ABB Relion 605 Series Instructions for use

Relion®605 series
Relion®605 series
Feeder/Motor protection and control /
Feeder/Motor protection
REF601/REJ601/REM601
Application Manual
Relion®605 series


Document ID: 1MDU07212-YN
Issued: 2014-08-11
Revision: D
Product version: 2.2FP1
© Copyright 2014 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB India Limited,
Distribution Automation
Maneja,
Vadodara, India
Telephone: +91 265 2604386
Fax: +91 265 2638922
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure
and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole
responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.

Table of contents
REF601 / REJ601 / REM601 1
Application Manual
Table of contents
Section 1 General..................................................................5
1.1 This manual.....................................................................................................5
1.2 Intended audience...........................................................................................5
1.3 Document revision history...............................................................................5
1.4 Document symbol and conventions ................................................................6
Section 2 REM601 overview.......Error! Bookmark not defined.
2.1 Overview ............................................................ Error! Bookmark not defined.
2.2 Product version history....................................................................................8
2.3 Operation Functionality ...................................................................................8
2.3.1 Relay functions...........................................................................................8
2.3.2 Optional function ......................................................................................10
2.4 Other Functions.............................................................................................10
2.4.1 Self-Supervision .......................................................................................10
2.4.2 Fault record and Trip counter...................................................................11
2.4.3 Event Log .................................................................................................12
2.4.4 Real Time Clock.......................................................................................15
2.4.5 Access Control .........................................................................................15
2.4.6 Power-ON sequence................................................................................15
Section 3 Technical Data.....................................................16
Section 4 Protection and Control Function...........................16
4.1 Three Phase Overcurrent Protection ............................................................16
4.1.1 Functionality .............................................................................................16
4.1.2 Principle of Operation...............................................................................16
4.1.3 Setting range of Three Phase Overcurrent Protection.............................16

Table of contents
2REF601 / REJ601 / REM601
Application Manual
4.2 Earth Fault Protection................................................................................... 17
4.2.1 Functionality ............................................................................................ 17
4.2.2 Principle of Operation.............................................................................. 17
4.2.3 Setting range of Earth fault Overcurrent Protection................................ 18
4.3 Three Phase Inrush Detector ............................. Error! Bookmark not defined.
4.4 Negative-sequence overcurrent protection .................................................. 18
4.4.1 Functionality ............................................................................................ 18
4.4.2 Principle of Operation.............................................................................. 19
4.5 Phase discontinuity protection ..................................................................... 19
4.5.1 Functionality ............................................................................................ 19
4.5.2 Principle of Operation.............................................................................. 19
4.6 Circuit breaker failure protection .................................................................. 20
4.6.1 Functionality ............................................................................................ 20
4.6.2 Principle of Operation.............................................................................. 20
4.7 Setting groups .............................................................................................. 22
4.8 Auto-reclose function.................................................................................... 22
4.8.1 Functionality ............................................................................................ 22
4.8.2 Principle of operation .............................................................................. 23
4.9 Thermal overload protection ........................................................................ 26
4.9.1 Functionality ............................................................................................ 26
4.9.2 Principle of operation .............................................................................. 26
4.10 Protection characteristics ............................................................................. 33
4.10.1 Time / Current characteristics ................................................................. 36
4.10.2 IEC 60255-3 IDMT characteristic............................................................ 36
4.10.3 ANSI C37.112 IDMT characteristic ......................................................... 37
4.10.4 RI type characteristic............................................................................... 38
4.11 Configurable Binary Outputs ........................................................................ 38
4.12 Configurable LED ......................................................................................... 40
4.13 Configurable Binary Inputs........................................................................... 41

