© Zennio Avance y Tecnología S.L. Edition 5 Further information www.zennio.com Page 1/2
MAXinBOX 8 v3
Multifunction actuator with 8 outputs (16 A)
ZIOMB8V3 TECHNICAL DOCUMENTATION
FEATURES
•2 different configurable blocks: shutter channels (up to 4), individual
outputs (up to 8) and 2-pipe fan coil control (up to 2)
•Outputs suitable for capacitive loads, maximum 140 µF
•Manual output operation with push button and LED status indicator
•20 logic functions
•Output timing
•Total data saving on KNX bus failure
•Integrated KNX BCU (TP1-256)
•Dimensions 67 x 90 x 79 mm (4.5 DIN units)
•DIN rail mounting according to IEC 60715 TH35, with fixing clamp
•Possibility of connecting different phases in adjacent outputs
•Conformity with the CE, UKCA, RCM directives (marks on the right side)
6. Programming/test button
8. Output status LED indicator
Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure)and if the device is not in safe mode,it starts a blue blinkingsequence.
Electric operation control device
Typical TP1 bus connector for 0.8 mm Ø rigid cable
Complementary characteristics
Protection class / Overvoltage category
Degree of protection / Pollution degree
IP20 / 2 (clean environment)
Independentdevice to be mounted inside electricalpanels with DIN rail (IEC
60715)
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status
Housing material / Ball pressure test temperature
PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors)
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).