ABB i-bus KNX JRA/S 6.230.3.1 User manual

ABB i-bus®KNX
JRA/S
6.230.3.1
Blind/Roller Shutter Actuator
with Binary Inputs
Product Manual


ABB i-bus®KNX
Contents
JRA/S 6.230.3.1 | 2CDC506083D0201 i
Contents
Page
1General ................................................................................................. 3
1.1 Using the product manual.............................................................................................................3
1.1.1 Notes............................................................................................................................................4
1.2 Overview of product and functions ...............................................................................................5
2Device technology............................................................................... 7
2.1 Technical data..............................................................................................................................7
2.1.1 Binary inputs.................................................................................................................................8
2.1.2 Rated current output 6 A...............................................................................................................9
2.1.3 Lamp load output 6 A..................................................................................................................10
2.2Connection diagram ...................................................................................................................11
2.3 Dimension drawing.....................................................................................................................12
2.4 Mounting and installation............................................................................................................13
3Commissioning.................................................................................. 15
3.1 Supplied state.............................................................................................................................15
3.2 Overview.....................................................................................................................................15
3.2.1 Input functions............................................................................................................................15
3.2.2 Output functions .........................................................................................................................16
3.3 Parameters.................................................................................................................................17
3.3.1 General parameter window.........................................................................................................18
3.3.2 Output A,B Operation mode parameter window.........................................................................21
3.3.2.1 Output A,B: Blind parameter window..........................................................................................22
3.3.2.1.1 Output A,B: Blind - Drive parameter window ..............................................................................27
3.3.2.1.2 Output A,B: Blind - Automatic parameter window.......................................................................29
3.3.2.1.3 Output A,B: Blind - Scene parameter window.............................................................................33
3.3.2.1.4 Output A,B: Blind - Safety parameter window.............................................................................36
3.3.2.2 Output A,B: Switch actuator (only "UP" contact) parameter window ..........................................38
3.3.2.2.1 Output A,B: Switch actuator - Time parameter window..............................................................42
3.3.2.2.2 Output A,B: Switch actuator - Time, - Flashing parameter window.............................................47
3.3.2.2.3 Output A,B: Switch actuator - Scene parameter window............................................................50
3.3.2.2.4 Output A,B: Switch actuator - Logic parameter window..............................................................53
3.3.2.2.5 Output A,B: Switch actuator - Forced operation parameter window...........................................55
3.3.2.3 Output A,B: Shutter parameter window......................................................................................58
3.3.2.3.1 Output A,B: Shutter - Drive parameter window...........................................................................62
3.3.2.3.2 Output A,B: Shutter - Automatic parameter window...................................................................63
3.3.2.3.3 Output A,B: Shutter - Scene parameter window.........................................................................63
3.3.2.3.4 Output A,B: - Shutter - Safety parameter window.......................................................................63
3.3.3 Input a Function parameter window...........................................................................................64
3.3.3.1 a: Blind sensor parameter window..............................................................................................65
3.3.3.2 a: Switch sensor parameter window...........................................................................................70
3.3.3.2.1 Distinction between long and short operation – No ....................................................................72
3.3.3.2.2 Distinction between long and short operation – Yes...................................................................74
3.3.3.2.3 a: Switch sensor - Objects "Switch" parameter window..............................................................75
3.3.3.3 Input a: Dim sensor parameter window......................................................................................80
3.3.3.4 Input a: Value/forced operation parameter window ....................................................................85
3.3.3.4.1 ParameterDistinction between long and short operation – No.................................................87
3.3.3.4.2 Parameter Distinction between long and short operation – Yes.................................................92
3.3.4 Commissioning without bus voltage ...........................................................................................93

