ZIEHL UFR1001E User manual

ZI
EHL industrie elektronik
GmbH
+ Co KG
Daimlerstraße 13, D 74523 Schwäbisch Hall
+ 49 791 504-0, info
@ziehl.de, www.ziehl.de
T
emperature Relays and MINI
KA
® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers
Grid- and Plant Protection
O
pera
ting
Manual
UFR1001E
updated: 2015
-11-20 Fu
from Firmware: 0-05
UFR
1001
E
12420
-0701-08
Page 1 / 45 www.ziehl.de
-
NA-p
rotection according to
VDE-AR-N 4105, in-plant power generators on the low voltage grid
- For use in in-plant power generators on the
medium voltage grid according to BDEW
- With selectable vector shift detection
- With selectable Rate of Change of Frequency (ROCOF, df/dt) protection
New, Firmware 0-05:
Default settings for
Austria
8 8 ,
Great Britain
8 8 8 8
and
monitoring of 1 or 2 phases against N
88
(Display of the firmware version: 8 8 8 8 for
>10s)
- Archive document -

UFR1001E 12420-0701-08 Page 2 / 45 www.ziehl.de
1. Application and brief description .............................................................................................. 4
2. Summary of the functions ......................................................................................................... 4
3. Display and controls .................................................................................................................. 5
4. Detailed description ................................................................................................................... 6
4.1 Description of the connections ........................................................................................... 6
4.2 Functional characteristics .................................................................................................. 6
5. Important information ................................................................................................................ 7
6. Assembly .................................................................................................................................... 8
7. Connection diagrams ................................................................................................................. 9
7.1 1x
PV, 2x section switch (= Standard low voltage) ............................................................ 9
7.2 Multiple PV with section switch and with a series-switched NC's as feedback contacts .. 10
7.3 Multiple PV with section switch and with a parallel-switched closing contacts as feedback11
7.4 1x PV, 1x section switch with nc/normally closed contacts (medium voltage) ................. 12
7.5
Generator operation, suppression of the feedback contacts ............................................ 13
8. Commissioning......................................................................................................................... 14
8.1 Program setup ................................................................................................................. 14
8.2 Control chart ..................................................................................................................... 15
8.3 Description of the parameters .......................................................................................... 1 7
8.4 Display mode (last decimal point off) ............................................................................... 17
8.5 Menu mode (last decimal point on) .................................................................................. 18
8.6 Configuration mode (last decimal point flashes) .............................................................. 18
8.7 Test mode (only activated and connected feedback contacts) ........................................ 18
8.8 Alarm counter................................................................................................................... 18
8.9 Cumulative alarm time (display in hours) ......................................................................... 18
8.10 Alarm memory .................................................................................................................. 19
8.11 Standby counter and standby time ................................................................................... 19
8.12 Code lock ......................................................................................................................... 20
8.13 Sealing ............................................................................................................................. 20
8.14 Simulation ........................................................................................................................ 21
8.15 Possible indications in display.......................................................................................... 22
9. Default settings and firmware version, VDE-AR-N 4105
+ BDEW ........................................ 23
9.1 Default settings and firmware version, ÖVE/ÖNORM E 8001-4-712, G83/2+G59/3 .............. 25
10. Technical Data .......................................................................................................................... 27
11. Maintenance and repair ........................................................................................................... 28
12. Troubleshooting and measures .............................................................................................. 29
13. Construction form V6 ............................................................................................................... 30
14. Certificate of conformity VDE-AR-N 4105 ............................................................................... 31
15. Certificate of conformity bdew 2008 + 2013 ........................................................................... 33
16. Certificate of conformity ÖVE/ÖNORM E 8001-4-712, Pr 10 .................................................. 40
17. Certificate of conformity GB G59/3, Pr 20+21......................................................................... 41
18. Certificate of conformity GB G83/2, Pr 22+23 ........................................................................ 42

UFR1001E 12420-0701-08 Page 3 / 45 www.ziehl.de
19. Certificate of conformity DIN V VDE V 0126-1-1, GB .............................................................. 43
20. Certificate of conformity DIN V VDE V 0126-1-1, Fr ............................................................... 44
21. Adjustment values table VDE-AR-N 4105, Low Voltage Pr 1+2+7 ........................................ 45
22. Adjustment values table BDEW June 2008, acc 3.2.3.3-1,Medium Voltage Pr 3-6 .............. 45

