ZIEHL UFR1001E User manual

ZIEHL industrie –elektronik GmbH + Co KG
Daimlerstraße 13, D –74523 Schwäbisch Hall
+ 49 791 504-0, [email protected], www.ziehl.de
Temperature Relays and MINIKA®, Mains Monitoring, Digital Panelmeters MINIPAN®, Switching Relays and Controls
Operating Instructions UFR1001E
updated: 131014 Fz/Ba
from Firmware: 0-04
UFR1001E 12420-0701-03 Page
1
/ 36 www.ziehl.de
- NA-protection according to VDE-AR-N 4105, in-plant power generators on the low voltage grid
- For use in in-plant power generators on the medium voltage grid according to BDEW
- With selectable vector shift detection
- With selectable Rate of Change of Frequency (ROCOF, df/dt) protection
New, Firmware 0-04:
ROCOF (df/dt) protection
Display of the firmware version: 8Info88fnr 8or press “Set” for >10s

UFR1001E 12420-0701-03 Page
2
/ 36 www.ziehl.de
Table of contents
1. Application and brief description........................................................................................................... 3
2. Summary of the functions ..................................................................................................................... 3
3. Display and controls .............................................................................................................................. 4
4. Detailed description ............................................................................................................................... 5
4.1 Description of the connections ......................................................................................................5
4.2 Functional characteristics..............................................................................................................5
5. Important information ............................................................................................................................ 6
6. Assembly ................................................................................................................................................ 7
7. Connection diagrams............................................................................................................................. 8
7.1 1x PV, 2x section switch (= Standard low voltage) ........................................................................8
7.2 Multiple PV with section switch and with a series-switched NC's as feedback contacts (expanded
inventory plant)..............................................................................................................................9
7.3 Multiple PV with section switch and with a parallel-switched closing contacts as feedback
contacts (expanded inventory plant)............................................................................................10
7.4 1x PV, 1x section switch with nc/normally closed contacts (medium voltage)..............................11
7.5 Generator operation, suppression of the feedback contacts (with external shut-down and mains
synchronization)..........................................................................................................................12
8. Commissioning..................................................................................................................................... 13
8.1 Program setup.............................................................................................................................13
8.2 Control chart.................................................................................................................................14
8.3 Description of the parameters.......................................................................................................16
8.4 Display mode (last decimal point off)...........................................................................................16
8.5 Menu mode (last decimal point on).................................................................................................17
8.6 Configuration mode (last decimal point flashes)..........................................................................17
8.7 Test mode (only activated and connected feedback contacts).....................................................17
8.8 Alarm counter..............................................................................................................................17
8.9 Cumulative alarm time (display in hours).....................................................................................17
8.10 Alarm memory.............................................................................................................................18
8.11 Standby counter and standby time..............................................................................................18
8.12 Code lock.....................................................................................................................................19
8.13 Sealing........................................................................................................................................19
8.14 Simulation...................................................................................................................................20
8.15 Possible indications in display.....................................................................................................21
9. Default settings and firmware version................................................................................................ 22
10. Technical Data...................................................................................................................................... 24
11. Maintenance and repair........................................................................................................................ 25
12. Troubleshooting and measures .......................................................................................................... 26
13. Construction form V6.......................................................................................................................... 27
14. Verification of conformity..................................................................................................................... 28
15. Unbedenklichkeitsbescheinigung ÖVE/ÖNORM E 8001-4-712........................................................... 34
16. Guidance value changes according to ÖVE/ÖNORM E 8001-4-712 .................................................. 35
17. Adjustment values table VDE-AR-N 4105, Low Voltage Pr 1+2.......................................................... 36
18. Adjustment values table BDEW June 2008, acc 3.2.3.3-1, Medium Voltage Pr 3-6........................... 36

