ZIEHL TR 800 Web User manual

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 1 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Operating Instructions
Universal-Relay TR 800 Web
Software version 1.1.9
MINIPAN®digital panel meters, temperature- and mains controlling,
special purpose instruments for customer requirements www.ziehl.com

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 2 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Table of contents
1. Application and short description ...........................................................................3
2. Overview of functions...............................................................................................3
3. Connection Plan........................................................................................................3
4. Display and controls.................................................................................................4
5. Important Information’s ............................................................................................5
6. Installation .................................................................................................................6
7. Detailed description..................................................................................................6
8. Start-up operation (commissioning)........................................................................7
8.1 General instructions on operating ...........................................................................7
8.2 Display mode ..........................................................................................................7
8.3 Menu mode.............................................................................................................7
8.4 Info mode................................................................................................................7
8.5 Short operating diagram..........................................................................................8
8.6 Overview of commissioning.....................................................................................9
8.7 Switching on the unit...............................................................................................9
8.8 Connection to network and controls........................................................................9
8.9 Find the unit in the network...................................................................................10
8.9.1 DHCP server.....................................................................................................10
8.9.2 Default IP- Adress 10.10.10.10.........................................................................10
8.9.3 Bonjour .............................................................................................................11
8.9.4 UPnP ................................................................................................................11
8.9.5 Information about the login window...................................................................11
8.10 Make the basic network settings...........................................................................12
8.11 Sensor settings .....................................................................................................13
8.12 Configuring the alarms..........................................................................................14
8.13 Alarm email...........................................................................................................15
8.14 System..................................................................................................................16
8.15 User management/access control.........................................................................17
8.16 Logging and FTP Upload ......................................................................................18
8.17 View measurements and alarms, sensor simulation .............................................20
8.18 Time-dependent control / Scheduler.....................................................................22
9. Ethernet protocols ..................................................................................................23
9.1 UDP ......................................................................................................................23
9.2 Modbus TCP.........................................................................................................23
9.3 SNMP....................................................................................................................23
9.4 FTP Upload (Option).............................................................................................23
9.5 AJAX data interface ..............................................................................................23
10. RS485 interface .......................................................................................................23
10.1 Ziehl Standard Protocol.........................................................................................23
10.2 Modbus RTU.........................................................................................................23
11. Maintenance and Repair.........................................................................................23
12. Troubleshooting......................................................................................................24
13. Technical Data.........................................................................................................25
14. Housing design V8..................................................................................................28

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 3 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
1. Application and short description
Web-IO Universal Relay with Ethernet-interface and 8 inputs for temperature-sensors
and other analogue signals.
The TR 800 Web can be connected to the internet or an intranet and operated via TCP/IP
from a normal PC with a suitable browser (tested with IE 7, IE 8 and Firefox 3). No special
software and no special instruction is required.
The Universal Relays TR 800 monitors and logs signals from up to 8 inputs.
Up to 8 limits (one per input) can be programmed for each of the 4 output-relays.
2. Overview of functions
8 measuring inputs:
oPt 100, Pt 1000 in 2- or 3-wire connection
oKTY 83 or KTY 84
oThermocouples type B, E, J, K, L, N, R, S, T
oDC 0-10 V, DC 0/4-20 mA
oResistance 500 Ohm, resistance 30 kOhm
4 relay-outputs (each potential-free change-over contact)
Ethernet interface (http, https, UDP, Modbus, Bonjour, UpNP, SNMP, AJAX)
RS485 interface (Standard Ziehl- and Modbus RTU- protocol)
Universal power-supply AC/DC 24-240 V
Integrated webserver for configuration, readout of measured data, user-management
email-alarms, data- and alarm-logging and ftp-upload
Time-dependent control (day/night)
Real-time clock with synchronisation with timeserver
3. Connection Plan
1) Terminating resistor active: Bridge A to A’ and B to B’

