ZIEHL SPI1021 User manual

ZIEHL industrie –elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
+ 49 791 504-0, [email protected]e, www.ziehl.de
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Operating Manual SPI1021
updated: 2018-03-08/Ba
from Firmware: 0-0
SPI1021 12570-0701-07 Page
1
/ 24 www.ziehl.de
- Grid- and Plant Protection According to CEI 0-21 and DEWA standard
- with self-test for < 11kW and Watchdog
- with integrated vector shift relay
- Pr3 = default

SPI1021 12570-0701-07 Page
2
/ 24 www.ziehl.de
Table of contents
1Display and controls .............................................................................................................................. 3
2Default settings and firmware version.................................................................................................. 4
3Application and brief description.......................................................................................................... 6
4Summary of the functions ..................................................................................................................... 6
5Connection diagram............................................................................................................................... 7
6Important information ............................................................................................................................ 8
7Assembly ................................................................................................................................................ 8
8Detailed description ............................................................................................................................... 9
8.1 Description of the connections....................................................................................................... 9
8.2 functional characteristics.............................................................................................................. 10
9Commissioning..................................................................................................................................... 11
9.1 Program Setup ............................................................................................................................ 11
9.2 Control chart Pr 1…6 ................................................................................................................... 12
9.3 description of the parameters....................................................................................................... 13
9.4 Display mode (last decimal point off) ........................................................................................... 13
9.5 Menu mode (last decimal point on).............................................................................................. 14
9.6 Configuration mode (last Decimal point flashes).......................................................................... 14
9.7 Self-test execute.......................................................................................................................... 14
9.8 Display Self-test result................................................................................................................. 14
9.9 Alarm counter.............................................................................................................................. 14
9.10 Cumulative alarm time (display in hours) ..................................................................................... 15
9.11 Alarm Memory............................................................................................................................. 15
9.12 Standby counter and standby time............................................................................................... 15
9.13 Code lock .................................................................................................................................... 16
9.14 Sealing ........................................................................................................................................ 16
9.15 Simulation.................................................................................................................................... 17
9.16 Possible indications in display...................................................................................................... 18
10 Technical Data...................................................................................................................................... 19
11 Maintenance and repair........................................................................................................................ 20
12 Troubleshooting an measures............................................................................................................. 21
13 Construction form V6........................................................................................................................... 22
14 Verification in conformity, CEI 0-21..................................................................................................... 23
15 Verification in conformity, DEWA........................................................................................................ 24

SPI1021 12570-0701-07 Page
3
/ 24 www.ziehl.de
1 Display and controls
1
Test Button
press briefly
the self-test result is displayed, display next result
Press for > 2 s
Start self-test, K1 de-energize, K2 energize
2
LEDs Inputs status (yellow)
OFF
Input not activ (open)
ON
Input activ (closed)
3
LEDs relay status (yellow)
OFF
Relay is released
ON
Relay is operating
4
Digital display 4-digits (red)
Depending on program, display of current voltage, frequency, vector shift, average value
Displays the alarm signals, e.g. 8AL 8, 8aL M8
Displays the errors with error code e.g. 8Err98
5
LED Time (yellow)
ON
A time is displayed
6
Last decimal point (red)
OFF
Display mode
Illuminated
Menu mode
Flashes
Configuration mode
7
Set / Reset key (in display mode, normal state)
Press briefly
Display of next measured value / alarm counter
Press for > 2 s
Reset, quit error messages
Press for > 4 s
Displays the program, e.g. 8Pr 18
Press for > 10 s
Displays the software version, e.g. 80-0 8
8
Up / Down key (in display mode, normal state)
Press briefly
Change to the menu mode, display of alarm memory (Down) / cumulative
time of alarms, standby counter, standby time (Up), pushing Set button for
≥ 2 s resets the stored values
Press for > 2 s
Display of MAX (Up) / MIN (Down) - measured values, additional pushing
of Set button for ≥ 2 s deletes the stored values
9
LEDs measurement allocation (yellow)
LEDs
Measured value
Lx and N ON
Voltage value (L1 against N, L2 against N, L3 against N)
Lx and Ly ON
Voltage value (L1 against L2, L2 against L3, L1 against L3)
Lx FLASHING quickly
Vector surge (L1, L2, L3)
L1 FLASHING
Frequency

