ZIEHL UFR1001E User manual

ZIEHL industrie –elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Quick Guide UFR1001E
updated: 2019-04-24/Ba
from Firmware: 0-10
UFR1001E 12420-0751-13 Seite
1
/ 8 www.ziehl.de
- NA-protection according to VDE-AR-N 4105:2011+2018-11, power generators at the low
voltage grid, TAR medium voltage VDE-AR-N 4110:2018-11
- for use in power generators at the medium voltage grid according to BDEW
- with selectable vector shift detection and Rate of Change of Frequency (ROCOF,df/dt)
Detailed operating manual see: https://www.ziehl.com/en/products/?view=detail&detail=54
New, Firmware 0-10: default setting program 2 for low voltage VDE-AR-N 4105:2018-11
4 new programs (11-14) for medium voltage according to 4110:2018-11, new test mode
(display of the firmware function 8Info8→8fnr 8 or press “Set” for >10 s)
General Notes
Compliance with the following instructions is mandatory to ensure the functionality and safety of the
product. If the following instructions given especially but not limited for general safety, transport, storage,
mounting, operating conditions, start-up and disposal / recycling are not observed, the product may not
operate safely and may cause a hazard to the life and limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.
Operating controls
1
Test button
Press
shortly
Display test-menu: Relay K1 (8tst18) or K2 (8tst28) can be tested independently. (3min
without a button is pressed = go back to the normal mode)
2
LEDs Frequency / voltage, above / below threshold (red)
ON, 8AL 8or 8AL M8
Above / below threshold
Flashing, 8AL 88or 8AL M8
OFF-delay 8dof 8active
3
LED Vektor shift (VSR, red)
ON, 8AL 8
Threshold value for vector shift exceeded
Flashing, 8AL 8
OFF-delay 8dof 8active
4
LEDs Relay status (yellow)
OFF
Relays de-energized
ON
Relays energized
5
Digital display 4-digit (red)
Depending on program, display of current voltage, frequency, vector shift, average value
Display of alarm message 8AL 8, 8aL M8
Display of error with error code e.g. 8Err98
6
LED Time (yellow)
ON
A time is displayed
7
Backmost decimal point (red)
OFF
Display mode
Lightning
Menu mode
Flashing
Configuration mode

UFR1001E 12420-0751-13 Page
2
/ 8 www.ziehl.de
9
Up / Down button (in display mode, normal state)
Press shortly
Change to the menu mode, display of alarm memory (Down) / cumulative
time of alarms, standby counter, standby time (Up),
pushing of Set button for ≥ 2 s makes a reset of the stored values