UFR1001E 12420-0701-03 Page
3
/ 36 www.ziehl.de
1. Application and brief description
The UFR1001E system-disconnection relay monitors voltage and frequency in three-phase current
networks. In complies with the conditions for centralized NA-protection according to VDE-AR-N 4105 in in-
plant power generators >30kVA, for feeding into the low voltage grid and the BDEW Directive for feeding
into the medium voltage grid. When using with generators, the evaluation of feedback contacts for the period
of a shut-down and during the synchronization can be suppressed.
The device has two channels which makes it more fail-safe. Input circuitry, evaluation and output relay are
provided in duplicate. Two processors monitor each other mutually. Feedback contacts are used to monitor
the functioning of both output relays and the section switch. During an alarm both channels shut down, the
cause is displayed and it is reported through transistor outputs.
2. Summary of the functions
Applications include monitoring the network in generating plants such as solar and wind turbine generator
systems along with mains protection in combined heat and power plants, also with synchronous generators
(Vector surge).
The device complies with the requirements of the public utility power providers for conventional protection in
low and medium voltage systems >30 kVA.
Under and overvoltage monitoring 40…520 V
Measurement against N and/or phase-phase
Under and overfrequency monitoring 45…65 Hz
Monitoring the voltage quality (10 minute average value)
Vector-surge monitoring 2…20° connectible
Fail-safe, with monitoring of the connected section switch (can be switched off), 2 automatic restarts on
error
Passive autonomous system detection in accordance with Chapter 6.5.3 and Appendix D2
Monitoring of Rate of Change of Frequency (ROCOF, df/dt) connectible
Supports the mains synchronization when using generators
Self-test
Response time adjustable 0.05 … 130.0 s, individual setting for each limit
Reset time adjustable 0 … 999 s, individual setting for each limit
Reset time 5s at limit violation < 3s
Presetting per VDE-AR-N 4105
Alarm counter for 100 alarms (with trip value, cause and rel. time stamp)
Record of the cumulative time of alarms
Standby input with counter and time memory
Test button, simulation function, measurement of the shut-down times
LEDs for alarm signals, measurement value allocation and relay status
Sealing facility and code protection for settings, values can also be read in the sealed state
Simple commissioning and programming through 6 basic programs with preset limits
Message outputs for general alarm and for forwarding the cause of switching to the upstream controller
(transistor, max. DC 27 V, 20 mA)
Medium voltage:
Per 2x2 limits for voltage and frequency: U<<, U<, U>, U>>, F<<, F<, F>, F>>
Hysteresis, response and reset value individually adjustable
Control voltage AC/DC 24-270 V
Distributor housing V6, 6 TE 105 mm wide, front-to-back size 55 mm

UFR1001E 12420-0701-03 Page
4
/ 36 www.ziehl.de
3. Display and controls
1
Test button
Press
briefly
Output relays de-energize immediately. If Y1+Y2 are connected and the feedback signal
is activated, the tripping time is displayed until the next time a button is pressed
2
LEDs frequency / voltage limit value undercut / exceeded (red)
On, 8AL 8or 8AL M8
Limit value undercut / exceeded
FLASHES, 8AL 8or 8AL M8
Reset delay 8dof 8counting down
3
LED vector surge (VSR, red)
ON, 8AL 8
Threshold value for vector shift exceeded
FLASHES, 8AL8
Reset delay 8dof 8counting down
4
LEDs relay status (yellow)
OFF
Relay is released
ON
Relay operating
5
Digital display 4-digits (red)
Depending on program, display of current voltage, frequency, vector shift, average value
Displays the alarm signals, e.g. 8AL 8, 8aL M8
Displays the errors with error code e.g. 8Err98
6
LED Time (yellow)
ON
A time is displayed
7
Last decimal point (red)
OFF
Display mode
Illuminated
Menu mode
Flashes
Configuration mode
8
Set/Reset key (in display mode, normal state)
Press briefly
Display of next measured value / alarm counter
Press for > 2 s
Reset, quit error messages
Press for > 4 s
Displays the program, e.g. 8Pr 18
Press for > 10 s
Displays the software version, e.g. 80-048
9
Up / Down key (in display mode, normal state)
Press briefly
Change to the menu mode, display of alarm memory (Down) / cumulative time
of alarms, standby counter, standby time (Up), pushing Set button for ≥ 2 s
resets the stored values
Press for > 2 s
Display of MAX (Up) / MIN (Down) - measured values, additional pushing of Set
button for ≥ 2 s deletes the stored values
10
LEDs measurement allocation (yellow)
LEDs
Measured value
Lx and N ON
Voltage value (L1 against N, L2 against N, L3 against N)
Lx and Ly ON
Voltage value (L1 against L2, L2 against L3, L1 against L3)
Lx FLASHING quickly
Vector surge (L1, L2, L3)
L1 FLASHING
Frequency