UFR1001E 12420-0701-08 Page 4 / 45 www.ziehl.de
1. Application and brief description
The UFR1001E system-disconnection relay monitors voltage and frequency in three-phase current
networks. In complies with the conditions for centralized NA-protection according to VDE-AR-N 4105 in
in-plant power generators >30kVA, for feeding into the low voltage grid and the BDEW Directive for
feeding into the medium voltage grid. When using with generators, the evaluation of feedback contacts
for the period of a shut-down and during the synchronization can be suppressed.
The device has two channels which makes it more fail-safe. Input circuitry, evaluation and output relay
are provided in duplicate. Two processors monitor each other mutually. Feedback contacts are used to
monitor the functioning of both output relays and the section switch. During an alarm both channels shut
down, the cause is displayed and it is reported through transistor outputs.
2.
Summary of the functions
Applications include monitoring the network in generating plants such as solar and wind turbine
generator systems along with mains protection in combined heat and power plants, also with
synchronous generators (Vector surge).
The device complies with the requirements of the public utility power providers for conventional
protection in low and medium voltage systems >30 kVA.
Measurement 3 / 2 / 1 phases against N and/or phase-phase
Under and over
Monitoring the voltage quality (10 minute average value)
Vector-
Fail-safe, with monitoring of the connected section switch (can be switched off), 2 automatic restarts
on error
Passive autonomous system detection in accordance with Chapter 6.5.3 and Appendix D2
Monitoring of Rate of Change of Frequency (ROCOF, df/dt) connectible
Supports the mains synchronization when using generators
Self-test
130.0 s, individual setting for each limit
Reset time 5s at limit violation < 3s
Presetting per VDE-AR-N 4105, BDEW, ÖVE/ÖNORM E 8001-4-712, G83/2, G59/3
Alarm counter for 100 alarms (with trip value, cause and rel. time stamp)
Record of the cumulative time of alarms
Standby input with counter and time memory
Test button, simulation function, measurement of the shut-down times
LEDs for alarm signals, measurement value allocation and relay status
Sealing facility and code protection for settings, values can also be read in the sealed state
Simple commissioning and programming through 6 basic programs with preset limits
Message outputs for general alarm and for forwarding the cause of switching to the upstream
controller (transistor, max. DC 27 V, 20 mA)
Medium voltage:
Per 2x2 limits for voltage and frequency: U<<, U<, U>, U>>, F<<, F<, F>, F>>
Hysteresis, response and reset value individually adjustable
Control voltage AC/DC 24-270 V
Distributor housing V6, 6 TE 105 mm wide, front-to-back size 55 mm

UFR1001E 12420-0701-08 Page 5 / 45 www.ziehl.de
3.
Display and controls
1 Test button
Press
briefly
Output relays de-energize immediately. If Y1+Y2 are connected and the feedback
signal is activated, the tripping time is displayed until the next time a button is
pressed
2 LEDs frequenc
y
/ volt
a
g
e li
m
it v
a
lue un
d
ercut / excee
d
e
d
(red)
On,
8 8
or
88
Limit value undercut / exceeded
FLASHES,
8 8
or
8 8
Reset delay
8 8
counting down
3 LED vector sur
g
e
(VSR, red)
ON,
8 8
Threshold value for vector shift exceeded
FLASHES,
8 8
Reset delay
8 8
counting down
4 LEDs relay status
(yellow)
OFF Relay is released
ON Relay operating
5 Digital display 4-digits
(red)
Depending on program, display of current voltage, frequency, vector shift, average value
Displays the alarm signals, e.g.
8 8
,
8 8
Displays the errors with error code e.g.
8 8
6 LED Ti
m
e
(yellow)
ON A time is displayed
7 L
a
st
d
eci
m
a
l point
(red)
OFF Display mode
Illuminated Menu mode
Flashes Configuration mode
8 Set/Reset key
(in display mode, normal state)
Press briefly Display of next measured value / alarm counter
Press for > 2 s Reset, quit error messages
Press for > 4 s Displays the program, e.g.
8 8
Press for > 10 s Displays the software version, e.g.
8 8
9 Up / Down ke
y
(in display mode, normal state)
Press briefly
Change to the menu mode, display of alarm memory (Down) /
cumulative time of alarms, standby counter, standby time (Up), pushing
Press for > 2 s Display of MAX (Up) / MIN (Down) - measured values, additional pushing
10 LEDs
m
e
a
sure
m
ent
a
lloc
a
tion
(yellow)
LEDs Measured value
Lx and N ON Voltage value (L1 against N, L2 against N, L3 against N)
Lx and Ly ON Voltage value (L1 against L2, L2 against L3, L1 against L3)
Lx FLASHING quickly Vector surge (L1, L2, L3)
L1 FLASHING Frequency