Press for > 2 s
Display of MAX (Up) / MIN (Down) measured values, additional pushing of
Set button for ≥ 2 s deletes the stored values
10
LEDs Allocation of the measured value (yellow)
LEDs
Measured value
Lx and N ON
Voltage (L1 against N, L2 against N, L3 against N)
Lx and Ly ON
Voltage (L1 against L2, L2 against L3, L1 against L3)
Lx flashing quickly
Vector shift (L1, L2, L3)
L1 flashing
Frequency
11
Sealable button + LED
Press for > 2 s
Lock / Unlock
LED red
Settings and simulation mode are locked,
in case of setting attempts 8LOc 8is displayed for 3 s
LED green
Setting and simulation enabled
Default settings and firmware version
When changing programs, all parameters are reset to the default settings.
Menu
Parameter / Unit
Default settings
Users
Data
Low volt. VDE-AR-N 4105:
Medium voltage
VDE-AR-N 4110:2018-11
2011
2018
2011
3 AC+N
230V
3 AC
+N
230V
2/1 AC+N
230V
3 AC+N
57,7V
3 AC
100V
3/2/1AC+
N
230V
3 AC
400V
Pr1
Pr2 *
Pr7
Pr11
Pr12
Pr13
Pr14
U,,
59.S2
59>S2
u,, Alarm on/off
-
on
-
Pr11
Pr12
Pr13
Pr14
u,, Overvoltage
V
-
287
-
on
on
on
on
H,, Hysteresis
V
-
35.0
-
69.2
120
287
498
dal Response time
s
-
0.10
-
1.0
1.0
3.0
3.0
dof OFF-delay
s
-
60
-
0.30
0.30
0.10
0.10
U,
59.S1
59>S1
u, Alarm on/off
on
off
on
60
60
60
60
u, Overvoltage
V
264
264
264
On
on
off
off
H, Hysteresis
V
5.0
12.0
5.0
63.5
110
249
430
dal Response time
s
0.10
0.10
0.10
1.0
1.0
3.0
3.0
dof OFF-delay
s
60
60
60
180.0
180.0
60.0
60.0
UM:
59-Av
UM Alarm on/off
on
on
on
60
60
60
60
UM Overvoltage
V
253
253 3
253
Off
Off
off
Off
HM Hysteresis
V
3.0
5.0
3.0
63.5
110
253
438
dal Response time
s
0.10
0.10
0.10
1.0
1.0
3.0
3.0
dof OFF-delay
s
60
60
60
0.10
0.10
0.10
0.10
U_
27.S1
27<S1
u_ Alarm on/off
on
On
on
60
60
60
60
u_ Undervoltage
V
184
184
184
On
On
on
on
H_ Hysteresis
V
5.0
12.0
5.0
46.2
80.0
184
318
dal Response time
s
0.10
3.00 3
0.10
1.0
1.0
35.0
35.0
dof OFF-delay
s
60
60
60
2.70
2.70
1.00
1.00
U__
27.S2
27<S2
u__ Alarm on/off
-
On
-
60
60
60
60
u__ Undervoltage
V
-
103
-
Off
Off
off
Off
H__ Hysteresis
V
-
93.0
-
26.0
45.0
111
180
dal Response time
s
-
0.30 3
-
1.0
1.0
108
108
dof OFF-delay
s
-
60
-
0.30
0.30
0.30
0.30
8
Set / Reset button (in display mode, normal state)
Press shortly
Display of next measured value / alarm counter
Press for > 2 s
Reset, quit error messages
Press for > 4 s
Display of program, e.g. 8Pr 18
Press for > 10 s
Display of firmware version, e.g. 80-108