UFR1001E 12420-0701-03 Page
5
/ 36 www.ziehl.de
11
Sealable button + LED
Press for > 2 s
Lock / Unlock
LED red
Settings and simulation mode are locked,
While attempting to set, 8LOc 8is displayed for 3s
LED green
Setting and simulation enabled
4. Detailed description
4.1 Description of the connections
Connection Description
A1 and A2
Rated control supply voltage Us, see Technical Data
11, 12, 14; 21, 22, 24
Relay K1 and K2
E1 –E2
Enable –Input
Volt-free contact
8vsr .88 off.8, no function
8vsr .88 on.8, E1-E2 closed: Vector shift active but not evaluated,
monitoring of feedback contacts off for use with generator (mains
synchronization)
8vsr .88stby.8, E1-E2 closed: K1 and K2 off (standby), vector shift off
8vsr .88Y1Y2.8, E1-E2 closed: Feedback contacts no evaluated, vector
shift off, when using with generator (mains synchronization)
Y0, Y1, Y2
Inputs, feedback contacts
Volt-free n/o or n/c contact, self-learning when switching on
Set value > turn-on time section switch under 8rel .88trel.8/ can
switch-off if not connected or if external devices/switches can activate the
section switch (8off .8)
I1
Supply voltage for digital outputs, max. 27 V DC
Q1…Q4
Digital output over-/undervoltage/-frequency, Q3 + Q4 = ROCOF
Q5
Digital output error, in Program 3-6 additionally the 2nd threshold value
L1, L2, L3, N
Phase L1, L2, L3 and neutral conductor
4.2 Functional characteristics
Functional characteristics
Explanation
VSR display value
The highest measured value is always displayed. The display value is reset
to 0 by deleting the max. value and when resetting into the go (good) state.
Delay Enable On time
Runs down when starting the unit and after opening the enable input; during
this time there is no evaluation of the vector shift
Reset time
When a reset time 8dof 8is running, it is always counted down in the
display (shortest one first)
Reset
Use the Reset key or interrupt the control voltage for > 2 s (comply with reset
delay)
Display mode 8Scn8
After the last measurement it switches into the scan mode; this is indicated
by the display8scn 8.
All measurements will now be displayed cyclically for the time set in 8dit8.
MIN / MAX values
All min and max values are saved zero-voltage maintained (non-volatile).
Tripping time
(only with feedback
contacts connected)
Connecting the feedback contacts enables measuring the shut-down time.
After a tripping time with the test button it is displayed until a button is
pressed again with a resolution of up to 1ms.
Total shut-down time = Tripping time + Response time 8 dal.8

UFR1001E 12420-0701-03 Page
6
/ 36 www.ziehl.de
After a shut-down in the simulation mode the total shut-down time is
displayed until the button is pressed again)
The longer time of both channels is always displayed.
Alarm counter
The unit saves max 100 alarms (cause, measurement value, at operating
time). The LEDs indicate the cause; the tripping value that led to the alarm
each stands in the 7-segment display. Alternately the time difference, current
operating time –tripping operating time is displayed. (how long ago the
alarm triggered)
Cumulative alarm time
8tal .8
The cumulative alarm time TAL indicates how long the relay was switched
off due to an alarm. It is recorded with a resolution of 1 minute and only
when the control voltage is applied.
Query: In the display mode button to 8ac .8is displayed. 1x button =
Cumulative alarm time8tal .8
Standby mode
8vsr .88stby.8
If E1-E2 are closed (e.g., by ripple control receiver, timer, dimmer), Relays
K1 and K2 are switched off. The number and duration of the shut-downs is
recorded.
Query: In the display mode button to 8ac .8is displayed. 2x button =
Standby counter 8stby.81x button = Standby time 8stby.8
Standby mode
8vsr .88y1y2.8
If E1-E2 are closed, the evaluation of the feedback contacts is suppressed.
That means when using generators, a section switch can be used for mains
synchronization.
Automatic restart attempts
If there is an error by the feedback contacts 8err78, 2 restart attempts are
automatically performed in an interval of 10s.
False triggering by undervoltage trips (e.g. during a thunderstorm) do not
lead to permanent shut-down.
5. Important information
A marked switch and a protective device must be provided in the supply line in the
vicinity of the device (easily accessible) as a disconnecting element
(rated current ≤ 6A).
Flawless and safe operation of such a device requires proper transport and storage, professional
instillation and later commissioning along with operation as intended.
Only persons who are familiar with the installation, commissioning and operation of the device and who
are correspondingly qualified for their job are permitted to work on the device. They must comply with the
contents of the operating manual, the instructions attached to the device and the pertinent safety
regulations for the erection and operation of electrical equipment.
The devices are built and certified in accordance with EN 60255 and leave the factory in a safe and
technically flawless condition. To maintain this condition they must comply with the safety regulations
marked in the operating manual with the headline "Caution". Failure to follow the safety regulations can
lead to death, bodily injury or property damage to the device itself and to other devices and equipment.
If the information contained in the operating instructions/operating manual are not sufficient,
please contact us directly or contact your responsible agency or representative.
Instead of the industrial norms and stipulations stated in the operating manual and applicable in Europe
you must comply with the valid and applicable regulations in the country of utilisation if the device is used
outside of the area of application.
WARNING
Hazards electrical voltage!
Can lead to an electric shock and burns.
Disconnect and de-energize before working on the system and the device.
!