SPI1021 12570-0701-07 Page
4
/ 24 www.ziehl.de
10
sealable button + LED
Press for > 2 s
Lock / Unlock
LED red
Settings and simulation mode are locked,
While attempting to set, 8LOc 8is displayed for 3s
LED green
Setting and simulation enabled
11
LEDs frequency / voltage / VSR Limit value undercut / exceeded (red)
ON, 8AL 8or 8AL M8
Limit value undercut / exceeded
FLASHES, 8AL 8or 8AL M8
Reset delay 8dof 8counting down
2 Default settings and firmware version
When changing programs, all parameters are reset to the *default settings.
Menu
item
Parameter / Unit
Default setting
Users
data
CEI 0-21
DEWA
3AC+N
230V
3AC
400V
1AC+N
230V
3AC+N
230V
3AC
400V
3AC
100V
Pr1
Pr2
Pr3 *
Pr4
Pr5
Pr6
U,,
59.S2
59>S2
u,, Alarm on/off
Off
Off
Off
Off
Off
OFF
u,, Overvoltage
V
264
458
264
264
458
115
H,, Hysteresis
V
10.5
17.5
10.5
10.5
17.5
4.5
dal Response time
s
0.10
0.10
0.10
0.10
0.10
0.10
dof OFF-delay
s
0
0
0
0
0
0
U,
59.S1
59>S1
u, Alarm on/off
On
On
On
On
On
On
u, Overvoltage
V
264
458
264
253
438
120
H, Hysteresis
V
10.5
17.5
10.5
10.5
17.5
4.3
dal Response time
s
0.20
0.20
0.20
0.20
0.20
0.60
dof OFF-delay
s
0
0
0
0
0
0
UM
59-Av
UM Alarm on/off
On
On
On
On
On
On
UM Overvoltage
V
253
438
253
253
438
110
HM Hysteresis
V
10.0
17.5
10.0
10.0
17.5
4.3
dal Response time
s
3.00
3.00
3.00
3.00
3.00
3.00
dof OFF-delay
s
0
0
0
0
0
0
U_
27.S1
27<S1
u_ Alarm on/off
On
On
On
On
On
On
u_ Undervoltage
V
196
339
196
196
339
85
H_ Hysteresis
V
8.0
13.5
8.0
8.0
13.5
3.5
dal Response time
s
0.40
0.40
0.40
0.40
0.40
1.50
dof OFF-delay
s
0
0
0
0
0
0
U__
27.S2
27<S2
u__ Alarm on/off
On
On
On
On
On
On
u__ Undervoltage
V
92
159
92
92
159
3.0
H__ Hysteresis
V
3.7
3.7
3.7
3.7
6.4
1.5
dal Response time
s
0.20
0.20
0.20
0.20
0.20
0.20
dof OFF-delay
s
0
0
0
0
0
0
F,,
81.S2
81>S2
F,, Alarm on/off
On
On
On
On
On
On
F,, Overfrequency
Hz
51.50
51.50
51.50
54.00
54.00
54.00
H,, Hysteresis
Hz
0.10
0.10
0.10
0.10
0.10
0.10
dal Response time
s
0.10
0.10
0.10
10.0
10.0
10.0
dof OFF-delay
s
0
0
0
0
0
0
F,
81.S1
81>S1
F, Alarm on/off
On
Off
Off
Off
Off
Off
F, Overfrequency
Hz
50.50
50.50
50.50
52.50
52.50
52.50
H, Hysteresis
Hz
0.10
0.10
0.10
0.10
0.10
0.10
dal Response time
s
10.00
0.10
0.10
0.10
0.10
0.10
dof OFF-delay
s
0
0
0
0
0
0

SPI1021 12570-0701-07 Page
5
/ 24 www.ziehl.de
Menu
item
Parameter / Unit
CEI 0-21
DEWA
Users
data
3AC+N
230V
3AC
400V
1AC+N
230V
3AC+N
230V
3AC
400V
3AC
100V
Pr1
Pr2
Pr3 *
Pr4
Pr5
Pr6
F_
81.S1
81<S1
F_ Alarm on/off
Off
Off
Off
OFf
Off
Off
F_ Underfrequency
Hz
49.50
49.50
49.50
47.50
47.50
47.50
H_ Hysteresis
Hz
0.10
0.10
0.10
0.10
0.10
0.10
dal Response time
s
0.10
0.10
0.10
4.00
4.00
4.00
dof OFF-delay
s
0
0
0
0
0
0
F__
81.S2
81<S2
F__ Alarm on/off
On
On
On
On
On
On
F__ Underfrequency
Hz
47.50
47.50
47.50
46.00
46.00
46.00
H__ Hysteresis
Hz
0.10
0.10
0.10
0.10
0.10
0.10
dal Response time
s
0.10
0.10
0.10
0.10
0.10
0.10
dof OFF-delay
s
0
0
0
0
0
0
UonF
UonF Alarm on/off
Off
Off
Off
On
On
On
UonF Spannung 0,2 Un
V
46
80
46
46
80
20
Vsr
78
vsr Alarm on/off
Off
Off
Off
Off
Off
Off
vsr Vector shift
°
10.0
10.0
10.0
10.0
10.0
10.0
dof OFF-delay
s
3
3
3
1
1
1
dEon Suppression time
s
2
2
2
2
2
2
vsr Number of phases
3ph
3ph
3ph
3ph
3ph
Rocf
81r
rocf Alarm on/off
Off
Off
Off
Off
Off
Off
dfdt delta f / delta t
Hz
/s
0.800
0.800
0.800
2.000
2.000
2.000
Per periods
20
20
20
20
20
20
dal Response time
s
0.10
0.10
0.10
0.10
0.10
0.10
dof OFF-delay
s
60
60
60
1
1
1
rEL
trEL response time Y1
s
5.0
5.0
Off
5.0
5.0
5.0
Don Delay On
s
300
300
300
300
300
300
Mode
mode Mode
Tran
Tran
Tran
Tran
Tran
Tran
Dal_ Response time(<</>>)
s
1.00
1.00
1.00
1.00
1.00
1.00
Dal_ Response time(<</>>)
s
4.00
4.00
4.00
4.00
4.00
4.00
ddi
ddi Display delay
s
0.5
0.5
0.5
0.5
0.5
0.5
dit Display duration SCn
s
3.5
3.5
3.5
3.5
3.5
3.5
Si
U Voltage
V
230
400
230
230
400
100
F Frequency
Hz
50.00
50.00
50.00
50.00
50.00
50.00
vsr Vector shift
°
0.0
0.0
0.0
0.0
0.0
0.0
CodE
pin Pincode
504
504
504
504
504
504
Info
fnr Firmware version
0-0D
0-0D
0-0D
0-0D
0-0D
0-0D
snr Serial number
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
h Operating hours
h
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
err Error counter
xxx
xxx
xxx
xxx
xxx
xxx
Pr Program
1
2
3
4
5
6
Display program: 8Info88Pr 8or when switching on, Display firmware version: 8Info88fnr 8