UFR1001E 12420-0751-13 Page
3
/ 8 www.ziehl.de
Menu
Parameter / Unit
Default settings
Users
Data
Low volt. VDE-AR-N 4105:
Medium voltage
VDE-AR-N 4110:2018-11
2011
2018
2011
3 AC+N
230V
3 AC
+N
230V
2/1 AC+N
230V
3 AC+N
57,7V
3 AC
100V
3/2/1AC+
N
230V
3 AC
400V
Pr1
Pr2 *
Pr7
Pr11
Pr12
Pr13
Pr14
F,,
81.S2
81>S2
F,, Alarm on/off
-
off
-
60
60
60
60
F,, Overfrequency
Hz
-
52.50
-
off
Off
on
On
H,, Hysteresis
Hz
-
2.40 ²
-
51.50
51.50
52.50
52.50
dal Response time
s
-
0.10
-
1.40 ²
1.40 ²
2.40 ²
2.40 ²
dof OFF-delay
s
-
60
-
0.10
0.10
0.10
0.10
F,
81.S1
81>S1
F, Alarm on/off
On
On
on
off
off
on
on
F, Overfrequency
Hz
51.50
51.50
51.50
51.50
51.50
51.50
51.50
H, Hysteresis
Hz
1.45 1
1.40 ²
1.45 1
1.40 ²
1.40 ²
1.40 ²
1.40 ²
dal Response time
s
0.10
0.10
0.10
5.40
5.40
5.00
5.00
dof OFF-delay
s
60
60
60
60
60
60
60
F_
81.S1
81<S1
F_ Alarm on/off
on
On
on
off
off
on
on
F_ Underfrequency
Hz
47.50
47.50
47.50
47.50
47.50
47.50
47.50
H_ Hysteresis
Hz
1.00
0.10
1.00
2.40 4
2.40 4
2.40 4
2.40 4
dal Response time
s
0.10
0.10
0.10
0.40
0.40
0.10
0.10
dof OFF-delay
s
60
60
60
60
60
60
60
F__
81.S2
81<S2
F__ Alarm on/off
-
Off
-
Off
Off
Off
Off
F__ Underfrequency
Hz
-
47.00
-
47.50
47.50
47.50
47.50
H__ Hysteresis
Hz
-
0.60
-
2.40 4
2.40 4
2.40 4
2.40 4
dal Response time
s
-
0.10
-
0.10
0.10
0.10
0.10
dof OFF-delay
s
-
60
-
60
60
60
60
uonf
uonf on/off
off
Off
off
off
off
off
off
uonf voltage
V
46.0
46.0
46.0
20.0
20.0
46.0
46.0
Vsr
78
vsr Alarm on/off
stby
Stby
stby
stby
stby
stby
stby
vsr Vector shift
°
10.0
10.0
10.0
10.0
10.0
10.0
10.0
dof OFF-delay
s
3
3
3
3
3
3
3
dEon Suppression time
s
2
2
2
3
3
3
3
vsr Number of phases
3ph
3ph
3ph
3ph
3ph
3ph
3ph
Rocf
81r
rocf Alarm on/off
Off
Off
Off
Off
Off
Off
Off
dfdt delta f / delta t
Hz
/s
0.800
2.000
0.800
2.000
2.000
2.000
2.000
Per periods
20
20
20
20
20
20
20
dal Response time
s
0.10
0.10
0.10
0.10
0.10
0.10
0.10
dof OFF-delay
s
60
60
60
60
60
60
60
rEL
trEL Response time Yx
s
5.0
5.0
5.0
off
off
off
off
dofa Mode
ind
Ind
ind
ind
ind
ind
ind
dofa Off-delay all
s
0
0
0
0
0
0
0
ddi
ddi Display delay
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
dit Display duration SCn
s
3.5
3.5
3.5
3.5
3.5
3.5
3.5
Si
U Voltage
V
230
230
230
57.7
100
230
400
F Frequency
Hz
50.00
50.00
50.00
50.00
50.00
50.00
50.00
vsr Vector shift
°
0.0
0.0
0.0
0.0
0.0
0.0
0.0
CodE
pin Pincode
504
504
504
504
504
504
504
Info
fnr Firmware version
0-10
0-10
0-10
0-10
0-10
0-10
0-10
snr Serial number
xxxx
xxxx
xxxx
xxxx
xxxx
xxxx
xxxx
h Operating hours
h
xxxx
xxxx
xxxx
xxxx
xxxx
xxxx
xxxx
err Error counter
xxx
xxx
xxx
xxx
xxx
xxx
xxx
Pr Program
1
2
7
11
12
13
14
* factory preset 1= Autohysteresis 50,05 Hz ² = Autohysteresis 50,10 Hz
3= Parameter can be changed independently of the code lock (only in Pr2) 4= Autohysteresis 49,90 Hz
Display of the program: 8Info8→8Pr 8or when switching on
Display of the firmware version: 8Info8→8fnr 8