ABB i-bus®KNX
Contents
ii 2CDC506083D0201 | JRA/S 6.230.3.1
3.4 Group objects ............................................................................................................................ 94
3.4.1 Summary of group objects......................................................................................................... 94
3.4.2 General group objects................................................................................................................ 98
3.4.3 Input a…l group objects............................................................................................................. 99
3.4.3.1 group objects Switch sensor.................................................................................................... 100
3.4.3.2 Switch/dimming sensor group objects ..................................................................................... 101
3.4.3.3 Blind sensor group objects....................................................................................................... 102
3.4.3.4 Value/forced operation group objects...................................................................................... 104
3.4.4 Output group objects................................................................................................................ 105
3.4.4.1 The parameter setting options for Outputs A, C, E, G, I and K are described in the
Parameterfenster Ausgang A, B Betriebsart, p. 21.................................................................. 105
3.4.4.2 Output A group objects............................................................................................................ 106
3.4.5 Output A,B: Blind and Shutter group objects ........................................................................... 109
4Planning and application.................................................................115
4.1 Output A,B............................................................................................................................... 115
4.1.1 Drive types............................................................................................................................... 115
4.1.2 General functions..................................................................................................................... 115
4.1.2.1 Travel times............................................................................................................................. 115
4.1.2.2 Safety....................................................................................................................................... 117
4.1.2.3 Determining the current position.............................................................................................. 118
4.1.2.4 Move to position in % [0…100]................................................................................................ 119
4.1.3 Automatic control..................................................................................................................... 119
4.1.3.1 Automatic sun protection ......................................................................................................... 120
4.1.3.2 Status feedback....................................................................................................................... 124
4.2 Output...................................................................................................................................... 125
4.2.1 Function diagram..................................................................................................................... 126
4.2.2 Time function ........................................................................................................................... 127
4.2.2.1 Staircase lighting ..................................................................................................................... 128
4.2.2.2 Switching ON/OFF delay ......................................................................................................... 129
4.2.2.3 Flashing................................................................................................................................... 130
4.2.3 Connection/logic...................................................................................................................... 131
4.2.4 Scene function......................................................................................................................... 133
4.3 Reaction on …......................................................................................................................... 135
4.3.1 Bus voltage recovery............................................................................................................... 135
4.3.2 ETS reset................................................................................................................................. 137
4.3.3 Download................................................................................................................................. 138
4.3.4 Bus voltage failure................................................................................................................... 139
AAppendix...........................................................................................141
A.1 Scope of delivery..................................................................................................................... 141
A.2 Blind/shutter status byte........................................................................................................... 142
A.3 Code table, 8 bit scene............................................................................................................ 143
A.4 4-bit Dim telegram input........................................................................................................... 144
A.5 Ordering details ....................................................................................................................... 145

ABB i-bus®KNX
General
JRA/S 6.230.3.1 | 2CDC506083D0201 3
1 General
The JRA/S 6.230.3.1 Blind/Roller Shutter Actuator with Binary Inputs provides intelligent building
engineering technology for a variety of room applications and partitioning requirements, for example in
hotel rooms, apartments, schools or public buildings.
Modern buildings require intelligent building engineering technology for safe and efficient operation. Many
buildings worldwide already use networked electrical installations to their fullest potential.
Hotels, hospitals, senior and student residential homes, assisted living accommodation, apartments and
much more: the Blind/Roller Shutter Actuator opens up new possibilities for buildings in the residential,
purpose-built and hotel sectors.
The Blind/Roller Shutter Actuator is designed with exactly these types of spaces in mind. It covers all the
electrical installation requirements for this application and provides the following functions in a compact
form:
•Shading (via blind or shutter)
•Lighting switching
In addition to these basic functions, it can be combined with a presence detector to provide additional
automation features. The fact that the devices communicate via the KNX bus also makes it possible to use
central control functions as well as sending emergency signals from rooms to a control center.
1.1 Using the product manual
This manual provides detailed technical information on the function, installation and programming of the
ABB i-bus®KNX JRA/S 6.230.3.1 Blind/Roller Shutter Actuator with Binary Inputs. The device is explained
using examples.
This manual is divided into the following chapters:
Chapter 1 General
Chapter 2 Device technology
Chapter 3 Commissioning
Chapter 4 Planning and application
Chapter A Appendix

ABB i-bus®KNX
General
42CDC506083D0201 | JRA/S 6.230.3.1
1.1.1 Notes
Notes and safety instructions are represented as follows in this manual:
Note
Tips for usage and operation
Examples
Application examples, installation examples, programming examples
Important
These safety instructions are used as soon as there is danger of a malfunction without risk of damage
or injury.
Caution
These safety instructions are used as soon as there is danger of a malfunction without risk of damage
or injury.
Danger
These safety instructions are used if there is a danger to life and limb with inappropriate use.
Danger
These safety instructions are used if there is an extreme danger to life with inappropriate use.