SPI1021 12570-0701-07 Page
6
/ 24 www.ziehl.de
3 Application and brief description
The SPI1021 monitors voltage and frequency in plants for own generation of electricity. It fulfills the
requirements of CEI 0-21 + DEWA.
6 selectable programs allow measuring, 3 phases to neutral (4-wire mode), 3 phases phase-phase (3-wire
mode) and single phase to neutral (2-wire).
The SPI1021 can monitor all decentralized power plants, photovoltaic, wind or thermal, that feed in the low or
medium voltage grid. In applications with possible asymmetry >6kVA, power balance has to be monitored
extra.
All limits are preset according to CEI 0-21(Pr1-3) or DEWA (Pr4-6). They can be changed if required and be
protected with a code and/or a seal.
A counter for alarms and standbys stores the last 100 events with reason and elapsed time. In addition the
time the SPI1021 has interrupted the plant is recorded. All values can be read displayed at the device and
give the operator valuable information about the availability of the plant.
The standby input allows a remote shutoff e.g. with a RCR. It can also be used to switch to an energy saving
mode by a timer or a twilight switch. Number of standbys and added time are stored and can be read in the
display.
4 Summary of the functions
When the device has been installed, a self-test starts automatically. The self-test can be repeated when
required. All values of the test are stored and can be read out at the display.
•Monitoring of under- and overvoltage 0/15-520 V
•Measuring of 3 phases with or without neutral or single phase
•Monitoring of over- and underfrequency 45-65 Hz (voltage dependent, adjustable)
•Monitoring of quality of voltage (10-minutes-average)
•Monitoring of vector-shift (connectible) and rocof (rate of change of frequency)
•Input IN2 for selection of frequency window
•Input In3 for selection of mode transitory or definitive
•Input Y0/Y1 for monitoring function of connected switch (automatic detection of nc/no)
•Relay K2 picks up (on time <500ms) only at failure at switch connected to K1, only with manual reset
•2 restarts at switch-on error of connected switch
•Self-test with storing of values
•Switching delays adjustable 0,05…130 s
•Switching-back-delays adjustable 0…999 s
•Different switching time according to type of alarm and selected mode
•Switch-on delay 300 s
•All parameters preset according to CEI 0-21
•Alarm counter for 100 alarms with value, reason and elapsed time
•Recording of added time of alarms
•Input for standby (off time <50ms) with counter and recording of time
•Simulation for testing
•Sealing, all parameters can be read out while sealed
•Easy installation and programming with 6 preset programs
•Supply-voltage AC/DC 24-270 V
•Housing for DIN-rail-mount, 105 mm wide, mounting height 70 mm

SPI1021 12570-0701-07 Page
7
/ 24 www.ziehl.de
5 Connection diagram
1x PV, 2x section switch
1) Feedback contacts not connected set 8rel .88trel.88off.8
2) Fuses only when line protection necessary, e.g. 3x16A
3) 8Pr 38Phase connect to L1, L2 and L3 are not connected
4) N connected set 8Pr 18, 8Pr 38, 8Pr 48
5) NC- or NO-contacts can be connected, automatic detection when switching on
6) must be connected for plants ≥ 20kW