Table of contents
REF601 / REJ601 / REM601 3
Application Manual
4.14 Breaker control and Trip command operation...............................................42
4.15 Trip Circuit Supervision .................................................................................42
Section 5 Use of LHMI.........................................................44
5.1 Overview .......................................................................................................44
5.1.1 LED’s........................................................................................................44
5.1.2 LCD display..............................................................................................45
5.1.3 Navigation ................................................................................................45
5.1.4 Authorization ............................................................................................46
5.1.5 Configuration status .................................................................................47
5.2 LHMI menu navigation ..................................................................................48
5.2.1 Default screen ..........................................................................................48
5.2.2 Main menu ...............................................................................................48
5.2.3 Menu –Measurement ..............................................................................49
5.2.4 Menu –Fault record .................................................................................50
5.2.5 Menu - Events ..........................................................................................50
5.2.6 Menu –Setting .........................................................................................51
5.2.7 Menu –Configuration...............................................................................53
5.2.8 Menu –Test .............................................................................................61
5.2.9 Access level .............................................................................................66
5.2.10 Version information ..................................................................................66
Section 6 Installation ...........................................................67
6.1 Unpacking and inspecting the device ...........................................................67
6.2 Storage..........................................................................................................67
6.3 Checking environmental condition and mounting space ..............................67
6.4 Relay wiring...................................................................................................68
6.5 Relay mounting and dimensions ...................................................................68
6.6 Terminal diagram ..........................................................................................71
6.7 Relay ordering information ............................................................................73

Table of contents
4REF601 / REJ601 / REM601
Application Manual
6.8 Accessories and ordering data..................................................................... 74
6.9 Setting table ................................................................................................. 75
6.10 Earthing of relay and Bonding of sensor cable shield.................................. 81
6.10.1 Earthing of relay ...................................................................................... 81
6.10.2 Shield connection at relay side (Sensor variant)..................................... 82

1MDU07212-YN Rev. D Section 1
General
REF601 / REJ601 / REM601 5
Application Manual
Section 1 General
1.1 This manual
This manual contains application and functionality descriptions and connection
diagrams, input and output signals, setting parameters and technical data. The
manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service. The manual can
also be used when calculating settings. The manual provides instructions on how to
operate the IED during normal service once it has been commissioned and to find
out how to handle disturbances or view calculated and measured network data in
order to determine the cause of a fault.
1.2 Intended audience
This manual addresses system engineers, installation and commissioning
personnel, who use technical data during engineering, installation and
commissioning, and in normal service. System engineer must have a thorough
knowledge of protection systems, protection equipment, protection functions and
the configured functional logics in the IEDs. The installation and commissioning
personnel must have a basic knowledge in handling electronic equipment.
This manual addresses Protection and control engineer responsible for planning,
pre-engineering and engineering. The protection and control engineer must be
experienced in electrical power engineering and have knowledge of related
technology, such as communication and protocols.
The manual also addresses the operator, who operates the IED on a daily basis. The
operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
1.3 Document revision history
Document
revision/date
Product version
Document history
A / 28.09.2012
2.1
Release of REF601/REJ601 with
conventional current transformer
B / 28.03.2013
2.2
Common version for REF601 /REJ601
CT and REF601 Sensor variant
C / 23.06.2014
2.2FP1
Release of REF601/REJ601 with
functionality for version 2.2 FP1
D / 11.08.2014
2.2FP1
Release of REM601 with functionality
for version 2.2 FP1

Section 1 1MDU07212-YN Rev. D
General
6REF601 / REJ601 / REM601
Application Manual
1.4 Document symbol and conventions
This publication includes the following icons that point out safety-related
conditions or other important information:
Safety indication symbols
The information icon alerts the reader to important facts and
conditions.
Non-observance can result in death, personal injury or substantial
property damage
Breaking the sealing tape on the upper handle of the device will
result in loss of warranty and proper operation will no longer be
guaranteed.
When the plug-in unit has been detached from the case, do not
touch the inside of the case. The relay case internals may contain
high voltage potential and touching these may cause personal
injury.
The warning icon indicates the presence of a hazard which could
result in personal injury.
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
National and local electrical safety regulations must always be
followed.
The device contains components which are sensitive to Electrostatic
discharge. Unnecessary touching of electronic components must
therefore be avoided.
Only a competent electrician is allowed to carry out the electrical
installation.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