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 4 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
4. Display and controls
1, 2 LEDs (yellow) RS485 interface
Rx flashes briefly: Unit is receiving data via the RS485 interface
Tx flashes briefly: Unit is transmitting data via the RS485 interface
Rx and Tx flash/illuminate during firmware update
3 LED (red) Sensor error
Illuminated: Fault in a sensor circuit
4 LEDs (red) alarm
Illuminated: Alarm (1-4) has occurred
Flashes briefly (1:4): Response delay is running
Flashes long (4:1): Backshift delay is running
Flashes uniformly (1:1): Ready for reset, reset with key
Press "SET/RESET" ≥ 2s or ext. Reset Y1/Y2
5 LED (yellow) Night
Illuminated: Limits for "Night" (can be set via browser) are active
6 LEDs (yellow) sensors
Illuminated: Displays the sensor value belonging to the LED in the
digital display
Flashes: Sensor error in the corresponding sensor circuit
7 LEDs (yellow) relay state
Illuminated: The relay belonging to the LED is picked up
Off: The relay belonging to the LED is released
8 Digital display (4 digits)
Display of sensor value
Display of error codes
Display of menu and configuration mode
9,10 Up button / Down button
Change into the menu mode (see Operating instructions Point 8.3)
11 Set/Reset button
Press briefly: Displays the next sensor (sensor LED illuminates)
Press for 10 s: Displays the software version (e.g. 0-00)
12 LED (yellow) Displays Ethernet transmission speed
Off: 10 Mbps On: 100 Mbps
13 LED (green) Displays Ethernet data traffic
Flashes during active data transmission
14 IP address slide switch
Towards Ethernet jack: IP address 10.10.10.10
Towards reset button: IP address User (set via web browser)
15 Webserver reset button
Internal webserver restarts when pressed (duration ca. 1 minute)

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 5 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
5. Important Information’s
To use the equipment flawless and safe, transport and store properly, install and start
professionally and operate as directed.
Only let persons work with the equipment who are familiar with installation, start and use
and who have appropriate qualification corresponding to their function. They must observe
the contents of the instructions manual, the information which are written on the equipment
and the relevant security instructions for the setting up and the use of electrical units.
The equipments are built according to DIN / EN and checked and leave the plant according
to security in perfect condition. To keep this condition, observe the security instructions with
the headline „Attention“ written in the instructions manual. Ignoring of the security
instructions may lead to death, physical injury or damage of the equipment itself and of other
apparatus and equipment.
If, in any case the information in the instructions manual is not sufficient, please contact our
company or the responsible representative.
Instead of the industrial norms and regulations written in this instructions manual valid for
Europe, you must observe out of their geographical scope the valid and relevant regulations
of the corresponding country.
DANGER!
Hazardous voltage!
Will cause death or serious injury. Turn off and lock out all power
supplying this device before working on this device.
Observe the maximum temperature permissible when installing in switching cabinet.
Make sure sufficient space to other equipment or heat sources. If the cooling
becomes more difficult e.g. through close proximity of apparatus with elevated
surface temperature or hindrance of the cooling air, the tolerable environmental
temperature is diminishing.
ATTENTION! Connection of sensors
The inputs 1T1, 1T2, 1T3 to 8T3 and RESET Y1, Y2 are not potentially
separated from output RS485. Temperature-sensors must have
a sufficient insulation.
Only signals according to SELV (Safety Extra Low Voltage) may be
connected.
The pluggable terminals of the measuring inputs have a special
contact-material and may only be used for the connection of the
sensors.
Attention! Universal power supply
The unit is equipped with a universal power supply, which is suitable for DC- and AC-
voltages. Before connecting the unit to the current, make sure that the allowed scope of
voltage of the control voltage Us, written on the lateral type plate, corresponds to the supply
voltage of the unit.
!