SPI1021 12570-0701-07 Page
8
/ 24 www.ziehl.de
6 Important information
A marked switch and a protective device must be provided in the supply line in the
vicinity of the device (easily accessible) as a disconnecting element
(rated current ≤ 6A).
Flawless and safe operation of such a device requires proper transport and storage, professional instillation
and later commissioning along with operation as intended.
Only persons who are familiar with the installation, commissioning and operation of the device and who are
correspondinglyqualifiedfor their job are permitted to work on the device.They must comply with the contents
of the operating manual, the instructions attached to the device and the pertinent safety regulations for the
erection and operation of electrical equipment.
The devices are built andcertified in accordance with EN 60255 and leave the factory in a safe and technically
flawless condition. To maintain this condition they must comply with the safety regulations marked in the
operating manual with the headline "Caution". Failure to follow the safety regulations can lead to death, bodily
injury or property damage to the device itself and to other devices and equipment.
If the information contained in the operating instructions/operating manual are not sufficient, please contact
us directly or contact your responsible agency or representative.
Instead of the industrial norms and stipulations stated in the operating manual and applicable in Europe you
must comply with the valid and applicable regulations in the country of utilisation if the device is used outside
of the area of application.
WARNING
Hazards electrical voltage!
Can lead to an electric shock and burns.
Disconnect and de-energize before working on the system and the device.
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air current,
the permissible ambient temperature is decreased.
Caution!
Before you apply mains voltage to the device, make sure that the permissible control
voltage Us on the side rating plate matches the mains voltage connected to the device!
7 Assembly
The device can be mounted:
•Distribution panel or control panel on 35 mm rail according to EN 60715

SPI1021 12570-0701-07 Page
9
/ 24 www.ziehl.de
8 Detailed description
8.1 Description of the connections
Connection Description
A1 and A2
Rated control supply voltage Us, see Technical Data
11, 12, 14; 21, 22, 24
Relay K1 (DDI) und K2 (rincalzo, back up, only with manual reset)
E1 –E2
Enable –Input
volt-free contact
8vsr .88 off.8, no function
8vsr .88 on.8, E1-E2 closed: Vector shift active but not
evaluated, monitoring of feedback contacts off for use with generator
(mains synchronization)
Y0, Y1
Inputs feedback contacts
Volt-free n/o or n/c contact, self-learning when switching on
Set value > turn-on time section switch under 8rel .88trel.8/
can switch-off if not connected or if external devices/switches can
activate the section switch (8off .8)
+U
Supply output for digital outputs, DC 15…35 V
IN1
(teledistacco, RCR)
volt-free contact
closed: K1 released <50 ms (Standby mode, 8stby.8)
IN2
(commando locale)
volt-free contact
transitory mode
open: 8F::.8+ 8F__ .8= 8 on.8; 8F: .8+ 8F_ .8= 8 off.8
closed: 8F::.8+ 8F__ .8= 8off.8; 8F: .8+ 8F_ .8= 8 on.8
definitiv mode
open: 8F::.8+ 8F__ .8= 8off.8; 8F: .8+ 8F_ .8= 8 on.8
closed: 8F::.8+ 8F__ .8= 8 on.8; 8F: .8+ 8F_ .8= 8 off.8;
alternative response time : 8dAl:.8+ 8dal_.8active
IN3
(signale esterno)
volt-free contact
8mode.88tran.8, 8mode.88defi.8, no function
8mode.88IN 3.8,
closed: Definitiv mode
open: Transitory mode
L1, L2, L3, N
Phase L1, L2, L3 and neutral conductor

SPI1021 12570-0701-07 Page
10
/ 24 www.ziehl.de
8.2 functional characteristics
Functional characteristics
Explanation
VSR display value
The highest measured value is always displayed. The display value
is reset to 0 by deleting the max. Value and when resetting into the
go (good) state.
Delay Enable On time
Runs down when starting the unit and after opening the enable
input; during this time there is no evaluation of the vector shift
Reset time
When a reset time 8dof 8is running, it is always counted down in
the display (shortest one first)
Reset
Use the Reset key or interrupt the control voltage for > 2 s (comply
with reset delay)
Display mode 8Scn8
After the last measurement it switches into the scan mode; this is
indicated by the display8scn 8.
All measurements will now be displayed cyclically for the time set in
8dit8.
MIN / MAX values
All min and max values are saved zero-voltage maintained (non-
volatile).
Alarm counter
The unit saves max 100 alarms (cause, measurement value, at
operating time). The LEDs indicate the cause; the tripping value
that led to the alarm each stands in the 7-segment display.
Alternately the time difference, current operating time –tripping
operating time is displayed. (how long ago the alarm triggered)
Cumulative alarm time
8tal .8
The cumulative alarm time TAL indicates how long the relay was
switched off due to an alarm. It is recorded with a resolution of 1
minute and only when the control voltage is applied.
Query: In the display mode button to 8ac .8is displayed. 1x
button = Cumulative alarm time8tal .8
Standby mode
8vsr .88stby.8
If IN1 is closed (e.g., by ripple control receiver, timer, dimmer),
Relays K1 and K2 are switched off. The number and duration of the
shut-downs is recorded.
Query: In the display mode button to 8ac .8is displayed. 2x
button = Standby counter 8stby.81x button = Standby time
8stby.8
Automatic restart attempts
If there is an error by the feedback contacts 8err78, 2 restart
attempts are automatically performed in an interval of 10s.
False triggering by undervoltage trips (e.g. during a thunderstorm)
do not lead to permanent shut-down.
Frequency undervoltage
protection
8uonF8
if one of the measured voltages less than 8uonf8, the frequency
evaluation is interrupted until all voltages have exceeded 8uonf8.
(does not apply to device start / apply of the control voltage)