1MDU07212-YN Rev. D Section 2
REF601/REJ601/REM601 overview
REF601 / REJ601 / REM601 7
Application Manual
Section 2 REF601/REJ601/REM601 overview
2.1 Overview
REF601/REJ601 is a dedicated feeder protection relay, intended for the protection
of utility substations and industrial power systems, in primary and secondary
distribution networks. Similarly REM601 is a dedicated motor protection relay,
intended for the protection of medium voltage and low voltage asynchronous
motors in manufacturing and process industry. REF601/REJ601/REM601 are the
member of ABB’s Relion ®product family and part of its 605 series.
The relay provides an optimized composition of protection, monitoring and control
functionality in one unit, with the best performance usability in its class and is
based on ABB’s in-depth knowledge of protection and numerical technology.
The common features of REF601/REJ601/REM601 includes:
Compact size and ease of use
Standard 1A or 5A CT input for phase current measurement
Alternate support for sensor input for phase current measurement
Earth current measurement internally or externally through CBCT
Local and remote control of circuit breaker
Trip Circuit Supervision and relay internal supervision
Lockout function
100 event logs with date and time stamping
Five analogue fault records
Non-resettable trip counter
On-line current measurements in primary value
Comprehensive local HMI
Universal auxiliary supply
Optional MODBUS RTU or IEC 60870-5-103 communication
Non-volatile memory for setting and fault records
User selectable rated frequency 50 / 60 Hz
Configurable binary inputs, outputs and alarm LEDs
Multi language support for local HMI
Two setting groups

Section 2 1MDU07212-YN Rev. D
REF601/REJ601/REM601 overview
8REF601 / REJ601 / REM601
Application Manual
The protection features of REF601/REJ601 includes:
Three-stage overcurrent protection
Two-stage earth-fault protection
Inrush detection for stability during transformer charging
Thermal overload protection
Negative sequence overcurrent
Phase discontinuity protection
Circuit breaker failure protection
Multi shot Auto recloser functionality for overhead line
The protection features of REM601 includes:
Three-phase thermal overload protection
Negative phase sequence protection
Phase discontinuity or single phasing protection and phase reversal protection
Motor start-up protection or stalling protection and repetitive start protection
Short circuit and earth fault protection
Motor load jam or locked rotor protection
Under current protection
Emergency restart function
Circuit breaker failure protection
2.2 Product version history
Product version
Release date
Product History
1.0
20.03.2009
Product released
1.0 SP1
21.08.2009
Service Pack released
2.0
04.04.2012
Version 2.0 released
2.1
28.09.2012
Version 2.1 release with support of
conventional current transformer
2.2
28.03.2013
Common version release for REF601 /
REJ601 CT and REF601 Sensor variant
2.2 FP1
23.06.2014
REF601 / REJ601 Version 2.2 FP1 released
2.2 FP1
11.08.2014
REM601 Version 2.2 FP1 released
2.3 Operation Functionality
2.3.1 Relay functions
REF601/REJ601/REM601 offers pre-configured functionality which facilitates
easy and fast commissioning of switchgear. To emphasize the simplicity of relay’s
usage, only application specific parameters needs to set within the relay’s intended
area of application.
The relay offers protection, control, measurement and condition monitoring
functionality. The table indicates the functions supported by the IED