UFR1001E 12420-0751-13 Page
4
/ 8 www.ziehl.de
Connection diagram, 1x section switch (VDE-AR-N 4105:2018-11)
1) Feedback contacts Y1/Y2 not connected set 8rel .8→8trel.8→8off.8
2) N connected set 8Pr 18, 8Pr 38or 8Pr 58
3) Nc- or no-contacts can be connected, automatic detection when switching on
4) Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5) Fuses only when line protection necessary, e.g. 16 A
6) Contact closed suppresses evaluation of feedback contacts and vector shift
(8vsr .8→8on.8) suppresses feedback contacts (8vsr .8→8y1y2.8) or switches device into
standby (8vsr .8→8stby.8= default setting) e.g. through ripple control receiver or timer
7) 1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 13, 20)
8) Additional switch-off of self generating plant.
Single-fault safety: shutdown of the self generation plant e.g. by ripple control input 0% with K2. Use
coupling relays ford contact multiplication of if safe isolation is required.
This second shutdown path must be tested separately during commissioning. (8tst28)
9) UPS/buffer. Switches have to withstand undervoltage for min. 3 s (FRT)

UFR1001E 12420-0751-13 Page
5
/ 8 www.ziehl.de
Description of the connections
A1 and A2
Rated control supply voltage Us, see Technical Data (any polarity)
11, 12, 14; 21, 22, 24
Relay K1 and K2
E1 –E2
Enable –Input
Volt-free contact
8vsr .8→8 off.8, no function
8vsr .8→8 on.8, E1-E2 closed: vector shift active but not evaluated,
monitoring of feedback contacts Y1/Y2 off for use with generator
8vsr .8→8stby.8, E1-E2 closed: K1 and K2 off (standby), vector shift off
8vsr .8→8Y1Y2.8, E1-E2 closed: monitoring of feedback contacts Y1/Y2 off,
vector shift off
Y0, Y1, Y2
Inputs, feedback
contacts
Volt-free n/o or n/c contact, self-learning when switching on
Adjust the turn-on time of the section switch under 8rel.8→8trel.8, switch-off
(8off .8) if not connected or if switches are controlled from other device
I1
Supply voltage for digital outputs, max. 27 V DC
Q1…Q4
Digital output over-/undervoltage/-frequency, Q3 + Q4 = ROCOF
Q5
Digital output Error, in Program 3-6 additionally the 2nd threshold value
L1, L2, L3, N
Phase L1, L2, L3 and neutral conductor
Important notice
In the supply line in the vicinity of the device (easily accessible), a switch
marked as disconnecting device as well as an overcurrent protection element
have to be provided.
Attention!
For the rated control supply voltage, see label at the side of the unit!
WARNING
Hazardous electrical voltage!
Can lead to electric shock and burns.
Before starting work, switch plant and device voltage-free.
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air
current, the permissible ambient temperature is decreased.
Mounting
The device can be mounted:
•Distribution panel or control panel on 35 mm rail according to EN 60715
Disposal
Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal
provisions.

UFR1001E 12420-0751-13 Page
6
/ 8 www.ziehl.de
Program setup
The suitable program must be set on the UFR1001E in accordance with the application. If the
UFR1001E is sealed/locked (red LED lightning), sealing has to be deactivated first.
Pr
Connection
Limit
Voltage
Country / Standard
* 2
3 AC with N
Niederspannung
2x over voltage, 2x under voltage
2x over frequency, 2x under frequency
10min average value,1x vector shift
1x ROCOF
230V
VDE-AR-N 4105:2018
1
3 AC with N
Niederspannung
1x over voltage, 1x under voltage
1x over frequency, 1x under frequency
10min average value, 1x vector shift
1x ROCOF
230V
VDE-AR-N 4105:2011
7
2/1 AC with N
11(3)
3 AC with N
Mittelspannung
2x over voltage, 2x under voltage
2x over frequency, 2x under frequency
10min average value, 1x vector shift
1x ROCOF
63,5V
VDE-AR-N 4110:2018
(BDEW Juni 2008 by
3.2.3.3-1)
12(4)
3 AC without N
100V
13(5)
3/2/1 AC with N
230V
14(6)
3 AC without N
400V
10
3/2/1 AC with N
1x over voltage, 1x under voltage
1x over frequency, 1x under frequency
10min average value, 1x vector shift
1x ROCOF
230V
ÖVE/ÖNORM
E 8001-4-712
15
3 AC with N
230V
VSE/EEA-CH 2014
20
3/2/1 AC with N
2x over voltage, 2x under voltage
2x over frequency, 2x under frequency
10min average value, 1x vector shift
1x ROCOF
230V
G98(G83/2) +
G99(G59/3)
21
3 AC without N
400V
22
3 AC with N
63,5V
23
3 AC without N
110V
* default setting, default settings 8pr 38... 8Pr 68, 8pr108, 8pr158, 8pr208... 8Pr238see
https://www.ziehl.com/en/products/?view=detail&detail=54
Adjustment process:
•If present, remove seal (only authorised person)
•Apply control supply voltage at A1-A2
•Slightly lift the button cover and turn 180°
•Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the
green LED is lightning.
•Press button 1x →Display 8Info.8
•Press button 5x →Display 8Pr 1.8
•Set the program with the buttons
•Press button 1x →Display 8no.8
•Press button 1x →Display 8yes.8
•Press button
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to “default settings“ (see
table „Default settings“). Only change the parameters after having selected the correct program.
Technical data
Rated control supply voltage Us: 24-270V AC/DC -15…+10 %, DC / 40-70 Hz, <5 VA
Output relays: 2 c/o contacts
Max. switching voltage 400 V AC
Inrush current (at 10 % ED) 25 A max. 4 s / 50 A max. 1 s
Rated operational current Ie(AC15) 230 V AC / 6 A
Fuse rating to achieve short-ciruit protection max. gG/gL/B 6 A

