4. Prior to use
Step 1: Open the valve(s)
Screw the valve on the top of the removable tank open
or open the valve for the external fuel tank and the
fire safety valve of the heater (if present).
Step 2: Start the fuel supply
Carefully press the red unlocking button for one sec-
ond to release the float in the fuel receptacle.
The fuel receptacle only has to be unlocked when the
heater is activated for the first time or after it has run
out of fuel, or if the heater has not been used for an
extended period of time. Unlocking may also be
required if the fuel inlet pressure exceeds 2.5 psi
(± 0.17 bar). In this case, a pressure reduction valve
must be installed.
Step 3: Adjust the clock
Important: The clock on the heater must always be set
to the correct time.
A. Switch the time selector switch to “CLOCK SET”
B. Press the “HOUR” and the “MINUTE” buttons to
adjust the hours and minutes. Pressing the “HOUR”
or “MINUTE” button once will adjust the time by
one unit (hours or minutes respectively). Holding
the button down accelerates the adjustment of the
time display.
All clock and timer settings are deleted if the power is
cut offfor a period longer than 10 seconds. The infor-
mation display flashes “PM 12:00” when the heater is
switched off. The clock and timer now have to be
reprogrammed.
C. Set the timer switch to the “NORMAL” setting after
completing the clock adjustment. The current time
is then displayed on the digital indicator.
5. Manual operation
The heater is operated directly by the user. However,
the heat yield is controlled automatically in accordance
with the room temperature registered by the tempera-
ture sensor.
Step 1: Select manual operation
If the heater is in “AUTO” mode, switch the “AUTO”
switch to “OFF” to change to “MANUAL” operation.
Step 2: Switch the heater ON
Press the ON/OFF button until “ON” is displayed. The
current room temperature and the set temperature are
displayed on the information display.
The ON/OFF light starts to flash, after which the heater
will switch on. The heater will not work if the room
temperature is higher than the desired temperature
setting.
Note: (*) The start-up time depends on the room tem-
perature.
After 9-15 minutes, the heater will automatically select
the correct operating mode and the ON/OFF button
will now be illuminated continuously.
Room temperature:
under 0°C -15 minutes
0°C - 15°C - 12 minutes
15°C -9minutes
If no flames are visible after the start-up period, the
heater will deactivate and then restart automatically. If
flames arestill not detected, the heater will deactivate
and will have to be restarted manually (error code EE-2
on information display).
Step 3: Setting the room temperature
Slide the “NORMAL” temperature selector to the
selected position in order to set the desired room tem-
perature.
The desired temperature setting is shown in the infor-
mation display when you set the room temperature.
The scale on the temperature selector only serves as a
reference point. The figures on the information display
and on the scale may differ, this is normal.
The operating mode is automatically controlled in
accordance with the room temperaturedetected by the
room temperature sensor. The heater works in the
“HIGH” operating mode until the room temperature
has reached the desired level.
When the room temperature reaches the chosen set-
ting, the heater automatically switches to the “MED”
or “LOW” operating mode in order to maintain the
desired temperature. If the room temperature exceeds
92
Chapter 2, OPERATION