UFR1001E 12420-0701-03 Page
7
/ 36 www.ziehl.de
6. Assembly
The device can be mounted:
Distribution panel or control panel on 35 mm rail according to EN 60715
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air
current, the permissible ambient temperature is decreased.
Caution!
Before you apply mains voltage to the device, make sure that the permissible control
voltage Us on the side rating plate matches the mains voltage connected to the device!
!

UFR1001E 12420-0701-03 Page
8
/ 36 www.ziehl.de
7. Connection diagrams
7.1 1x PV, 2x section switch (= Standard low voltage)
1) Feedback contacts not connected set 8rel .88trel.88off.8
2) N connected set 8Pr 18, 8Pr 38or 8Pr 58
3) Nc- or no-contacts can be connected, automatic detection when switching on
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 3x16A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .88on.8) suppresses feedback contacts (8vsr .88y1y2.8) or switches device into
standby (8vsr .88stby.8= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-03 Page
9
/ 36 www.ziehl.de
7.2 Multiple PV with section switch and with a series-switched NC's as feedback contacts
(expanded inventory plant)
1) Contactor feedback contacts not connected set 8rel .88trel.88off.8
2) N connected set 8Pr 18, 8Pr 38or 8Pr 58
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 3x16A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .88on.8) suppresses feedback contacts (8vsr .88y1y2.8) or switches device into
standby (8vsr .88stby.8= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-03 Page
10
/ 36 www.ziehl.de
7.3 Multiple PV with section switch and with a parallel-switched closing contacts as feedback
contacts (expanded inventory plant)
1) Feedback contacts not connected set 8rel .88trel.88off.8
2) N connected set 8Pr 18,r 8Pr 38or 8Pr 58
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 3x16A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .88on.8) suppresses feedback contacts (8vsr .88y1y2.8) or switches device into
standby (8vsr .88stby.8= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-03 Page
11
/ 36 www.ziehl.de
7.4 1x PV, 1x section switch with nc/normally closed contacts (medium voltage)
1) Feedback contacts not connected set 8rel .88trel.88off.8
2) N connected set 8Pr 18, 8Pr 38or 8Pr 58
3) Nc- or no-contacts can be connected, automatic detection when switching on
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 3x16A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .88on.8) suppresses feedback contacts (8vsr .88y1y2.8) or switches device into
standby (8vsr .88stby.8= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-03 Page
12
/ 36 www.ziehl.de
7.5 Generator operation, suppression of the feedback contacts (with external shut-down and
mains synchronization)
1) Feedback contacts not connected set 8rel .88trel.88off.8
2) N connected set 8Pr 18, 8Pr 38or 8Pr 58
3) Nc- or no-contacts can be connected, automatic detection when switching on
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 3x16A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .88on.8) suppresses feedback contacts (8vsr .88y1y2.8) or switches device into
standby (8vsr .88stby.8= default setting) e.g. through ripple control receiver or timer