UFR1001E 12420-0701-08 Page 6 / 45 www.ziehl.de
11 Sealable button + LED
Press for > 2 s Lock / Unlock
LED red Settings and simulation mode are locked,
While attempting to set, 8 8 is displayed for 3s
LED green Setting and simulation enabled
4.
Detailed description
4.1 Description of the connections
Connection Description
A1 and A2 Rated control supply voltage Us, see Technical Data
11, 12, 14; 21, 22, 24
Relay K1 and K2
E1 E2
Enable Input
Volt-free contact
8 8 8 8 , no function
8 8 8 8 , E1-E2 closed: Vector shift active but not evaluated,
monitoring of feedback contacts off for use with generator (mains
synchronization)
8 8 8 8 , E1-E2 closed: K1 and K2 off (standby), vector shift
off
8 8 8 8 , E1-E2 closed: Feedback contacts no evaluated,
vector shift off, when using with generator (mains synchronization)
Y0, Y1, Y2
Inputs, feedback contacts
Volt-free n/o or n/c contact, self-learning when switching on
Set value > turn-on time section switch under 8 8 8 8 / can
switch-off if not connected or if external devices/switches can activate
the section switch (8 8)
I1 Supply voltage for digital outputs, max. 27 V DC
Digital output over-/under voltage/-frequency, Q3 + Q4 = ROCOF
Q5 Digital output error, in Programs with >> and << additionally the 2nd
threshold value
L1, L2, L3, N Phase L1, L2, L3 and neutral conductor
4.2 Functional characteristics
Functional characteristics Explanation
VSR display value The highest measured value is always displayed. The display value is reset to 0
by deleting the max. value and when resetting into the go (good) state.
Delay Enable
On time Runs down when starting the unit and after opening the enable input; during this
time there is no evaluation of the vector shift
Reset time When a reset time 8
8 is running, it is always counted down in the display
(shortest one first)
Reset Use the Reset key or interrupt the control voltage for
> 2 s (comply with reset
delay)
Display mode 8 8
After the last measurement it switches into the scan mode; this is indicated by
the display8 8.
All measurements will now be displayed cyclically for the time set in 8 8.
MIN / MAX values
All min and max values are saved zero-voltage maintained (non-volatile).