SPI1021 12570-0701-07 Page
11
/ 24 www.ziehl.de
9 Commissioning
9.1 Program Setup
The suitable program must be set on the SPI1021 in accordance with the application. If the SPI1021 is
sealed/locked (red LED illuminated), the sealing has to be deactivated first.
Pr
Connection
Limit
Rated
voltage
default
setting
Standard
1
3 AC with N
2x overvoltage, 2x undervoltage
2x overfrequency, 2x underfrequency
10min mean value, 1x vector shift,
1x rocof
230V
CEI 0-21
CEI 0-21
+
DEWA
2
3 AC without N
400V
CEI 0-21
*3
1 AC with N
230V
CEI 0-21
4
3 AC with N
230V
DEWA
5
3 AC without N
400V
DEWA
6
3 AC without N
100V
DEWA
* default setting
Adjustment process:
If present, remove seal (only authorized person)
•Apply control supply voltage at A1-A2
•Slightly lift the key cover and turn 180°
•Actuate the small blue button by firmly pressing the button cover (LED starts flashing) until the green
LED is illuminated.
Sealing is deactivated
•Press button 1x display 8Info.8
•Press button 5x display 8Pr 1.8
•Set the program with the buttons
•Press button 1x display 8no.8
•Press button 1x display 8yes.8
•Press button
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to “default settings
(see table „Default settings“). Only change the parameters after having selected the correct
program.

SPI1021 12570-0701-07 Page
12
/ 24 www.ziehl.de
9.2 Control chart Pr 1…6
[ ] = Unit
Up/Down simultaneously sets the
value to the lowest value.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err5 = Internal control
Err7 = Contactor feedback
contacts K1
Err8 = Limit error
Err9 = Parameter error
1) 1/3AC+N = 300V
Display mode
Configuration mode
Menu mode

SPI1021 12570-0701-07 Page
13
/ 24 www.ziehl.de
9.3 description of the parameters
Parameters
Display
Explanation
Adjustment range
Power up delay
(delay On)
8don 8
Runs once at startup device,
adjustable 8rel .88don .8
80.08… 89998
Limit value
8U,, 88U, 8
8u_ 88U__ 8
8Um 8
Voltage limit value
815.08… 83008
815.08… 85208
Limit value
F,, ,8F, 8
,
8F_ 8,8F__8
Frequency limit value
845.008… 865.008
Frequency
Undervoltage
8UonF8
frequency undervoltage, below this value
the frequency protection is inhibited
80.08… 8320 8
Hysteresis
8H 8
253V (Limit) –3V (Hysteresis) =
250V (Reset value)
If the limit value is offset in Pr1 or Pr2 at
8F, 8, the hysteresis also has to be
adapted.
81.08… 899.08
80.058… 810.008
Response time
(delay Alarm)
8dAL 8
An alarm is suppressed for the set time
(seconds)
80.058… 8120.08
Turn-on time
(delay Off)
8dOF 8
Reset is delayed for the set time, also
during voltage recovery, this time (seconds)
is always counted down in the display
808… 8 9998
Enable time
(delay On)
8dEon8
There is no evaluation of the vector shift
during this time; starts with the application
of the control voltage and when opening the
Enable input
828… 8208
VSR
8VSR8
81 Ph8: a vector surge on one phase leads
to an alarm
83 Ph8: a vector surge on all phases
simultaneously leads to an alarm
81 Ph8… 83 Ph8
Limit value
8dfdt8
ROCOF, df/dt limit value
8 0.108… 85.008
Periods
8per 8
Measuring time ROCOF,
(4=sensitive, 50=insensitive)
Response time=
8per 8* Period duration + 8dal 8
848… 8 508
delay Display
8ddi 8
Interval during which the display is updated
in the display mode
80.18… 82.08
9.4 Display mode (last decimal point off)
In the display mode, the SPI1021 is in its normal state; here, depending on the program, the actual voltage,
the highest actual 10 minute mean value, the frequency or the vector surge is displayed. In addition, the alarm
signals (e.g. 8aL 8, 8aL m8) and error codes (e.g. 8err98) are displayed.
Function button
Set / Reset
Press briefly: Switches the measurement, alarm counter
Press for > 2 s: Resets after locked alarm
(not possible if doF Reset delay is counting down)
Press for > 4 s: Displays the program, e.g. 8Pr 18
Press for > 10 s: Displays the software version, e.g. 80-038
Function key
Up / Down
Press briefly: Change into the menu mode,
Display alarm counter: Down = Query the memory
Up = Query the cumulative alarm time
Press for ≥ 2 s: Displays MAX and MIN measurements, additionally
pressing the Set key for ≥ 2 s deletes the saved values