UFR1001E 12420-0701-03 Page
13
/ 36 www.ziehl.de
8. Commissioning
8.1 Program setup
The suitable program must be set on the UFR1001E in accordance with the application. If the UFR1001E is
sealed/locked (red LED illuminated), the sealing has to be deactivated first.
Pr
Connection
Threshold values
Voltage
*1
3 AC with N
Low voltage
1x overvoltage, 1x undervoltage
1x overfrequency, 1x underfrequency
10 min average value, 1x vector shift
1x ROCOF
230 V
2
3 AC without N
400 V
3
3 AC with N
Medium voltage
2x overvoltage, 2x undervoltage
2x overfrequency, 2x underfrequency
10min mean value, 1x vector shift
1x ROCOF
57.7 V
4
3 AC without N
100 V
5
3 AC with N
230 V
6
3 AC without N
400 V
* default setting
Adjustment process:
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the key cover and turn 180°
Actuate the small blue button by firmly pressing the button cover (LED starts flashing) until the
green LED is illuminated.
Sealing is deactivated
Press button 1x display 8Info.8
Press button 5x display 8Pr 1.8
Set the program with the buttons
Press button 1x display 8no.8
Press button 1x display 8yes.8
Press button
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to “default settings“ (see
table „Default settings“). Only change the parameters after having selected the correct program.

UFR1001E 12420-0701-03 Page
14
/ 36 www.ziehl.de
8.2 Control chart
8Pr 183AC with N, acc. VDE-AR-N 4105 8Pr 283AC without N, acc. VDE-AR-N 4105
[ ] = Unit
Up/Down simultaneously sets the
value to the lowest value.
Code-Reset = 2 s Set when mains
are switched on. (Pin = 504)
Error messages:
Err4 = Tolerance Master Slave
Err5 = Internal control
Err6 = Communication
Err7 = Contactor feedback
contacts K1/K2
Err8 = Limit error
Err9 = Parameter error
Display mode
Configuration mode
Menu mode
1) 3AC+N = 300V

UFR1001E 12420-0701-03 Page
15
/ 36 www.ziehl.de
8Pr 38, 8Pr 583AC with N, medium voltage 8Pr 48, 8Pr 683AC without N, medium voltage
[ ] = Unit
Up/Down simultaneously sets
the value to the lowest value.
Code-Reset = 2 s Set when
mains are switched on. (Pin =
504)
Error messages:
Err4 = Tolerance Master
Slave
Err5 = Internal control
Err6 = Communication
Err7 = Contactor feedback
contacts K1/K2
Err8 = Limit error
Err9 = Parameter error
1) 3AC+N = 300V
Display mode
Configuration mode
Menu mode

UFR1001E 12420-0701-03 Page
16
/ 36 www.ziehl.de
8.3 Description of the parameters
Parameters
Display
Explanation
Adjustment range
Limit value
8U,, 8
8U, 8
8u_ 8
8U__ 8
8Um 8
Voltage limit value
815.08… 83008
815.08… 85208
Limit value
F,, ,
8F, 8,
8F_ 8,
8F__ 8
Frequency limit value
845.008… 865.008
Limit value
8dfdt8
ROCOF, df/dt limit value
8 0.108… 85.008
Hysteresis
8H 8
253V (Limit) –3V (Hysteresis) =
250V (Reset value)
If the limit value is offset at 8F, 8, the
hysteresis also has to be adapted so that the
reset point lies at 50.05 Hz again.
81.08… 899.08
80.058… 810.008
Response
time
(delay Alarm)
8dAL 8
An alarm is suppressed for the set time
(seconds)
80.058… 8130.08
Turn-on time
(delay Off)
8dOF 8
Reset is delayed for the set time, also during
voltage recovery, this time (seconds) is always
counted down in the display
808… 8 9998
Enable time
(delay On)
8dEon8
There is no evaluation of the vector shift during
this time; starts with the application of the
control voltage and when opening the Enable
input
828… 8208
VSR
8VSR8
81 Ph8: a vector surge on one phase leads to
an alarm
83 Ph8: a vector surge on all phases
simultaneously leads to an alarm
81 Ph8… 83 Ph8
Periods
8per 8
Measuring time ROCOF, (4=sensitive,
50=insensitive)
Response time=
8per 8* Period duration + 8dal 8
848… 8508
delay Display
8ddi 8
Interval during which the display is updated in
the display mode,
80.18… 82.08
8.4 Display mode (last decimal point off)
In the display mode, the UFR1001E is in its normal state; here, depending on the program, the actual
voltage, the highest actual 10 minute mean value, the frequency or the vector surge is displayed. In addition,
the alarm signals (e.g. 8aL 8, 8aL m8) and error codes (e.g. 8err98) are displayed.
Function button
Set / Reset
Press briefly: Switches the measurement, alarm counter
Press for > 2 s: Resets after locked alarm
(not possible if doF Reset delay is counting down)
Press for > 4 s: Displays the program, e.g. 8Pr 18
Press for > 10 s: Displays the software version, e.g. 80-048
Function key
Up / Down
Press briefly: Change into the menu mode,
Display alarm counter: Down = Query the memory
Up = Query the cumulative alarm time
Press for ≥ 2 s: Displays MAX and MIN measurements, additionally
pressing the Set key for ≥ 2 s deletes the saved
values