UFR1001E 12420-0701-08 Page 7 / 45 www.ziehl.de
Tripping time
(only with feedback contacts
connected)
Connecting the feedback contacts enables measuring the shut-down time. After
a tripping time with the test button it is displayed until a button is pressed again
with a resolution of up to 1ms.
Total shut-down time = Tripping time + Response time 8 8
After a shut-down in the simulation mode the total shut-down time is displayed
until the button is pressed again)
The longer time of both channels is always displayed.
Alarm counter
The unit saves max 100 alarms (cause, measurement value, at operating time).
The LEDs indicate the cause; the tripping value that led to the alarm each
stands in the 7-segment display. Alternately the time difference, current
operating time tripping operating time is displayed. (how long ago the alarm
triggered)
Cumulative alarm time
8 8
The cumulative alarm time TAL indicates how long the relay was switched off
due to an alarm. It is recorded with a resolution of 1 minute and only when the
control voltage is applied.
Query: In the display mode button to 8 8 is displayed. 1x button =
Cumulative alarm time8 8
Standby mode
8 8 8 8
If E1-E2 are closed (e.g., by ripple control receiver, timer, dimmer), Relays K1
and K2 are switched off. The number and duration of the shut-downs is
recorded.
Query: In the display mode button to 8 8 is displayed. 2x button =
Standby counter 8 8 1x button = Standby time 8 8
Standby mode
8 8 8 8
If E1-E2 are closed, the evaluation of the feedback contacts is suppressed. That
means when using generators, a section switch can be used for mains
synchronization
.
Automatic restart attempts
If there is an error by the feedback contacts 8 8, 2 restart attempts are
automatically performed in an interval of 10s.
False triggering by undervoltage trips (e.g. during a thunderstorm) do not lead to
permanent shut-down.
5.
Important information
A marked switch and a protective device must be provided in the supply line in the
vicinity of the device (easily accessible) as a disconnecting element
(rated current ≤ 6A).
Flawless and safe operation of such a device requires proper transport and storage, professional
instillation and later commissioning along with operation as intended.
Only persons who are familiar with the installation, commissioning and operation of the device and who
are correspondingly qualified for their job are permitted to work on the device. They must comply with
the contents of the operating manual, the instructions attached to the device and the pertinent safety
regulations for the erection and operation of electrical equipment.
The devices are built and certified in accordance with EN 60255 and leave the factory in a safe and
technically flawless condition. To maintain this condition they must comply with the safety regulations
marked in the operating manual with the headline "Caution". Failure to follow the safety regulations can
lead to death, bodily injury or property damage to the device itself and to other devices and equipment.
If the information contained in the operating instructions/operating manual are not sufficient, please
contact us directly or contact your responsible agency or representative.
Instead of the industrial norms and stipulations stated in the operating manual and applicable in
Europe you must comply with the valid and applicable regulations in the country of utilisation if the
device is used outside of the area of application.
!

UFR1001E 12420-0701-08 Page 8 / 45 www.ziehl.de
WARNING
Hazards electrical voltage!
Can lead to an electric shock and burns.
Disconnect and de-energize before working on the system and the device.
6.
Assembly
The device can be mounted:
Distribution panel or control panel on 35 mm rail according to EN 60715
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air
current, the permissible ambient temperature is decreased.
Caution!
Before you apply mains voltage to the device, make sure that the permissible control
voltage
Us
on the side rating plate matches the mains voltage connected to the device!
!

UFR1001E 12420-0701-08 Page 9 / 45 www.ziehl.de
7.
Connection diagrams
7.1 1x PV, 2x section switch (= Standard low voltage)
1)
Feedback contacts not connected set
8 8
8 8 8 8
2)
N connected set
8 8
,
8 8
or
8 8
3)
Nc- or no-contacts can be connected, automatic detection when switching on
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control
receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8 8 8 8
) suppresses feedback contacts (
8 8 8 8
) or switches device into
standby (
8 8 8 8
= default setting) e.g. through ripple control receiver or timer
7)
1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 20)

UFR1001E 12420-0701-08 Page 10 / 45 www.ziehl.de
7.2 Multiple PV with section switch and with a series-switched NC's as feedback contacts
(expanded inventory plant)
1)
Contactor feedback contacts not connected set
8 8
8 8 8 8
2)
N connected set
8 8
,
8 8
or
8 8
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control
receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8 8 8 8
) suppresses feedback contacts (
8 8 8 8
) or switches device into
standby (
8 8 8 8
= default setting) e.g. through ripple control receiver or timer
7)
1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 20)

UFR1001E 12420-0701-08 Page 11 / 45 www.ziehl.de
7.3 Multiple PV with section switch and with a parallel-switched closing contacts as feedback
(expanded inventory plant)
1)
Feedback contacts not connected set
8 8
8 8 8 8
2)
N connected set
8 8
,r
8 8
or
8 8
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control
receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8 8 8 8
) suppresses feedback contacts (
8 8 8 8
) or switches device into
standby (
8 8 8 8
= default setting) e.g. through ripple control receiver or timer
7)
1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 20)