ABB i-bus®KNX
General
JRA/S 6.230.3.1 | 2CDC506083D0201 5
1.2 Overview of product and functions
The Blind/Roller Shutter Actuator controls blinds or shutters. The input signals are detected via binary
inputs or directly via the sensors connected to the KNX.
The Blind/Roller Shutter Actuator is a modular installation device with a module width of 12 units in Pro M
design for installation in the distribution board. It connects to the ABB i-bus® via a bus connection terminal
at the front. The device can be operated manually, for example during commissioning, by applying an
auxiliary voltage to the bus terminals. Physical address assignment and parametrization are carried out
with the ETS Engineering Tool Software.
The device has six changeover contacts for actuating blinds, shutters or window curtains. They can also
be programmed as switch outputs, e.g.:
•As a blind output: blinds, curtains or shutters
•As a switch output: switching for lights and consumers
It also has twelve floating binary inputs. These are used to control the blind/shutter channels. They can
also be used for the lighting switch function.
The scanning voltage for the binary inputs is provided by the device. The binary inputs are divided into six
groups of two.
Overview of the number and allocation of the inputs and outputs:
Inputs JRA/S 6.230.3.1
Binary via contact scanning
12
Outputs
JRA/S 6.230.3.1
6 A changeover contact (blind) or
6 A switching contact 6

ABB i-bus®KNX
General
62CDC506083D0201 | JRA/S 6.230.3.1

ABB i-bus®KNX
Device technology
JRA/S 6.230.3.1 | 2CDC506083D0201 7
2 Device technology
JRA/S 6.230.3.1
The Blind/Roller Shutter Actuator with
Binary Inputs is a modular installation
(MDRC) device in Pro
Mdesign. It is
intended for installation in the distribution
board on 35 mm mounting rails. Physical
address assignment and device
parametrization are carried out using
ETS and the current appli
cation.
The JRA/S 6.230.3.1 is powered via the
ABB i-bus®and does not require an
additional auxiliary voltage supply.
The device is ready for operation after
connecting the bus voltage.
2.1 Technical data
Power supply Bus voltage 21…32 V DC
Current consumption, bus
Maximum 12 mA (Fan-in 1)
Leakage loss, bus
Maximum 250 mW
Leakage loss, device
Maximum 4.8 W *
* The maximum power consumption of the
device results from the following specifications: Relay 6 A 6 x 0.8 W
Blind output
6 x 6 A, AC3, 250 V AC
Connections
KNX
Via bus connection terminals, 2-fold (red/black)
0.8 mm Ø, single core
Circuits
Ferrules without/with plastic sleeves
TWIN ferrules
Tightening torque
Screw terminal with universal head (PZ 1)
0.2…4 mm² stranded, 2 x (0.2…2.5 mm²)
0.2…6 mm² single core, 2 x (0.2…4 mm²)
without: 0.25…2.5 mm²
with: 0.25…4 mm²
0.5…2.5 mm²
Max. 0.6 Nm
Operating and display elements Push button/LED For assignment of the physical address
Protection degree
IP 20 To DIN EN 60 529
Protection class
II To DIN EN 61 140
Isolation category Overvoltage category III according to EN 60 664-1
Pollution degree 2 to EN 60 664-1
KNX safety extra low voltage
SELV 24 V DC
2CDC071001S0017

ABB i-bus®KNX
Device technology
82CDC506083D0201 | JRA/S 6.230.3.1
Temperature range Operation
Transport
Storage
-5 °C…+45 °C
-25…+70 °C
-25…+55 °C
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, Pro
M
Dimensions 90 x 216 x 64.5 mm (H x W x D)
Mounting width in space units 12x 18 mm modules
Mounting depth 64.5 mm
Installation On 35 mm mounting rail To DIN EN 60 715
Mounting position any
Weight
0.55 kg
Housing/color
Plastic housing, gray
Approvals
KNX to EN 50 090-1, -2
Certification
CE marking
In accordance with the EMC directive and low
voltage directive
2.1.1 Binary inputs
Rated values
Number 121)
Unscanning voltage 32 V, pulsed
Inscanning current 0.1 mA
Inscanning current when switching on Maximum 355 mA
Permitted cable length
≤ 100 m one-way, at cross-section 1.5 mm² even
when the core is routed in a multi-control cable
1) All binary inputs are internally connected to the same potential.