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 6 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
ATTENTION! When all relays are programmed in operation current
mode (= pick up at alarm), a loss of the supply voltage or an instrument
failure can remain unidentified.
When the relay is applied as control instrument, the operator must
ensure, that this error is recognized by regular examinations.
We recommend to program and accordingly evaluate at least one relay
in the closed-circuit current mode.
6. Installation
The unit can be installed as follows:
Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715
With screws M4 for installation on walls or panel. (additional latch not included in delivery)
Connection according to connection plan or type plate.
A circuit-breaker or switch must be situated within easy reach of the
unit and fused. Installation excess current protection should be ≤10 A.
7. Detailed description
The TR 800 Web measures up to 8 connected sensors, displays the measured values
and evaluates them.
Configuration and operation are performed with a computer through a web browser
A setting can be made for each sensor
oAssignment limit <-> Alarm (as desired)
oAlarm active / inactive
oLimit for alarm on
oLimit for alarm off
For Relays K1 .. K4 (Alarm 1 .. Alarm 4) can be set individually
oResponse delay and switch-back delay
oRelay on/off during alarm (operating or closed-circuit current)
oAlarm during error (message about sensor errors and device errors)
oAlarm locked, (To reset, press "SET" ≥ 2s or ext. reset Y1/Y2
Ethernet interface for
ohttp and https (under http, port can be set and switched off)
oUDP protocol to read out data (port adjustable)
oModbus protocol to read data
RS485 interface for
ostandard Ziehl protocol to read data
oModbus RTU protocol to read data
Via the web browser, the following functions are available
oDisplay measurement, min and max values with date/timestamp
oSensor simulation for simulating individual sensors
oAlarm status display
oSensor configuration (name, type, compensation, scale and unit)
oAlarm configuration (limits, operating/no-load current, alarm during error, alarm
locked, response /switch-back delay and email)
oTime-controlled day/night limits switchover
oData logging, alarm logging and parameter logging with date/timestamp
!
!

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 7 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
oNetwork configuration
oSystem settings
oUser management
8. Start-up operation (commissioning)
8.1 General instructions on operating
One can identify the device operating mode with the decimal point behind the last 7-segment
display.
8.2 Display mode
Decimal point off (normal state for measurement display)
Displays the current sensor value (related yellow sensor LED
illuminated, change to next sensor by pressing Set -> button)
LED yellow
RS485 Rx / Tx
Flashes during data communication via RS485 interface
LED yellow
Day / Night
ON = Limits for "Night" are active
OFF = Limits for "Day" are active
LED yellow
Relay K1 .. K4
ON = Relay operating
OFF = Relay is released
LED red
Alarm 1 .. 4
Flashes 1:4 = Response delay is active
Flashes 4:1 = switch-back delay is active
Flashes 1:1 = Ready for switch back, reset with press
"SET/RESET" button ≥ 2s or close ext. Reset Y1/Y2
On = Alarm on
OFF = Alarm off
LED yellow
Sensor 1 .. 8
ON = Measurement of selected sensors in the display.
Flashes = Error in sensor circuit
LED red
Sensor error
On = Fault in a sensor circuit
(Defective, yellow sensor LED flashes)
Function key
Set/Reset
Press briefly: Displays the next sensor (sensor LED illuminates)
Press for 10 s: displays the software version
Function keys
Up and Down
Press briefly: Change into the menus mode
8.3 Menu mode
Decimal point on
Select the menu items to view the parameters
Function keys
Up and Down
Press briefly: Select menu item; change into the display mode
Function keys
Set/Reset
Press briefly: Change into the configuration mode
8.4 Info mode
Decimal point flashes
Function keys
Up and Down
Not in use
Function keys
Set/Reset
Select next parameter; after the last parameter change into
menu mode