UFR1001E 12420-0701-08 Page 12 / 45 www.ziehl.de
7.4 1x PV, 1x section switch with nc/normally closed contacts (medium voltage)
1)
Feedback contacts not connected set
8 8
8 8 8 8
2)
N connected set
8 8
,
8 8
or
8 8
3)
Nc- or no-contacts can be connected, automatic detection when switching on
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control
receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8 8 8 8
) suppresses feedback contacts (
8 8 8 8
) or switches device into
standby (
8 8 8 8
= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-08 Page 13 / 45 www.ziehl.de
7.5 Generator operation, suppression of the feedback contacts
(with external shut-down and mains synchronization)
1)
Feedback contacts not connected set
8 8
8 8 8 8
2)
N connected set
8 8
,
8 8
or
8 8
3)
Nc- or no-contacts can be connected, automatic detection when switching on
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control
receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8 8 8 8
) suppresses feedback contacts (
8 8 8 8
) or switches device into
standby (
8 8 8 8
= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-08 Page 14 / 45 www.ziehl.de
8.
Commissioning
8.1 Program setup
The suitable program must be set on the UFR1001E in accordance with the application. If the
UFR1001E is sealed/locked (red LED illuminated), the sealing has to be deactivated first.
Pr Connection Treshol
d
V
a
lues
V
olt
a
g
e Countr
y
/ St
a
n
d
a
r
d
*1 3 AC with N Low voltage
1x over voltage, 1x under voltage
1x over frequency, 1x under frequency
10 min average value, 1x vector shift
1x ROCOF
230V
VDE-AR-N 4105
2 3 AC without N 400V
7 2/1 AC with N 230V
3 3 AC with N Medium voltage
2x over voltage, 2x under voltage
2x over frequency, 2x under frequency
10min mean value, 1x vector shift
1x ROCOF
57,7V
BDEW Juni 2008
nach 3.2.3.3-1
4 3 AC without N 100V
5 3/2/1 AC with
N 230V
6 3 AC without N 400V
10 3/2/1 AC
with N
1x overvoltage, 1x under voltage
1x over frequency, 1x under frequency
10 min average value, 1x vector shift
1x ROCOF
230V
ÖVE/ÖNORM
E 8001-4-712
20 3/2/1 AC
with N
2x over voltage, 2x under voltage
2x over frequency, 2x under frequency
10min mean value, 1x vector shift
1x ROCOF
230V
G83/2 + G59/3
21 3 AC without N 400V
22 3 AC with N 57,7V
23 3 AC without N 100V
* default setting
Adjustment process:
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the key cover and turn 180°
Actuate the small blue button by firmly pressing the button cover (LED starts flashing) until
the green LED is illuminated.
Sealing is deactivated
Press button 1x display 8 8
Press button 5x display 8 8
Set the program with the buttons
Press button 1x display 8 8
Press button 1x display 8 8
Press button
Device resets and starts with the newly selected program
Hint:
Only change the parameters after having selected the correct
program.

UFR1001E 12420-0701-08 Page 15 / 45 www.ziehl.de
8.2 Control chart
P
r Co
n
n
ectio
n
Cou
n
tr
y
/
Standard
1 3 AC
+ N
VDE-AR-N
4105
2 3 AC
7 2/1 AC + N
10 3/2/1 AC
+ N
ÖVE/
ÖNORM
E 8001-4-712
[ ]
=
Unit
Up/Down simultaneously sets the
value to the lowest value.
Code-Reset =
2
s
Set when mains
are switched on. (Pin = 504)
Error messages:
= Tolerance Master Slave
= Internal control
= Communication
= Contactor feedback
contacts K1/K2
= Limit error
= Parameter error
D
isplay
mode
C
o
nfi
g
urati
o
n m
o
de
M
enu mode
1) 3AC+N = 300V

UFR1001E 12420-0701-08 Page 16 / 45 www.ziehl.de
Pr Co
n
n
ectio
n
Cou
n
tr
y
/
Standard
3 3 AC + N
BDEW
Juni 2008
nach
3.2.3.3-1
4 3 AC
5 3/2/1 AC +
N
6 3 AC
20 3/2/1 AC +
N
G83/2 +
G59/3
21 3 AC
22 3 AC + N
23 3 AC
[ ] = Unit
Up/Down simultaneously sets
the value to the lowest value
.
Code-Reset =
2 s
Set when
mains are switched on. (Pin =
504)
Error messages:
= Tolerance Master
Slave
= Internal control
= Communication
= Contactor feedback
contacts K1/K2
= Limit error
= Parameter error
1) 3AC+N = 300V
Dis
p
la
y
mode
C
onfiguration mode
Menu mode