UFR1001E 12420-0701-03 Page
17
/ 36 www.ziehl.de
8.5 Menu mode (last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically returns to
the display mode.
Function button
Set / Reset
Press briefly: Change into the configuration mode
Press for ≥ 2 s: Returns to the display mode (the most recently set values
are then applied)
Function key
Up / Down
Press briefly: Select menu item; changes into the display mode
8.6 Configuration mode (last decimal point flashes)
In the configuration mode you can set the value of a parameter. The display alternates between the
parameter relation and the currently set value until one of the Up/Down buttons is pressed, which changes
the value of the parameter. If no key is pressed for 2 s the display starts alternating again.
If no key is pressed for 30 s (simulation mode 15 min) one automatically returns to the display mode (the
most recently set value is applied during this)
Function button
Set / Reset
Press briefly: The settings are taken over; continue to next parameter.
Changes into menu mode after the last parameter
Press for ≥ 2 s: Returns to the display mode (the most recently set values are
then applied)
Function key
Up / Down
Press briefly/long: Value change of the parameter (slow/fast)
Hint: Simultaneously pressing the Up and Down keys resets the adjustable value to zero. If the Up or Down
button is kept pressed while setting the value the change in the display is accelerated.
8.7 Test mode (only activated and connected feedback contacts)
If feedback contacts of the section switch are connected to the UFR1001E and activated (value > set turn-
on time of section switch, e.g. 5.0s), the trip circuit can be tested by pressing the Test button. To do that, the
measurement voltage has to be connected and no alarm is allowed to be present!
After pressing the Test button the UFR1001E triggers. The tripping time of the internal relay + section switch
are measured through the feedback contacts. After successful tripping, the tripping time of the slower switch
remains shown in the display until any key is pressed.
8.8 Alarm counter
The alarm counter 8ac 8is increased by 1 with every shut-down. Up to 100 shut-downs are counted. That
allows quick detection of how often the UFR1001E has shut down since the last delete of the alarm counter
(see cumulative alarm time).
Query the alarm counter:
Change into the display mode
Press the button several times until display 8acxx8
8.9 Cumulative alarm time (display in hours)
The cumulative alarm time 8tal 8indicates how long the relay was switched off due to an alarm. It is
recorded with a resolution of 1 minute and only when the control voltage is applied.
Query the cumulative alarm time:
Change into the display mode
Press the button several times until display 8acxx8
Press the button 1x display 8tal 8/ 8x.xx8
Delete the alarm counter and cumulative alarm time (only together):
Display alarm counter8acxx8
Press the button 1x display 8tal 8/ 8x.xx8
Keep the button pressed for 2s until display 8tal 8/ 80.008