SPI1021 12570-0701-07 Page
14
/ 24 www.ziehl.de
9.5 Menu mode (last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically returns to
the display mode.
Function button
Set / Reset
Press briefly: Change into the configuration mode
Press for ≥ 2 s: Returns to the display mode (the most recently set values
are then applied)
Function key
Up / Down
Press briefly: Select menu item; changes into the display mode
9.6 Configuration mode (last Decimal point flashes)
In the configuration mode you can set the value of a parameter. The display alternates between the parameter
relation and the currently set value until one of the Up/Down buttons is pressed, which changes the value of
the parameter. If no key is pressed for 2 s the display starts alternating again.
If no key is pressed for 30 s (simulation mode 15 min) one automatically returns to the display mode (the most
recently set value is applied during this)
Function button
Set / Reset
Press briefly: The settings are taken over; continue to next parameter.
Changes into menu mode after the last parameter
Press for ≥ 2 s: Returns to the display mode (the most recently set values are
then applied)
Function key
Up / Down
Press briefly/long: Value change of the parameter (slow/fast)
Hint: Simultaneously pressing the Up and Down keys resets the adjustable value to zero. If the Up or Down
button is kept pressed while setting the value the change in the display is accelerated.
9.7 Self-test execute
In programs 1, 3, 4 the SPI1021 has an automatic self-test as recommended in CEI 0-21 and DEWA.
K1 can pick up only after the self-test has been passed once.
Self-test starts automatically as soon as measuring voltage is connected for the first time to a new device and
when there is no alarm! Self-test also starts automatically when program has been changed to 1, 3, 4.
Self-test can be started manually by pressing button Test for ≥2 s.
During the Self-test is 8test8displayed.
At the end of the test the result 8pass8(passed) or 8fail8(not passed) is displayed for 30 seconds. Reset
stops the test.
During self-test supply- and measuring-voltage may not be disconnected!
9.8 Display Self-test result
The values and times have been measured during self-test can be displayed by pressing button Test shortly.
Kind of limit (8U::8, 8U: 8, 8Um 8, 8U_ 8, 8U__ 8, 8f::8, 8f: 8, 8F_ 8, 8F__ 8), response time,
measured value, trigger value and adjusted limit are displayed. LEDs (yellow) at the terminals L1…N shows
the measured and trigger value.
By pressingTest shortlydisplay changesto the values of thenext kind of limit. At lastthe result 8pass8(passed)
or 8fail8(not passed) is displayed and additionally the switching time from K1 if 8trel8is activated.
Display automatically returns to normal mode 30 s after button Test has been pressed for the last time.
9.9 Alarm counter
The alarm counter 8ac 8is increased by 1 with every shut-down. Up to 100 shut-downs are counted. That
allows quick detection of how often the SPI1021 has shut down since the last delete of the alarm counter (see
cumulative alarm time).
Query the alarm counter:
•Change into the display mode
•Press the button several times until display 8acxx8

SPI1021 12570-0701-07 Page
15
/ 24 www.ziehl.de
9.10 Cumulative alarm time (display in hours)
The cumulative alarm time 8tal 8indicates how long the relay was switched off due to an alarm. It is
recorded with a resolution of 1 minute and only when the control voltage is applied.
Query the cumulative alarm time:
•Change into the display mode
•Press the button several times until display 8acxx8
•Press the button 1x display 8tal 8/ 8x.xx8
Delete the alarm counter and cumulative alarm time (only together):
•Display alarm counter8acxx8
•Press the button 1x display 8tal 8/ 8x.xx8
•Keep the button pressed for 2s until display 8tal 8/ 80.008
9.11 Alarm Memory
Independent of the alarm counter, the SPI1021 stores the most recent 100 shut-down causes (cause,
measurement value, at operating time). Simulated alarms are also registered. The LEDs indicate the cause;
the tripping value that led to the alarm each stands in the 7-segment display. Alternative to that
the time is shown in hours which have passed since the last tripping (with applied control voltage).
These values remain saved even after the power has been turned off.
Query alarm memory:
•Change into the display mode
•Press the button several times display 8acxx8
•Press the button 1x display 8 x.xx8/ 8x.xx8
(tripping value or error no. / time that has passed in hours)
•Press the button 1x, go to next alarm
The alarm memory is only deleted during a program change.
9.12 Standby counter and standby time
The standby counter 8stby8, is increased by 1 with every standby shut-down. Up to 9999 shut-downs are
counted. That lets the SPI1021 quickly detect how often, e.g., shut-down was performed through a ripple
control receiver.
Query the standby counter:
•Change into the display mode
•Press the button several times until display 8acxx8
•Press the button 2x display 8stby8/ 8xxxx8
The standby time 8stby8indicates how long the relay was switched off by the standby mode. It is recorded
with a resolution of 1 minute and only when the control voltage is applied and if no alarm is present.
Query the standby time:
•Change into the display mode
•Press the button several times until display 8acxx8
•Press the button 3x display 8stby8/ 8x.xx8(Time LED is illuminated)
Delete the standby counter and standby time (only together):
•Display alarm counter8acxx8
•Press the button 2x display 8stby8/ 8xxxx8
•Keep the button pressed for 2s until display 8stby8/ 808