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 8 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
S 1
100
1000
83
84
th..
0-10
0-20
4-20
R500
R30.0
diff
S 2
100
1000
83
84
th..
0-10
0-20
4-20
R500
R30.0
diff
Sensor
1Sensor
2Sensor
3Sensor
4..8
,192
168
´ 1
_ 95
Dhcp
Off / on / fail
IP
AL 1
AL 2
AL 3
AL 4
S 3 –S 8
Sensor
typ
...
...
= Reset
= Down
= Up
>2s = Set
IP-
Thermocouples (th..)
thb = Typ B
thn = Typ E
thj = Typ J
thk = Typ K
thl = Typ L
thn = Typ N
thr = Typ R
ths = Typ S
tht = Typ T
8.5 Short operating diagram
8typ type of sensor8
8S 1 8… 8S 8 8sensors 1 to 8
8nc8not connected
81008type Pt 100
810008type Pt 1000
8838KTY 83
8848KTY 84
8th . .8thermocouples
80-108voltage input 0-10 V
80-208current input 0-20 mA
84-208current input 4-20 mA
8r5008resistance 500 Ohm
8r30.08resistance 30 K Ohm
8diff8difference
8IP 8IP- address
8IP- 8IP- address
8,19281 digit of IP- address
8π16882 digit of IP- address
8´1 3 digit of IP- address
8_ 9584 digit of IP- address
8dhcp8DHCP
8 off8DHCP off
8on8DHCP on
8faIl8DHCP missed
8Al 18... 8Al 48alarms 1 to 4
8boot8webserver starts
Menu mode
Info mode
Display mode
normal operation
error messages:
Er 1 = sensor shortcircuit
Er 2 = sensor break
Er 4 = thermocouple poled wrong
Er 5 = no contact to web-module
Er 8 = error in unit
Er 9 = error in parameters
Sensors assigned to an alarm are lighting (yellow)
Sensors having caused an alarm are blinking (yellow)

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 9 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.6 Overview of commissioning
Must
Can
Overview
X
8.7 Switch on the unit
X
8.8 Connection to network and controls
X
8.9 Find the unit in the network
8.9.1 DHCP server
8.9.2 Default IP address 10.10.10.10
8.9.3 Bonjour
8.9.4 UPnP
X
8.10 Make the basic network settings
X
8.11 Sensor settings
X
8.13 Configure the alarms
X
8.13 Alarm email
X
8.14 System
X
8.15 User management/access control
X
8.16 Logging
X
8.17 View measurements and alarms, sensor simulation
8.7 Switching on the unit
Apply supply voltage to terminals A1 and A2,
Ca. 2s long, all LEDs and the digital display illuminate ( 8.8.8.8. )
The TR 800 Web is now ready to operate
In the digital display, boot flashes (alternating with sensor value), the
integrated webserver starts (duration ca. 1-2 minutes). After boot
extinguishes, the unit can be addressed via its interfaces.
8.8 Connection to network and controls

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 10 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.9 Find the unit in the network
Prerequisite: Web browser Internet Explorer 7,8 or Firefox 3 (tested).
The TR 800 Web provides four facilities to find itself in the network:
8.9.1 DHCP server
In the network, there is a DHCP server; newly added units automatically are assigned an
IP address
Query of the IP address in the unit
Press the DOWN button 2x, then the SET button
IP address appears in the digital display
Status of DHCP query is displayed ( off / on / FAIL )
Start web browser and enter the IP address in the address line [Return]
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without password)
If the network logon fails via DHCP, a network configuration will be performed based on
zeroconf (IP = 169.254.x.x).
8.9.2 Default IP- Address 10.10.10.10
! Use this setting for configuration only.
Push slide switch to IP 10.10.10.10 (sketch Point 8.8)
Requires a reboot of webserver (press RESET button), in the digital display boot
flashes (start duration ca. 1 min)
User management is deactivated, http-Port = 80 und https-Port = 443
Note: The following actions can only be performed with administrator rights.
Enter this command into your PC in the input prompt (command line):
route add 10.10.10.10 xxx.xxx.xxx.xxx (xxx.xxx.xxx.xxx= IP address of PC)
Route for the TR 800 Web
ping 10.10.10.10
Connection test
TR 800 Web replies
Reply from 10.10.10.10: Bytes=32 Time=3ms TTL=32
Reply from 10.10.10.10: Bytes=32 Time=1ms TTL=32
Ping statistic for 10.10.10.10:
Package: Sent = 4, Received = 4, Lost = 0 (0% loss),
Connection okay
Start web browser and enter the IP address (10.10.10.10) in the address line [Return]
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without password)
Make the basic network settings
Push the slide switch to IP USER (sketch Point 8.8)
Requires a reboot of webserver (press RESET button), in the digital display boot
flashes (start duration ca. 1-2 minutes
Note: The settings made in the web browser under "Network" are only effective after the
slide switch is switched to IP User and the unit has been rebooted (press RESET button).