UFR1001E 12420-0701-08 Page 17 / 45 www.ziehl.de
8.3 Description of the parameters
Parameters
Display Explanation Adjustment range
Limit value
8 8
8 8
8 8
88
8 8
Voltage limit value
8 8 … 8 8
8 8 … 8 8
Limit value
,
8 8
,
8 8
,
8 8
Frequency limit value 8 8 … 8 8
Limit value
8 8 ROCOF, df/dt limit value 8 8… 8 8
Hysteresis
8 8
253V (Limit) 3V (Hysteresis) =
250V (Reset value)
If the limit value is offset at 8 8, the
hysteresis also has to be adapted so that
the reset point lies at 50.05 Hz again.
8 8 … 8 8
8 8 … 8 8
Response
time
(delay
Alarm)
8 8 An alarm is suppressed for the set time
(seconds) 8 8 … 8 8
Turn-on time
(delay Off)
8 8
Reset is delayed for the set time, also
during voltage recovery, this time
(seconds) is always counted down in the
display
8 8 … 8 8
Enable time
(delay On)
8 8
There is no evaluation of the vector shift
during this time; starts with the application
of the control voltage and when opening
the Enable input
8 8 … 8 8
VSR
8 8
8 8: a vector surge on one phase
leads to an alarm
8 8: a vector surge on all phases
simultaneously leads to an alarm
8 8 … 8 8
Periods
8 8
Measuring time ROCOF, (4=sensitive,
50=insensitive)
Response time=
8 8 * Period duration + 8 8
8 8 … 8 8
delay
Display
8 8 Interval during which the display is
updated in the display mode, 8 8 … 8 8
8.4 Display mode (last decimal point off)
In the display mode, the UFR1001E is in its normal state; here, depending on the program, the actual
voltage, the highest actual 10 minute mean value, the frequency or the vector surge is displayed. In
addition, the alarm signals (e.g. 8
8 , 8 8 ) and error codes (e.g. 8 8 ) are displayed.
Function button
Set / Reset
Press briefly: Switches the measurement, alarm counter
Press for > 2 s: Resets after locked alarm
(not possible if doF Reset delay is counting down)
Press for > 4 s: Displays the program, e.g. 8 8
Press for > 10 s: Displays the software version, e.g. 8 8
Function key Press briefly: Change into the menu mode,

UFR1001E 12420-0701-08 Page 18 / 45 www.ziehl.de
Up / Down Display alarm counter: Down = Query the memory
Up = Query the cumulative alarm time
Displays MAX and MIN measurements, additionally
values
8.5 Menu mode (last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically
returns to the display mode.
Function button
Set / Reset
Press briefly: Change into the configuration mode
Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down Press briefly: Select menu item; changes into the display mode
8.6 Configuration mode (last decimal point flashes)
In the configuration mode you can set the value of a parameter. The display alternates between the
parameter relation and the currently set value until one of the Up/Down buttons is pressed, which
changes the value of the parameter. If no key is pressed for 2 s the display starts alternating again.
If no key is pressed for 30 s (simulation mode 15 min) one automatically returns to the display mode (the
most recently set value is applied during this)
Function button
Set / Reset
Press briefly: The settings are taken over; continue to next parameter.
Changes into menu mode after the last parameter
Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down Press briefly/long: Value change of the parameter (slow/fast)
Hint: Simultaneously pressing the Up and Down keys resets the adjustable value to zero. If the Up or
Down button is kept pressed while setting the value the change in the display is accelerated.
8.7 Test mode (only activated and connected feedback contacts)
If feedback contacts of the section switch are connected to the UFR1001E and activated (value > set
turn-on time of section switch, e.g. 5.0s), the trip circuit can be tested by pressing the Test button. To do
that, the measurement voltage has to be connected and no alarm is allowed to be present!
After pressing the Test button the UFR1001E triggers. The tripping time of the internal relay + section
switch are measured through the feedback contacts. After successful tripping, the tripping time of the
slower switch remains shown in the display until any key is pressed.
8.8 Alarm counter
The alarm counter 8 8 is increased by 1 with every shut-down. Up to 100 shut-downs are counted.
That allows quick detection of how often the UFR1001E has shut down since the last delete of the alarm
counter (see cumulative alarm time).
Query the alarm counter:
Change into the display mode
Press the button several times until display 8xx8
8.9 Cumulative alarm time
(display in hours)
The cumulative alarm time 8 8 indicates how long the relay was switched off due to an alarm. It is
recorded with a resolution of 1 minute and only when the control voltage is applied.
Query the cumulative alarm time:
Change into the display mode