UFR1001E 12420-0701-03 Page
18
/ 36 www.ziehl.de
8.10 Alarm memory
Independent of the alarm counter, the UFR1001E stores the most recent 100 shut-down causes (cause,
measurement value, at operating time). Simulated alarms are also registered. The LEDs indicate the cause;
the tripping value that led to the alarm each stands in the 7-segment display. Alternative to that
the time is shown in hours which have passed since the last tripping (with applied control voltage).
These values remain saved even after the power has been turned off.
Query alarm memory:
Change into the display mode
Press the button several times display 8acxx8
Press the button 1x display 8 x.xx8/ 8x.xx8
(tripping value or error no. / time that has passed in hours)
Press the button 1x, go to next alarm
The alarm memory is only deleted during a program change.
8.11 Standby counter and standby time
The standby counter 8stby8, is increased by 1 with every standby shut-down. Up to 9999 shut-downs are
counted. That lets the UFR1001E quickly detect how often, e.g., shut-down was performed through a ripple
control receiver.
Query the standby counter:
Change into the display mode
Press the button several times until display 8acxx8
Press the button 2x display 8stby8/ 8xxxx8
The standby time 8stby8indicates how long the relay was switched off by the standby mode. It is recorded
with a resolution of 1 minute and only when the control voltage is applied and if no alarm is present.
Query the standby time:
Change into the display mode
Press the button several times until display 8acxx8
Press the button 3x display 8stby8/ 8x.xx8(Time LED is illuminated)
Delete the standby counter and standby time (only together):
Display alarm counter8acxx8
Press the button 2x display 8stby8/ 8xxxx8
Keep the button pressed for 2s until display 8stby8/ 808

UFR1001E 12420-0701-03 Page
19
/ 36 www.ziehl.de
8.12 Code lock
You can protect the set parameters by enabling the code lock here.
The device acknowledges an incorrect entry with 8err8(flashes three times).
Adjustment process:
Select the menu item with the buttons until display 8Code.8
Press the button 1x display 8Pin 8/ 808
Set the saved pin code with the buttons (default setting is 85048)
Press the button 1x display 8Code8/ 8off 8
Use the buttons to set the desired code lock:
o8off8off, all parameters can be changed
o8On8on, no parameters can be changed
Press the button 1x display 8Pin 8/ 85048
Use the buttons to set the new, desired pin code (caution: write down the pin code)
Press the button 1x
Code lock on, display 8on8flashes three times
Code lock off, display 8off 8flashes three times
Return to menu mode, menu item code lock
If there are any problems with the code lock (pin forgotten), the lock can be switched off and the pin can be
reset to 504 by keeping the Set key pressed while switching on the mains until 8Code8/ 8off8appears
in the display.
8.13 Sealing
All the settings and the simulation mode can be locked.
If the LED is illuminated, the UFR1001E is locked.
If an attempt is made to change a setting in the locked state, for 3s the display shows 8LOc 8.
Adjustment procedure Sealing/Lock ON (OFF):
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the key cover and turn 180°
Actuate the small blue button by pressing the button cover very firmly (LED starts flashing)
until the green LED is illuminated.

UFR1001E 12420-0701-03 Page
20
/ 36 www.ziehl.de
8.14 Simulation
Here, the voltage, frequency or a vector surge can be simulated and the setting can be tested. All 3 phases
plus the 10 minute mean value are always simulated. All functions of the device operate as if this value is
actually being measured. Alarm and error messages are only indicated with the LEDs and not in the display.
The set values are simulated until the menu item si . is exited with the or
button. If the UFR1001E is sealed/locked, simulation is not possible.
If the section switch feedback contacts are connected to the UFR1001E and enabled, (set value > section-
switch turn-on time under 8trel.8), after a shut-down, the tripping time (dAL + time of slowest section
switch) is displayed.
Adjustment process:
Select the menu item with the buttons until display 8si .8
Press the button 1x display 8si 8/ 8u 8
Use the buttons to set the measurement factor for simulation:
o8u 8Voltage + 10min mean value (frequency = last simulated value)
o8f 8Frequency (voltage = last simulated value)
o8vsr 8Vector shift
Press the button 1x display 82308(selected measurement factor is simulated)
Use the buttons to set the desired value
After exiting the Simulation menu item with the buttons, the unit switches over to monitoring the limits.
The unit automatically returns to the display mode if no button is pressed for 15 minutes.
Hint: A limit value should be tested that is higher than the set 10min mean value. If the 10min mean value
has to be temporarily switched off, set (8Um .88off.8since otherwise it will trip first. The same
applies, for example, for U, , during a simulation of U,, in Pr3 and Pr4. (Medium voltage)