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 11 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.9.3 Bonjour
Plugin for Internet Explorer (www.apple.com/bonjour)
Plugin for Firefox Browser (www.bonjourfoxy.net)
Optional in the Safari browser (switch on)
Note: not available if the http-service has been disabled.
Windows: Download the plugin for Internet Explorer from the Internet and install it
Mac OS X: Bonjour is integrated in the system (Safari browser)
Linux: Bonjour not available
Start browser and let TR 800 Web search with Bonjour.
Double click on the device found
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without
password)
8.9.4 UPnP
Available for Windows starting from Win XP
Note: not available if the http port has been switched off
Start network browser (network environment),
("Symbols for show Network UPnP devices" must be active)
Double click on the device found
The TR 800 Web homepage opens in the web browser
Close the login window with the OK button (without user name and without
password)
8.9.5 Information about the login window
Closing the login window (click on OK button) is delayed a couple of seconds as data still
needs to be transmitted in the background.
If the user admin/access control is inactive (default) the login window is not visible.
The user management/access control is always deactivated if the slide switch is set to
IP=10.10.10.10 (see Points 8.8 and 8.9.2).
If the user admin/access control is active (see Point 8.15), the Username and Password
must be entered.
Entry is case-sensitive.
Guest access (if activated, see Point 8.15) is made by logging in without any user name and
password. Guests can only view the "Measurements" and "Sensors" web pages. It is not
possible to change the parameters.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 12 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.10 Make the basic network settings
Select "Network" in the web browser menu
Network TCP/IP:
You can enter the desired network parameters here.
Ask your network administrator if necessary.
Note: Switch off http with http-Port = 0.
UDP settings:
The device provides a facility to download data via the UDP protocol.
The related UDP port can be changed here.
RS485 interface:
If the device is operated on a RS485 interface, the parameters and the protocol can be
selected here
Email settings:
The TR 800 Web provides a facility for sending an email if the alarm state changes.
Enter the access data into the corresponding boxes.
Active services:
Services may be disabled.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 13 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.11 Sensor settings
Select "Sensors" in the web browser menu
Make the settings for the connected sensor types here. A name can be assigned for each
sensor for clear identification.
Box
Description
Sensor name
State a name for sensors 1 - 8
Current value
Display the measurement with the unit
Sensor type
Select the sensor type
Wire
Compensation
only with Pt100 / Pt1000: Select "3-wire" or choose a total wire
resistance for 2-wires.
2-wire technique wire resistance compensation:
To compensate the wire resistance short-circuit the wires nearby the
sensor and measure the wire resistance. We recommend to use 2 or
better 3 wires for each sensor.
With 2-wire connection and a common wire for all signals, all sensor
measuring currents will be added on the common wire. Thus the value
of the compensation wire resistance RK must be calculated as follows:
RK = (n+1) x RL/2
(RL = wire resistance of two wires, n = number of sensors)
Scaling on
Zero-point
Full-scale
Dec. point
Scaling for temperature sensors not available.
Zero-point scaling
Full-scale scaling
Decimal point scaling
Unit
°C, °F, V, mA, Ω, kΩ, % and a freely-definable unit (box can be edited).
°C and °F are available for temperature sensors.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 14 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.12 Configuring the alarms
Box
Description
Day / Night
Switch the display of the alarm values for day / night operation.
Definition of the switchover times in the "Time control" menu
Attention: Only affects the values of "Alarm ON" and "Alarm OFF"
Alarm name
State a name for the respective alarm
Delay
on: Time (in s) during which an alarm is suppressed:
off: Backshift (in s) after an alarm
Relay on alarm
on: The relay picks up during an alarm
off: The relay releases during an alarm
Alarm on error
on: This alarm is non-delayed triggered during:
device error
sensor error (even if the sensors are not "active")
off: This alarm is not triggered during a sensor error / device error.
If a sensor triggers an alarm, and this sensor has an error, then
the alarm is non-delayed reset (even if "Alarm locked '= on).
Alarm locked
on: An alarm occurring one time will not be automatically reset. Only
pressing reset (close "SET/RESET" button ≥ 2s or ext. Y1/Y2 reset or
break of supply voltage Us) resets the alarm.
off: Alarm not locked
Sensor no.
active: Switches the alarm for this sensor on/off
Alarm on : Value at which the device triggers an alarm
Alarm off: Value at which the device resets an alarm

