ZIEHL STW12V User manual

ZIEHL industrie – elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
+ 49 791 504-0, info@ziehl.de, www.ziehl.de
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Operating Manual
STW12V
updated: 2022-09-21/Um
For more information and help about this product please scan the QR-Code or
choose the following link: STW12V
Operating manual, Quick guide, Datasheet, Connection diagram, CAD Data
Firmwareupdates, FAQ, Videos about installation and settings, Certificates
STW12V 12470-0710-00 Page 1 / 8 www.ziehl.de
- Current Relay, 12 inputs in OR circuit with adjustable response threshold

STW12V 12470-0710-00 Page 2 / 8 www.ziehl.de
Table of content
1General Notes......................................................................................................................................... 3
2Application and brief description.......................................................................................................... 3
3Functional overview............................................................................................................................... 3
4Display and controls .............................................................................................................................. 3
5Connection diagram............................................................................................................................... 4
6Important notes ...................................................................................................................................... 5
7Assembly ................................................................................................................................................ 5
8Detailed description ............................................................................................................................... 5
8.1 Connection of current transducer STWA1(H):.................................................................................5
8.2 Current sensor or contact connection only:.....................................................................................6
8.3 Mixed operation: Transducers, sensors and contacts can also operate in mixed mode .................6
9Technical data ........................................................................................................................................ 6
10 Type V4 ................................................................................................................................................... 8
11 Disposal .................................................................................................................................................. 8

STW12V 12470-0710-00 Page 3 / 8 www.ziehl.de
1 General Notes
Compliance with the following instructions is mandatory to ensure the functionality and safety of the
product. If the following instructions given especially but not limited for general safety, transport,
storage, mounting, operating conditions, commissioning and disposal / recycling are not observed,
the product may not operate safely and may cause a hazard to the life and limb of users and third
parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory
material defect liability rights and to the liability of the buyer for the product that has become unsafe
due to the deviation from the specifications.
2 Application and brief description
ZIEHL current relays in the OR circuit are particularly suitable for applications where dusts, fumes, vapours or
gases are generated at various electrical consumers, which must be removed by a central extraction system.
An integrated shutdown delay controls the operation of the extraction system after working hours.
Automatic actuation with 12 inputs with adjustable response threshold.
Current is detected using current transducers type STWA1(H), current sensors S1 (also DC) or potential free
contacts.
If current is detected on at least one input, the current sensor turns on or a contact closes, the built-in relay
turns on. If the current is turned off in all monitored circuits or if it falls below the set response threshold (for
detection with STWA1(H)), the output relay disconnects with the set delay.
An adjustable response threshold allows the user to allow smaller currents without triggering switching
operations. For example, the device can be turned on to make adjustments in an electronic circuit (small
current through a current transducer). However, the extraction will not start until the main motor is turned on
(high current).
The adjustable shutdown delay makes it easy to set the delay time value.
3 Functional overview
monitoring up to 12 current circuits in an OR circuit
inputs for current transducer STWA1(H), current sensor S1 and potential free contacts
switching point adjustable 0.5 - 5 A (only for connection to the converter)
adjustable switch-off delay 1 - 60 s
plug-in connection terminals
low-voltage AC/DC adapter 24-240 V
distributor housing
4 Display and controls
1)
Response threshold adjustment
knob for transmitter connection
with integrated yellow LED:
LED is on
relay on
LED flashes
relay on
delay time active
LED is off
relay off
2) Delay time adjustment knob

STW12V 12470-0710-00 Page 4 / 8 www.ziehl.de
5 Connection diagram
Note!
When using STWA1H current transducers instead of STWA1:
ensure correct wiring of the connections
o STWA1H (+) = 1 … 12
o STWA1H (-) = ┴

STW12V 12470-0710-00 Page 5 / 8 www.ziehl.de
6 Important notes
DANGER!
Hazardous voltage!
Will cause death or serious injury. Turn off and lock out all power
supplying this device before working on this device.
Attention!
Before switching on make sure that the operational voltage Us of the
type- plate and the mains voltage are the same.
7 Assembly
The unit can be mounted as follows:
mounting of the on a 35 mm mounting rail according to EN 60715
optional: M4 screw fitting, only with additional bolt (not included)
Make the connection in accordance with the wiring diagram or the nameplate
When installing the device into the switchgear cabinet, please observe the max.
admissible temperature. Care for both, sufficient clearance to other devices and
sources of heat or enough forced draught. If cooling is made more difficult, e.g. close
devices with increased surface temperature or by handicap of airflow cooling, the
permissible ambient temperature has to be reduced.
8 Detailed description
The current relay STW12V operates in the OR circuit.
8.1 Connection of current transducer STWA1(H):
If a current greater than the set value "I" flows through at least one of up to 12 monitored wires, the relay
activates (yellow LED is on).
If the value falls approx. 0.3 A below the inrush current (yellow LED flashes),
the relay switches off again after the delay time set with the " t " adjustment knob has elapsed (yellow
LED goes out).
Failure-free and safe operation of the equipment requires that it is properly transported and stored,
professionally installed and commissioned, and operated as intended.
Work on the unit may only be performed by persons who are familiar with the installation, startup and
operation of the unit and who have the necessary qualifications for this works. They must comply with the
operating manual, the instructions placed on the device and the relevant safety regulations for the
installation and operation of electrical systems.
The units are built and tested in accordance with DIN EN and leave the factory in perfect safety condition.
If the information in the manual is not sufficient, please contact us directly or your sales agent.
Instead of the industrial standards and regulations mentioned in the operating manuals and applicable in
Europe, observe any relevant regulations valid in the country of use, should the device is operated outside
the above area.