SPI1021 12570-0701-07 Page
16
/ 24 www.ziehl.de
9.13 Code lock
You can protect the set parameters by enabling the code lock here.
The device acknowledges an incorrect entry with 8err8(flashes three times).
Adjustment process:
•Select the menu item with the buttons until display 8Code.8
•Press the button 1x display 8Pin 8/ 808
•Set the saved pin code with the buttons (default setting is 85048)
•Press the button 1x display 8Code8/ 8off 8
•Use the buttons to set the desired code lock:
o8off8off, all parameters can be changed
o8On8on, no parameters can be changed
•Press the button 1x display 8Pin 8/ 85048
•Use the buttons to set the new, desired pin code (caution: write down the pin code)
•Press the button 1x
Code lock on, display 8on8flashes three times
Code lock off, display 8off 8flashes three times
Return to menu mode, menu item code lock
If there any problems with the code lock (Pin forgotten), the lock can be switched off and the pin can be reset
to 504 by keeping the Set key pressed while switching on the mains until 8Code8/ 8off8appears in the
display.
9.14 Sealing
All the settings and the simulation mode can be locked.
If the LED is illuminated, the SPI1021 is locked.
If an attempt is made to change a setting in the locked state, for 3s the display shows 8LOc 8.
Adjustment procedure Sealing/Lock ON (OFF):
•If present, remove seal (only authorized person)
•Apply control supply voltage at A1-A2
•Slightly lift the key cover and turn 180°
•Actuate the small blue button by pressing the button cover very firmly (LED starts flashing)
until the green LED is illuminated.

SPI1021 12570-0701-07 Page
17
/ 24 www.ziehl.de
9.15 Simulation
Here, the voltage, frequency or a vector surge can be simulated and the setting can be tested. All 3 phases
plus the 10 minute mean value are always simulated. All functions of the device operate as if this value is
actually being measured. Alarm and error messages are only indicated with the LEDs and not in the display.
The set values are simulated until the menu item si . is exited with the or button. If the SPI1021 is
sealed/locked, simulation is not possible.
If the section switch feedback contacts are connected to the SPI1021 and enabled, (set value > section-
switch turn-on time under 8trel.8), after a shut-down, the tripping time (dAL + time of slowest section switch)
is displayed.
Adjustment process:
•Select the menu item with the buttons until display 8si .8
•Press the button 1x display 8si 8/ 8u 8
•Use the buttons to set the measurement factor for simulation:
o8u 8Voltage + 10min mean value (frequency = last simulated value)
o8f 8Frequency (voltage = last simulated value)
o8vsr 8Vector shift
•Press the button 1x display 82308(selected measurement factor is simulated)
•Use the buttons to set the desired value
After exiting the Simulation menu item with the buttons, the unit switches over to monitoring the limits.
The unit automatically returns to the display mode if no button is pressed for 15 minutes.
Hint: A limit value should be tested that is higher than the set 10min mean value. If the 10min mean value has
to be temporarily switched off, set (8Um .88off.8since otherwise it will trip first. The same applies, for
example, for U, , during a simulation of U,, .

SPI1021 12570-0701-07 Page
18
/ 24 www.ziehl.de
9.16 Possible indications in display
display mode
8 AL 8,8Am 8
Alarm , Alarm 10min mean value
8Err58…8err98
Error messages (see 11. Error messages and measures)
8Ac 8 ,8tal 8
Alarm counter, cumulative alarm time
8Scn 8 ,8 M 8
Scan mode, 10min mean value
Menu mode / configuration mode
U,, ,8U, 8,
8u__ 8,8U_ 8
Voltage limit value
UM 8
Limit value 10min mean value
H,, ,8H, 8,
8H__ 8,8H_ 8,8HM 8
Hysteresis (if a limit value is changed, the reset value also shifts; that
means it might be necessary to adapt it)
F,, ,8F, 8,
8F__ 8,8F_ 8
Frequency limit value
8dal 8,8dof 8
Response time, Reset time; is always counted down in the display
UonF8
Frequency undervoltage (inhibited frequency protection)
8vsr 8,8rocf8
Vector surge, ROCOF
8dfdt8,8 per8
Limit ROCOF, response time in periods (4=sensitive, 50=insensitive)
8stby8
Standby mode, standby-time, standby-counter
8Deon8
Delay Enable On, suppression time when switching on and after opening
the enable input
81 ph 8 ,83 ph 8
Single phase, three-phase vector shift evaluation
8rel 8,8trel8
Relay, Section switch turn-on time, 8off8no feedback contacts
tdon8
Power Up delay, runs once at power up device
mode ,8tran8,defi8
Mode, Transitory Mode, Definitiv Mode
8ddi 8
Delay display, to calm down the display
Dit 8
Display duration scan mode (each measurement is displayed for this
duration)
8Si 8
Simulation
F ,8U 8
Frequency, voltage
Code ,8Plo 8,8vsr8
Code lock / sealing, vector shift
8Pin 8
Pin code (default 504)
Info8
Device information, program change
Fnr 8,8snr 8
Firmware version, serial number
h 8
Operating hours
Err 8,8del 8
Error counter, delete error counter
8yes 8,8no 8
Yes, no query for acknowledgement
Pr 8
Program
8on8,8oFF8
On, Off