UFR1001E 12420-0751-13 Page
7
/ 8 www.ziehl.de
Output voltage - transistor outputs Q1-Q5
Operational voltage VQ4.5-27 V DC
Max. current consumption Q1…Q5 20 mA / output
Input circuit - feedback contacts Y0 –Y1/2
No-load voltage at the control inputs 15-35 V DC
Subject to change without prior notice
Control chart (Pr 1, 7, 10, 15 see Detailed operating manual
https://www.ziehl.com/en/products/?view=detail&detail=54)
Pr
Connection
Country /
Standard
2
3 AC
+ N
VDE-AR-N
4105:2018
11
3 AC
+ N
VDE-AR-N
4110:2018
12
3 AC
13
3/2/1 AC
+ N
14
3 AC
3
3 AC
+ N
BDEW Juni
2008 nach
3.2.3.3-1
4
3 AC
5
3/2/1 AC
+ N
6
3 AC
20
3/2/1 AC
+ N
G98(G83/2)
+
G99(G59/3)
21
3 AC
22
3 AC
+ N
23
3 AC
[ ] = Unit
Pressing buttons Up/Down
simultaneously, sets the
values to the smallest one.
Code-Reset = Press button Set 2 s
while applying control supply voltage.
(Pin = 504)
Error reports:
Err4 = Tolerance Master Slave
Err5 = internal regulation
Err6 = communication error
Err7 = return error K1/K2
Err8 = limit error high < low
Err9 = parameter error
1) 3AC+N = 300V
Configuration mode
Menu mode
Display mode

UFR1001E 12420-0751-13 Page
8
/ 8 www.ziehl.de
Troubleshooting
Error
Cause
Remedy
8EEEE8or 8-EEE8appears
in the display
Measured voltage, frequency
or the vector shift is too large
or too small
Consider the measuring range
8Err48
appears in the display
Tolerance error, internal
measurement value deviation
of both channels
Perform a reset →
interrupt the control supply voltage
for >5 s *
8Err58
appears in the display
Error internal regulation
8Err68
appears in the display
Communication error internal
interface
8Err78appears in the
display even after 2
automatic repeated trials of
switching on + LED K1
and/or K2 is lightning
Error feedback contacts,
switches not connected
correctly or broken or
switches are controlled from
other device
Feedback contacts not connected
- set 8rel .8→8trel.8→8off8
Feedback contacts connected
- check the correct connection
- Adjust the turn-on time under 8rel .8
→8trel.8greater then the switch-on
time of the switcher
- Perform a reset →press Set/Reset
for >2 s
8Err88
appears in the display
Hysteresis error:
overlapping of the release
points
Upper threshold value must be higher
than the lower threshold value, check the
threshold values
8Err98
appears in the display
Configuration error
Reset to factory settings, see “Program
setup” *
A time expires in the display
If a OFF-delay 8dof 8is
active, the time runs down in
the display (the shortest one
first)
Wait until the time is complete
(depending on the setting, several times
may elapse one after the other)
Device cannot be configured
/ only the threshold values
can be configured
Code lock / Sealing activated
When having problems with the code
lock (Pin forgotten), the lock can be
deactivated and the pin can be reset to
504 , by pressing the button until
8Code8/ off8is shown in the display,
while switching on the control supply
voltage
Implausible voltage values
Pr selected with N, but N not
connected
Select Pr without N or connect N
8Loc 8
appears in the display
Sealing is active
See „Program setup“
8Code8
appears in the display
Code lock is active
See „Code lock“
8stby8appears in the
display
Standbymode, E1-E2 closed
check parameter 8vsr.8
8Al 8and LED Q3 (f>) is
on, reading value in good
range
hysteresis for 8F, 8
incorrectly
Ceck hysteresis for reset point
50,05 Hz
8noY18or 8noY28appears
in the display
Feedback contact not
connected or switch does not
switch
Check the connection and function of the
switch.
Its normal in Pr2 at Test 2 8noY28.
*If the error cannot be patched by a reset, send back to factory for repair.
Other manuals for UFR1001E
5
Table of contents
Other ZIEHL Relay manuals

ZIEHL
ZIEHL MSF 220 SE User manual

ZIEHL
ZIEHL TR250 User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL STW1K User manual

ZIEHL
ZIEHL MS220KA User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL MS220C User manual

ZIEHL
ZIEHL STW20K User manual

ZIEHL
ZIEHL MS220KA User manual

ZIEHL
ZIEHL SPI1021 User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL EFR4001IP User manual

ZIEHL
ZIEHL COSFI100V User manual

ZIEHL
ZIEHL STW12V User manual

ZIEHL
ZIEHL SW32V User manual

ZIEHL
ZIEHL MS220VA User manual

ZIEHL
ZIEHL STW1000V2 User manual

ZIEHL
ZIEHL VG1200 User manual