PROBLEM CAUSE SOLUTION
Yellow L.E.D. light ashes 3 times
when there are no
users.
Front of Object Lock Sensor is
covered or Object Lock Sensor is
set too far out, registering the
opposite wall or door as a user.
Remove item covering sensor or
adjust Object Lock Sensor activation
distance. (See Appendix B – Adjust-
ing the E-Z Flush.)
Yellow L.E.D. light ashes continuous-
ly when Object
Lock Sensor is activated by a user.
E-Z Flush unit is in 10-minute
start-up mode (when rst activated), or
Sensor Range Reset
Button has been depressed.
Yellow L.E.D. light will ash only 3
times, acknowledging a user is in view
after the 10-minute start-up mode.
Red L.E.D. light ashes. Batteries need replacing. Replace batteries.
Not enough water to xture or too
much water to xture.
Diaphragm damaged or valve
control stop improperly adjusted.
Replace diaphragm and/or adjust
valve control stop.
Valve will not operate. Object Lock Sensor range set too
close to E-Z Flush, batteries are
dead, or water supply is turned o.
Adjust Object Lock Sensor, replace
batteries, or turn water on. If the E-Z
Flush does not begin to function, call
Customer Service at 1-800-997-3876.
Valve does not shut o. Dirt or debris preventing diaphragm
from functioning properly.
Remove dirt or debris, check by-pass
hole in diaphragm.
Valve does not ush even after Object
Lock Sensor has been adjusted.
Batteries are dead. Replace batteries. If the E-Z Flush
does not begin to function, call Cus-
tomer Service at 1-800-997-3876.
Flush Valve Trouble Shooting Guide
Problem Corrective Action
“Status – Good” posted in plumbSMART and faucet actuaon
event data not appearing in plumbSMART (< 2 hours) or
“Device Not Communicang” warning or severe alert posted in
plumbSMART for all devices (> 3 hours)
Step 1
Verify gateway Status LED ashes twice every 2 seconds. If LED
is OFF or ON solid, power cycle the gateway and wait for no
more than 5 minutes for unit to inialize and connect.
Step 2
Aer inializaon is nished, LORA LED should turn ON solid
within an addional minute.
Step 3
If LORA LED does not turn ON solid and ethernet cable
connected, contact facility IT administrator to modify port rules
to allow Zurn gateway to access the internet via local router.
If gateway model is ETH/LTE, visually verify SIM card is installed
in designated slot on the side of gateway. If unit has a SIM card,
then disconnect ethernet cable and power cycle the gateway
and wait for unit to inialize and connect. LORA LED should
turn ON solid aer inializaon.
Step 4
If problem sll present, move gateway closer to LoRa monitors
and/or verify gateway mounng, orientaon and connecons
comply with requirements listed in Zurn Gateway Installaon
Guide.
Contact Zurn Customer Service at 1.855.ONE.ZURN
(1.855.663.9876) for assistance with addional troubleshoong
steps.
Trouble Shooting: Gateway
For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training