ABB i-bus®KNX
Device technology
JRA/S 6.230.3.1 | 2CDC506083D0201 9
2.1.2 Rated current output 6 A
Rated values
Number
6 or 12 contacts
U
n
rated voltage
250/440 V AC (50/60 Hz)
I
n
rated current (per output)
6 A
Switching currents
AC3* operation (cos ϕ= 0.45)
To EN 60 947-4-1 6 A/230 V
AC1* operation (cos ϕ= 0.8)
To EN 60 947-4-1 6 A/230 V
Fluorescent lighting load as per
DIN EN 60 669-1 6 A/250 V (35 µF)1)
Minimum switching capacity
20 mA/5 V
10 mA/12 V
7 mA/24 V
DC current switching capacity (resistive load)
6 A/24 V=
Service life
Mechanical service life > 107
Electronic service life
To IEC 60 947-4-1
AC1* (240 V/cos ϕ = 0.8)
> 105
AC3* (240 V/cos
ϕ =
0.45)
> 1.5 x 104
AC5a* (240 V/cos ϕ = 0.45) > 1.5 x 104
Switching times2)
Maximum relay position change per output and
minute if only one relay is switched.
2,683
1) The maximum inrush-current peak may not be exceeded, see chapter 2.1.3.
2) The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. The typical relay delay is approx. 20 ms.
*What do the terms AC1, AC3 and AC5a mean?
In intelligent installation systems, different switching capacities and performance specifications that are
dependent on the special applications have become established in domestic and industrial installations.
These performance specifications are rooted in the respective national and international standards. The
tests are defined to simulate typical applications, e.g. motor loads (industrial) or fluorescent lamps
(residential).
Specifications AC1 and AC3 are switching performance specifications which have become established in
the industrial field.
Typical application:
AC1 – Non-inductive or slightly inductive load, resistive furnaces (relates to switching of ohmic/resistive
loads)
AC3 – Squirrel-cage motors: starting, switching off motors during running (relates to (inductive) motor load)
AC5a – Switching of electric discharge lamps
These switching performances are defined in the standard EN 60947-4-1 Contactors and motor-starters -
Electromechanical contactors and motor-starters. The standard describes starters and/or contactors that
were originally used primarily in industrial applications.

ABB i-bus®KNX
Device technology
10 2CDC506083D0201 | JRA/S 6.230.3.1
2.1.3 Lamp load output 6 A
Lamps
Incandescent lamp load
1200 W
Fluorescent lamps T5/T8
Uncompensated
Parallel compensated
DUO circuit
800 W
300 W
350 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer 800 W
1000 W
Halogen lamps 230 V 1000 W
Dulux lamp
Uncompensated
Parallel compensated 800 W
800 W
Mercury-vapor lamp
Uncompensated
Parallel compensated
1000 W
800 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150
µ
s)
200 A
Maximum peak inrush current Ip(250 µs) 160 A
Maximum peak inrush current Ip(600 µs) 100 A
Device type Application Max. number of
Group objects Max. number of
Group addresses Max. number of
assignments
JRA/S 6.230.3.1 Shutter Actuator binary input 6f12f/... 255 255 255
* … = Current version number of the application. Please refer to the software information on our website for this purpose.
Note
ETS and the current version of the device application are required for programming.
The current version of the application is available for download at www.abb.com/knx. After import into
ETS, it is available in ETS under ABB/Blind/Switch.
The device does not support the locking function of a KNX device in ETS. Using a BCU code to inhibit
access to all the project devices has no effect on this device. Data can still be read and programmed.

ABB i-bus®KNX
Device technology
JRA/S 6.230.3.1 | 2CDC506083D0201 11
2.2 Connection diagram
JRA/S 6.230.3.1
1
Label carrier
2
Programming LED
3
Programming button
4
Bus connection terminal
5
Blind/shutter (A, B)
6
Blind/shutter (C, D)
7
Blind/shutter (E, F)
8
Blind/shutter (G, H)
9
Blind/shutter (I, J)
10
Blind/shutter (K, L)
11
Binary inputs (g, h, i, j, k, l)
12
Binary inputs (a, b, c, d, e, f)
2CDC072027F0016

ABB i-bus®KNX
Device technology
12 2CDC506083D0201 | JRA/S 6.230.3.1
2.3 Dimension drawing
2CDC072028F0016

ABB i-bus®KNX
Device technology
JRA/S 6.230.3.1 | 2CDC506083D0201 13
2.4 Mounting and installation
The device is a modular installation device for quick installation in distribution boards on 35 mm mounting
rails to DIN EN 60 715.
The installation position can be selected as required.
Electrical connection is via screw terminals. The device connects to the bus via the supplied bus
connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the bus voltage.
The devices must be accessible for the purposes of operation, testing, visual inspection, maintenance and
repair in compliance with DIN VDE 0100-520.
Commissioning requirement
In order to commission the device, a PC with ETS, as well as a connection to the ABB i-bus®,
e.g. via a KNX interface, is required.
The device is ready for operation after the bus voltage is applied. No additional auxiliary voltage
is required.
Mounting and commissioning may only be carried out by electrical specialists. The applicable standards,
directives, regulations and specifications for the country in question must be observed when planning and
setting up electrical installations and security systems for intrusion and fire detection.
•Protect the device from damp, dirt and damage during transport, storage and operation.
•Only operate the device within the specified technical data!
•The device should only be operated in an enclosed housing (distribution board)!
•Switch off the device supply voltage before mounting.
Danger
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.