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 15 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Definition of alarm values:
Value in
box
Value in
box
Alarm state
Alarm on
>
Alarm off
Alarm if: Measurement value >= Alarm on
Alarm off if: Measurement value < Alarm off
Alarm on
<
Alarm off
Alarm if: Measurement value <= Alarm on
Alarm off if: Measurement value > Alarm off
8.13 Alarm email
In addition to an alarm message on Relay K1-K4, an email can also automatically be sent.
Box
Description
Dropdown list
Selects for which alarm (1-4) an email will be sent
Email
"Alarm ON"
Email will be sent if an alarm occurs
Email
"Alarm OFF"
Email will be sent if an alarm expires
Recipient
Enter email addresses (separated with a semicolon) or press "Add"
button and select the addresses from the list (emails of the addresses
entered in the [Users] menu)
Subject
Optional subject text
Text
Optional instructions text

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 16 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.14 System
The device name appears in the uppermost line of the website after saving.
The TR 800 Web has a real-time clock that can be synchronized with a "Timeserver" (NTP
protocol, uses UDP Port 123). The server, router, proxy … connected to the network usually
provides such a function. Timeservers from the Internet can also be used (e.g.
ptbtime1.ptb.de). Ask your network administrator if necessary. Alternatively, the system time
can be manually set and transferred with the "Update TR 800 system time".
Function
Description
Save device
settings
Every change in the device can be taken over with the [Save] button; a
new configuration point is automatically added. It is saved with the
date, time and the user. A comment can be added to these points.
Save device
settings
on a PC
Activate the desired configuration
Click the link [Download config. file]
The file is downloaded to the PC
Copy device
settings
from PC to
TR 800 Web
Press [Search …] button. Choose the desired "Config. file" and press
the [upload] button.
The config. file is uploaded and the configuration is taken over
Reactivate saved
device settings
Activate the desired configuration
Press the [Reactivate] button
The saved configuration is taken over
Set factory settings
Press the [Set factory settings] button
The device configuration is set to the delivered condition
Using the functions "Save device settings to a PC"

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 17 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
and "Transfer device settings from PC to TR 800 Web"
you can very simply copy the device settings to multiple TR 800 Webs.
Firmware updates including the installation instructions can be downloaded from the
www.ziehl.com website as needed.
8.15 User management/access control
The TR 800 Web has user management with access control. Stipulate the administrator, user
and guest access here as required. If the user management is switched on (checkbox [active]),
a password can be assigned to each user (and administrator). To do that, click on the [Change
password] button. In the window that opens, enter the first and second lines for each desired
password.
If the settings for the email account ("Network" menu) have been made, a test mail can be sent
to each user.
Possibly occurring transmission errors are logged in the "Test mail log file".