STW12V 12470-0710-00 Page 6 / 8 www.ziehl.de
8.2 Current sensor or contact connection only:
If the current sensor turns on or the contact closes, the relay turns on (yellow LED is on).
If all sensors are off or all contacts are open (yellow LED flashes), the relay switches off again after the
delay time set with the setting knob " t " (yellow LED goes out).
The output is a potential-free switching contact.
8.3 Mixed operation: Transducers, sensors and contacts can also operate in mixed mode
Note:
The wires can also be looped through the STWA1(H) current transducer several times if the minimum
response threshold is too low. The current transducer STWA1(H) can be loaded with a maximum current AC
100 A. The switch point setting for current " I " is only active when the transducer is connected.
If only sensors or contacts are connected, the switch point setting for current " I " does not work.
Tipps:
Response threshold is too high (current flow in the wire is too low):
wires pass through the current transducer STWA1(H) several times.
Response threshold is too low (base load current must be extinguished):
connect a resistor (0.25 W / 200 V) before the corresponding input of STW, to the
current transducer STWA1(H).
750 Ω resistor = increase by a factor 2
330 Ω resistor = increase by a factor 4
120 Ω resistor = increase by a factor 10
Due to large tolerances that must be considered, we recommend that the best values be determined
by trial and error method.
Length of connecting cables STWA1(H):
Up to 50 m, but much longer are also possible.
Shielding may be required when laid parallel to power lines
9 Technical data
Control voltage Us: DC 24 - 240 V
AC 20 - 264 V
Tolerance
-
with ≤ 4 pcs. S1 current sensors
DC 20.4
-
297 V
AC 20
-
264 V 50/60 Hz
-
with
> 4 pcs. S1 current sensors
DC 80.0
-
297 V
AC 80
-
264 V 50/60 Hz
Power consumption
- without S1 current sensors < 2 W < 5 VA
- with 4 pcs. S1 current sensors < 3 W < 9 VA
-
with 12 pcs. S1 current sensors
< 5.5 W
< 16 VA

STW12V 12470-0710-00 Page 7 / 8 www.ziehl.de
Relay output: 1 switching contact (CO)
Switching voltage max AC 250 V
Switching current max 5A
Switching capacity max 1250 VA (resistive load) max 120 W at 24 V DC
Rated operational current Ie AC15 Ie = 3 A Ue = 250 V
DC13 Ie = 2 A Ue = 24 V
Ie = 0.2 A Ue = 125 V
Ie = 0.1 A Ue = 250 V
Recommended initial protection T 3.15 A (gL)
Durability of mechanical contacts 3 x107switching cycles
Life of electrical contacts 1 x 105switching cycles at AC 250 V / 6 A
Test conditions EN 61010-1
Rated insulation voltage Ui 300 V Pollution degree 2
Rated withstand surge voltage 4000 V
EMC immunity EN 61326-1 (industrial environment)
Interference emission EMC EN 61326-1 CISPR 11 Class B
Operating cycle 100 %
Permissible ambient temperature -20 °C +65 °C (without condensation and icing)
Measuring inputs: max 30 V, max 3mA
Connection - current transducer STWA1 or STWA1H
- current sensor S1 (see Us from STW12V)
- potential-free contacts
- total connection of the listed sensors
Switching point / limit value
Limit value I (current) adjustable via STWA1 AC 0.5 5 A
Tolerance ±20 %
Current sensor S1 or not adjustable contact not adjustable
Switch off delay adjustable 1. 60 s
Reception delay approx. 0.5 s
Overload capacity with STWA1 max 100A continuous, max 300 A for 10 s
+18V OUT 17 V ... 21 V
Casing: Type V4, distributor mounting
Mounting depth 55 mm
Width 4 TE
Dimensions (W x H x D) 70 x 90 x 58 mm
Cable connection one cable je 1 x 1.5 mm2
Fine wire with conductor ferrule je 1 x 1.0 mm2
Tightening torque of fixing screw 0.5 Nm
Protection deg. enclosure IP 30
Protection deg. snaps IP 20
Fixing Snap-on attachment on standard 35 mm rail in accordance
with EN 60 715 or screw fixing (with additional screw)
Weight ca. 150g, with packaging approx. 175g
Subject to technical changes

STW12V 12470-0710-00 Page 8 / 8 www.ziehl.de
10 Type V4
Dimensions in mm
1 Upper part / cover
2 Bottom part / base
3 Snap / bar for snap mounting
4 Sealing latch
5 Front panel insert / front panel
6 Position downward
7 Snap on wall mount with screws. Screw hole Ø 4,2 mm / for fixing to the wall with screws, Ø
4,2 mm.
11 Disposal
Disposal should be carried out properly and in an environmentally friendly manner in
accordance with legal provisions.
ZIEHL is registered with the EAR Foundation under WEEE no .: DE 49 698 543.
70
Option
5
7
6
58
48
16.5
4
1
2
3
61.8
45
3
(90)
116
98
This manual suits for next models
1
Table of contents
Other ZIEHL Relay manuals

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL STW1K User manual

ZIEHL
ZIEHL MSF 220 SE User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL TR600 User manual

ZIEHL
ZIEHL MS220KA User manual

ZIEHL
ZIEHL TR1200IP User manual

ZIEHL
ZIEHL STW20K User manual

ZIEHL
ZIEHL VG1200 User manual

ZIEHL
ZIEHL MSR820V User manual
Popular Relay manuals by other brands

DOLD
DOLD Safemaster LG 5925 Original instructions

Pilz
Pilz PNOZ s4.1 operating manual

Siemens
Siemens SIRIUS 3RA283 Series Original operating instructions

Siemens
Siemens 3NB2 - 4KK Series operating instructions

Emerson
Emerson Alco Controls PS4 Series operating instructions

Pickering
Pickering 40-110 user manual