UFR1001E 12420-0701-08 Page 19 / 45 www.ziehl.de
Press the button several times until display 8xx8
Press the button 1x display 8 8 8xxx8
Delete the alarm counter and cumulative alarm time (only together):
Display alarm counter8xx8
Press the button 1x display 8 8 8xxx8
Keep the button pressed for 2s until display 8 8 8 8
8.10 Alarm memory
Independent of the alarm counter, the UFR1001E stores the most recent 100 shut-down causes (cause,
measurement value, at operating time). Simulated alarms are also registered. The LEDs indicate the
cause; the tripping value that led to the alarm each stands in the 7-segment display. Alternative to that
the time is shown in hours which have passed since the last tripping (with applied control voltage).
These values remain saved even after the power has been turned off.
Query alarm memory:
Change into the display mode
Press the button several times display 8xx8
Press the button 1x display 8 xxx8 8xxx8
(tripping value or error no. / time that has passed in hours)
P
ress the button 1x,
g
o to next alarm
The alarm memory is only deleted during a program change.
8.11 Standby counter and standby time
The standby counter 8 8, is increased by 1 with every standby shut-down. Up to 9999 shut-downs
are counted. That lets the UFR1001E quickly detect how often, e.g., shut-down was performed through a
ripple control receiver.
Query the standby counter:
Change into the display mode
Press the button several times until display 8xx8
Press the button 2x display 8 8 8xxxx8
The standby time 8 8 indicates how long the relay was switched off by the standby mode. It is
recorded with a resolution of 1 minute and only when the control voltage is applied and if no alarm is
present.
Query the standby time:
Change into the display mode
Press the button several times until display 8xx8
Press the button 3x display 8 8 8xxx8 (Time LED is illuminated)
Delete the standby counter and standby time (only together):
Display alarm counter8xx8
Press the button 2x display 8 8 8xxxx8
Keep the button pressed for 2s until display 8 8 8 8

UFR1001E 12420-0701-08 Page 20 / 45 www.ziehl.de
8.12 Code lock
You can protect the set parameters by enabling the code lock here.
The device acknowledges an incorrect entry with 8 8 (flashes three times).
Adjustment process:
Select the menu item with the buttons until display 8 8
Press the button 1x display 8 8 8 8
Set the
saved
pin code with the buttons (
default setting is
8 8 )
Press the button 1x display 8 8 8 8
Use the buttons to set the desired code lock:
o
8 8 off, all parameters can be changed
o
8 8 on, no parameters can be changed
Press the button 1x display 8 8 8 8
Use the buttons to set the new, desired pin code
(
caution: write down the pin code
)
Press the button 1x
Code lock on, display 8 8 flashes three times
Code loc
k
off, dis
p
la
y
8 8 flashes three times
Return to menu mode, menu item code lock
If there are any problems with the code lock (pin forgotten), the lock can be switched off and the pin can
be reset to 504 by keeping the Set key pressed while switching on the mains until 8 8 8 8
appears in the display.
8.13 Sealing
All the settings and the simulation mode can be locked.
If the LED is illuminated, the UFR1001E is locked.
If an attempt is made to change a setting in the locked state, for 3s the display shows 8 8.
Adjustment procedure Sealing/Lock ON (OFF):
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the key cover and turn 180°
Actuate the small blue button by pressing the button cover very firmly (LED starts
flashing) until the green LED is illuminated.
Other manuals for UFR1001E
5
Table of contents
Other ZIEHL Relay manuals

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL FRMU1000 User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL STW1000V2 User manual

ZIEHL
ZIEHL SPI1021 User manual

ZIEHL
ZIEHL TR250 User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL TR600 User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL COSFI100V User manual

ZIEHL
ZIEHL MS220Vi User manual

ZIEHL
ZIEHL STW12V User manual

ZIEHL
ZIEHL EFR4001IP User manual

ZIEHL
ZIEHL TR111V User manual

ZIEHL
ZIEHL TR1200IP User manual

ZIEHL
ZIEHL SW32V User manual

ZIEHL
ZIEHL MSF 220 SE User manual

ZIEHL
ZIEHL VG1200 User manual