ABB i-bus®KNX
Device technology
14 2CDC506083D0201 | JRA/S 6.230.3.1
Supplied state
The device is supplied with the physical address 15.15.255. The application is pre-installed.
Hence, only group addresses and parameters need to be loaded during commissioning.
The complete application can be reloaded if required. Downloads may take longer after a change of
application or a discharge.
Allocation of the physical address
The assignment and programming of the physical address are carried out in ETS.
The device features a button for assignment of the physical device address. The red LED lights up
after the button has been pushed. It switches off as soon as ETS has assigned the physical address or the
button is pressed again.
Download response
Depending on the PC that is used, the progress bar for the download may take up to one and a half
minutes to appear, due to the complexity of the device.
Cleaning
The voltage supply to the device must be switched off before cleaning. If devices become dirty, they can
be cleaned using a dry cloth or a cloth dampened with a soapy solution. Never use corrosive agents or
solutions.
Maintenance
The device is maintenance-free. In the event of damage (e.g. during transport and/or storage), do not carry
out any repairs.

ABB i-bus®KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 15
3 Commissioning
3.1 Supplied state
In the supplied state, all outputs are set to Blind mode.
All inputs are set to 2-button blind operation mode, with the first input assigned to "up" and the second to
"down".
Input pairs are always assigned to the output with the same letter (e.g. a, b to A, B)
This means that the outputs can be switched as soon as the bus voltage is applied:
Closing the contact at input a closes relay A, raising the connected blind. Closing the contact at input b
closes relay B, lowering the connected blind.
3.2 Overview
The Shutter Actuator binary input 6f12f application and ETS Engineering Tool Software 4.2 or later are
used to parametrize the device. The application provides the device with a comprehensive and flexible
range of functions. The standard settings allow simple commissioning. The functions can be expanded
if required.
The available functions are as follows:
Binary input
Twelve binary inputs are available, e.g. Light ON/OFF in the entrance area of the
room, in the bathroom and for freestanding or table lamps, move blinds UP/DOWN,
and send an emergency signal.
Blind/shutter Six blind outputs are available. They can also be set as switch outputs.
3.2.1 Input functions
The following table provides an overview of the functions possible with the device inputs and the
Shutter Actuator binary input 6f12f application:
Input functions
a…l
Switch sensor
Switch/dimming sensor
Blind sensor
Value/forced operation
= Function is supported

ABB i-bus®KNX
Commissioning
16 2CDC506083D0201 | JRA/S 6.230.3.1
3.2.2 Output functions
The following table provides an overview of the functions possible with device outputs and the
Shutter Actuator binary input 6f12f application:
Output functions Blind/shutter output
AB, CD, EF, GH, IJ, KL Switch output
A, C, E, G, I, K
Time
Staircase lighting
Switching ON/OFF delay
Flashing
Scene
Assignment of the output to scenes
Bit logic
AND/OR/XOR or GATE
Forced operation
1 bit or 2 bit
Shading control
Automatic Sun Protection
Safety function
= Function is supported

ABB i-bus®KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 17
3.3 Parameters
The ETS Engineering Tool Software is used to parametrize the device. The application is available in ETS
under ABB/Blind/Switch.
This chapter describes the device parameters using the parameter windows. Parameter windows are
structured dynamically so that further parameters are enabled depending on the parametrization and
function of the outputs.
The default values of the parameters are underlined, e.g.:
Options: Yes
No
Note
The device features several inputs/outputs. As the functions are identical for all inputs/outputs, they will
be explained using input/output A/B as an example.

ABB i-bus®KNX
Commissioning
18 2CDC506083D0201 | JRA/S 6.230.3.1
3.3.1 General parameter window
The higher-level parameters can be set in this parameter window.
Table of contents
Other ABB Controllers manuals

ABB
ABB TZIDC-110 User manual

ABB
ABB IRC5 Compact User manual

ABB
ABB i-bus KNX User manual

ABB
ABB Welcome M2300 User manual

ABB
ABB i-bus FCC/S 1 1 Series User manual

ABB
ABB ControlMaster CM15 Training manual

ABB
ABB COMMANDER C355 User manual

ABB
ABB PS D75 840 Series Technical specifications

ABB
ABB ACS880-07 User manual

ABB
ABB FC/S 1.1 User manual