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 18 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
8.16 Logging and FTP Upload
Logging:
Measurement data and alarms are automatically logged as specified. Data records of 1500
measurements and 500 alarm changes are logged in two ring memories. 100 ring memories
are stored internally.
Recording time depending on the setting of the interval:
current ring memory
recording time
100 ring memory -backups
Interval
1500 data records
days
days
month
year
00:00:02
0:50:00
0.0
17.4
0.6
0.0
00:00:10
4:10:00
0.2
17.4
0.6
0.0
00:00:30
12:30:00
0.5
52.1
1.7
0.1
00:01:00
25:00:00
1.0
104.2
3.4
0.3
00:03:00
75:00:00
3.1
312.5
10.3
0.9
00:05:00
125:00:00
5.2
520.8
17.1
1.4
00:30:00
750:00:00
31.3
3125.0
102.7
8.6
01:00:00
1500:00:00
62.5
6250.0
205.5
17.1

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 19 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
Log description:
Content of the log files
Individual data records
Min/Max values with date/time
Date/time; Measurement values sensors 1-8; Alarm
values 1-4 (sum of the sensors that triggered the alarm
S1=1, S2=2…S8=128); Error number (device error)
Interval
In this time interval, the data is logged.
Checkbox ring memory
Data und Alarms
Selection of the ring buffer, sorted by date.. „current“ = the
last 1500 / 500 records.
DecSeparator
This character is used in the csv files.
[Display measurements] button
[Display alarms] button
The selected memory of data and the alarm states can be
viewed in a new window
[Delete measurements] button
[Delete alarms] button
The current memory and the backups are deleted.
Download measurement data
link Download alarms link
The selected memory is downloaded as a csv file
FTP Upload:
With the FTP upload, depending on selection, the current data values and alarms, the current
ring memory for data and alarms, and the internally stored ring memories are uploaded.
There are files with the extension ". upl" uploaded and then renamed to ". csv".
The filename uses the local time format. Inside the files, the selected time format is used (see
System Settings). In the case of transmission problems, see the "Transmission Log" file.
Upload Selection
present data and alarms
The file „current.csv“ will be uploaded.
Current data memory
The file „values.csv“ will be uploaded. The content consists of
1500 records (current ring memory data). file size about 100-
200 kbyte.
Data memory backups
The file(s) „values.xxx.csv“ will be uploaded. xxx = Date/time in
local time format.
Current alarms memory
The file „alarms.csv“ “ will be uploaded. The content consists
of 500 records (current ring memory alarms). file size about
40-80 kbyte.
Alarms memory backups
The file(s) „alarms.xxx.csv“ will be uploaded. xxx = Date/time
in local time format.
Trigger
Log interval
Time between upload of „present data and alarms“, current
data memory and current alarms memory .If available, also the
memory backup files are uploaded.
.
additional upload on
„alarm on“ und „alarm off“
On change of alarm, the upload is performed.
Button [manual upload]
An upload is performed.
Link Transmission Log
Transmission Log from the last upload. Link colour:
black: success; red: error.
Target Server
address
Enter the address of the destination FTP server IP or host
name. You can optionally add the port number. For example
"192.168.3.3" or "192.168.3.3:2000" or "ftpserver.com"

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05
Page 20 of 28 Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
directory
Enter the directory where the files are stored. Example:
"test/test2"
The indication of sub-directories with "/".
There must be no "\" be used.
anonymous login
Can be activated when the FTP server allows anonymous
login.
username
User name for login on the FTP server
Password
Password for the login on the FTP server
„delete“ before „rename“
This is to activate when the FTP server rename a file into an
existing file is not accepted.
This is in some Windows FTP servers / server program
needed. See Transmission Log.
8.17 View measurements and alarms, sensor simulation
Here, all measurements can be clearly viewed with min./max. values plus the alarms. Using the
sensor simulation, individual sensor values can be simulated. The simulation independently
switches off after 15 minutes with no changes in the simulation value.
Other manuals for TR 800 Web
3
Table of contents
Other ZIEHL Relay manuals

ZIEHL
ZIEHL VG1200 User manual

ZIEHL
ZIEHL TR250 User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL SPI1021 User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL TR 800 Web User manual

ZIEHL
ZIEHL UFR1001E User manual

ZIEHL
ZIEHL STW20K User manual

ZIEHL
ZIEHL COSFI100V User manual

ZIEHL
ZIEHL UFR1001E User manual