=No Alarm; 1=Alarm
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Cx] Alarm 1
0=Alarm; 1=No Alarm
291, 319, 347, 375, 403,
431, 459, 487, 515, 543,
571, 599
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Cx] Alarm 2
0=No Alarm; 1=Alarm
1 Bit
I
C - - W -
DPT_Alarm
0/1
[Cx] Alarm 2
0=Alarm; 1=No Alarm
292, 320, 348, 376, 404,
432, 460, 488, 516, 544,
572, 600
1 Bit
I
C - - W -
DPT_Ack
0/1
[Cx] Unfreeze Alarm
Alarm1=Alarm2=No Alarm + Unfreeze (1)
=> End Alarm
293, 321, 349, 377, 405,
433, 461, 489, 517, 545,
573, 601
1 Bit
I
C - - W -
DPT_Scene_AB
0/1
[Cx] Move (Reversed)
0=Lower; 1=Raise
294, 322, 350, 378, 406,
434, 462, 490, 518, 546,
574, 602
1 Bit
I
C - - W -
DPT_Ack
0/1
[Cx] Direct Positioning 1
0=No Action; 1=Go to Position
295, 323, 351, 379, 407,
435, 463, 491, 519, 547,
575, 603
1 Bit
I
C - - W -
DPT_Ack
0/1
[Cx] Direct Positioning 2
0=No Action; 1=Go to Position
296, 324, 352, 380, 408,
436, 464, 492, 520, 548,
576, 604
1 Bit
I
C - - W -
DPT_Ack
0/1
[Cx] Direct Positioning 1 (Save)
0=No Action; 1=Save Current Position
297, 325, 353, 381, 409,
437, 465, 493, 521, 549,
577, 605
1 Bit
I
C - - W -
DPT_Ack
0/1
[Cx] Direct Positioning 2 (Save)
0=No Action; 1=Save Current Position
607, 639, 671, 703, 735,
767
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] On/Off
0 = Off; 1 = On
608, 640, 672, 704, 736,
768
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] On/Off (Status)
0 = Off; 1 = On
609, 641, 673, 705, 737,
769
1 Bit
I
C - - W U
DPT_Heat_Cool
0/1
[FCx] Mode
0 = Cool; 1 = Heat
610, 642, 674, 706, 738,
770
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[FCx] Mode (Status)
0 = Cool; 1 = Heat
611, 643, 675, 707, 739,
771
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Fan: Manual/Automatic
0 = Automatic; 1 = Manual
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Fan: Manual/Automatic
0 = Manual; 1 = Automatic
612, 644, 676, 708, 740,
772
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Manual/Automatic (Status)
0 = Automatic; 1 = Manual
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Manual/Automatic (Status)
0 = Manual; 1 = Automatic
Table of contents
Other Zennio Controllers manuals

Zennio
Zennio LUMENTO X4 Guide

Zennio
Zennio MAXinBOX 24 Guide

Zennio
Zennio MAXinBOX FC 0-10V FAN Guide

Zennio
Zennio ZCL-MCC User manual

Zennio
Zennio HeatingBOX 230V 4X Guide

Zennio
Zennio ZoningBOX 6 Guide

Zennio
Zennio Tecla 55 X Sign User manual

Zennio
Zennio MINiBOX 45 v3 Guide

Zennio
Zennio MINiBOX 25v2 User manual

Zennio
Zennio MAXinBOX FC 0-10V FAN User manual

Zennio
Zennio MAXinBOX 16 Guide

Zennio
Zennio FANinBOX 110V 1CH Guide

Zennio
Zennio MAXinBOX User manual

Zennio
Zennio Roll-ZAS User manual

Zennio
Zennio ALLinBOX 1612 Guide

Zennio
Zennio ZoningBOX 6 User manual

Zennio
Zennio inBOX 24 v2 User manual

Zennio
Zennio ALLinBOX 1612 v2 User manual

Zennio
Zennio MINiBOX 25 Guide

Zennio
Zennio MAXinBOX FANCOIL 4CH2P Guide