SPI1021 12570-0701-07 Page
19
/ 24 www.ziehl.de
10 Technical Data
Control voltage Us:
Rated-Connection AC/DC 24-270 V, 0/40...70 Hz, <1,8W / <6,5 VA
DC: 20,4...297 V, AC: 20,4...297 V
Voltage drop SPI1021 must be supplied with a UPS (>5s)
Output relay: 2 x change-over contact
Switching voltage Max. AC 440 V
Conventional thermal current Ith 6 A
Inrush current (at 10 % ED) 25 A max. 4 s / 50 A max. 1 s
Nominal operating current Ie (AC 15) 6 A AC 250 V
Recommended series fuse gG/gL 6 A
Contact service life, mech. 30 x 106switching cycles
Contact service life, electr. 1 x 106operating cycles at AC 250 V / 6 A
2 x 105operating cycles at AC 250 V / 10 A cos φ 0.6
Voltage measurement:
Measurement voltage phase –phase AC 15…530 V (< 5 V: 0 is displayed)
Adjustment range phase –phase AC 0/15…520 V
Measurement voltage phase –N AC 10…310 V (< 5 V: 0 is displayed)
Adjustment range phase –N AC 0/15…300 V
Measurement principle Real root mean square measurement both half waves
Hysteresis Adjustable 1.0…99.9 V
Measurement error (with N) ± 0.6 % of the measurement value
Measurement error (without N) ± 0.8 % of the measurement value
Display accuracy >100V: -1 digit (res. 1 V)
<100V: -1 digit (res. 0.1V)
Measurement function 3-phase with/without N
Response time Adjustable 0.05 (±15ms)…120.0 s
Reset time Adjustable 0(>200ms) … 999 s
Frequency measurement
Frequency range 40…70 Hz (U-L1 > 8UonF8)
Adjustment range 45.00…65.00 Hz
Hysteresis 0.05…10.00 Hz
Measurement accuracy ± 0.04Hz ± 1 digit
Response time Adjustable 0.05 (±15ms)…120.0 s
Reset time Adjustable 0 (>200ms) … 999 s
Vector surge
Measurement range 0…45.0°
Adjustment range 2.0…20.0°
Response time < 50 ms
Reset time Adjustable 3…240 s
Delay at Us on Adjustable 2…20 s
ROCOF (df/dt)
Frequency range 40…70 Hz
Adjustmet range 0,100…5,000 Hz/s, 4…50 Periods
Hysteresis fixed 0,05Hz
Measurement error ± 0,04Hz ± 1Digit
Response time adjustable 0,05 (±15ms) … 130.0 s
Reset time adjustable 0 (>200ms) … 999 s
Measurement time Number of adjusted Periods * Periods duration + Response
time

SPI1021 12570-0701-07 Page
20
/ 24 www.ziehl.de
Digital inputs (INx)
Output voltage +U DC 15…35 V
Current INx > 3 mA
Contactor feedback inputs
Voltage Y0 –Y1/2 DC 15…35 V
Current > 3 mA
Contactor response time (section switch) Adjustable 0.5...99.0 s
Self-test and Watchdog
in programs / alarms Pr 1, 3, 4
alarms U>>, U>, U10min (dAL=100ms), U<, U<<, f>>, f>, f<, f<<
Slope Rate Voltage <150V: 2,5V/s, ≥150V: 5,0V/s
Slope Rate Frequency 0,05Hz/s
Permissible tolerance measured value –trigger value: ≤±1%
Response time: ±20ms
Display result „Pass“ = passed, „Fail“ = failed
TimeOut / max. Duration 180s / 18 min (all dAL=120.0 s)
Watchdog internally
Test conditions EN 60255
Rated impulse withstand voltage 4000 V
Overvoltage category III
Pollution degree 3
Rated insulation voltage Ui 300 V
Operating time 100 %
Permissible ambient temperature -20 °C... +55 °C
EN 60 068-2-2 dry heat
EMC - noise immunity EN 61000-6-2
EMC - noise emission EN 61000-6-3
Housing:
Construction form V6
Front-to-back size 55 mm
Dimensions (W x H x D) 90 x 105 x 69 mm
Wiring connection single strand each 1 x 4mm2
Finely stranded with wire end ferrule each 1 x 2.5mm2
Protection class, housing IP 30
Protection class, terminals IP 20
Mounting snap-on fastening on 35 mm mounting rail acc.
EN 60 715 or with M4 screwed attachment
(additional bar not included in the scope of delivery)
Weight: approx. 250 g
We reserve the right to make technical changes
11 Maintenance and repair
The SPI1021 is maintenance-free. Periodically test for proper functioning.
Other manuals for SPI1021
1
Table of contents
Other ZIEHL Relay manuals

ZIEHL
ZIEHL VG1200 User manual

ZIEHL
ZIEHL STW20K User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL STW1K User manual

ZIEHL
ZIEHL MS220KA User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL TR250 User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL TR1200IP User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL TR250 User manual

ZIEHL
ZIEHL STW1000V2 User manual

ZIEHL
ZIEHL TR111V User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL STW12V User manual

ZIEHL
ZIEHL FRMU1000 User manual

ZIEHL
ZIEHL UFR1001E User manual