1MDU07212-YN Rev. D Section 2
REF601/REJ601/REM601 overview
REF601 / REJ601 / REM601 9
Application Manual
Table 1: Relay functions
Test
Related products
REJ601/
REF601
REJ601/
REF601
REJ601/
REF601
REM601
REM601
Functionality
ANSI
IEC
B
C
D
B
C
Protection
Non-directional overcurrent
protection, low-set stage
51
3I>
●
●
●
●
●
Non-directional overcurrent
protection, high-set stage
50-1
3I>>
●
●
●
●
●
Non-directional overcurrent
protection, instantaneous stage
50-2
3I>>>
●
●
●
●
●
Earth-fault protection, low-set
stage
51N
Io>
●
●
●
●
●
Earth-fault protection, high-set
stage
50N
Io>>
●
●
●
●
●
Three phase transformer inrush
detector
68
3I2f>
●
●
●
-
-
Three-phase thermal protection
for feeders, cables, distribution
transformers and motor
49
3Ith>
-
●
●
●
●
Phase discontinuity / Single
phasing protection
46PD
I2/I1>
-
●
●
●
●
Negative-sequence overcurrent
protection
46
I2>
-
-
●
●
●
Phase reversal protection
46R
I2R>
-
-
●
●
●
Motor startup supervision /
Stalling protection with provision
of speed switch input
Repetitive start up protection and
restart inhibit
51LRS/
14/48/66
I2t n<
-
-
-
●
●
Locked rotor protection during
running
50-2
3I>>>
-
-
-
●
●
Under current protection
37
3I<
-
-
-
●
●
Emergency restart
ESTART
ESTART
-
-
-
●
●
Circuit breaker failure protection
51BF/
51NBF
3I>/Io>
BF
-
●
●
●
●
Master trip
86
Master
Trip
●
●
●
●
●
Two setting group
-
-
●
●
●
●
●
Control (Function available in REF601 and REM601 Application configuration C )
Breaker control functionality
I <-> O
CB
I <-> O
CB
●
●
●
-
●
Auto-reclosing
79
O -> I
-
-
●
-
-

Section 2 1MDU07212-YN Rev. D
REF601/REJ601/REM601 overview
10 REF601 / REJ601 / REM601
Application Manual
Table 1: Relay functions, continue
Test
Related products
REJ601/
REF601
REJ601/
REF601
REJ601/
REF601
REM601
REM601
Functionality
ANSI
IEC
B
C
D
B
C
Condition monitoring
Trip circuit supervision
TCM
TCS
●
●
●
●
●
Measurement
Three-phase current
measurement
3I
3I
●
●
●
●
●
Residual current measurement
In
Io
●
●
●
●
●
Negative phase sequence
current
I2
I2
-
-
●
●
●
Thermal level
ϑ
ϑ
-
●
●
●
●
Operation counter
-
-
●
●
●
●
●
Motor run time
-
-
-
-
-
●
●
Latest motor start up max.
current
-
-
-
-
-
●
●
Latest motor start up time
-
-
-
-
-
●
●
Time to next possible motor start
up
-
-
-
-
-
●
●
● = Included
2.3.2 Optional function
The relay supports two optional communication MODBUS RTU and IEC 60870-5-
103, on a two wire RS485 interface.
2.4 Other Functions
2.4.1 Self-Supervision
The IED is provided with an extensive self-supervision system which continuously
supervises the software and the electronics. It handles run-time fault situations and
informs the user about a fault via the LHMI.
At normal condition (no internal fault), the green Ready LED glow and the self-
supervision output contact is closed. When an internal fault is detected in the IED,
the green LED ceases to glow and the self-supervision contact opens. Also, all
other outputs are released.
Figure 1: Behavior of contact assigned for Unit ready / IRF
5
6
BO4
(IRF)
XK2:
5
6
BO4
(IRF)
XK2:
Normal condition
IRF condition or no
auxiliary power

1MDU07212-YN Rev. D Section 2
REF601/REJ601/REM601 overview
REF601 / REJ601 / REM601 11
Application Manual
Internal fault indications have the highest priority on the LHMI. None of other
LHMI indications can override the internal fault indication. An indication about the
fault is shown as a message on the LHMI.
The internal fault code indicates the type of internal IED fault
Table 2: Internal fault indications and fault codes
Internal fault code
Type of fault
IRF 008
Internal supply voltage check
IRF 016
Power on “EEPROM“ check fault
IRF 032
Runtime “EEPROM“ check fault
IRF 064
Gain check fault
The user can try to eliminate the fault by restarting the IED. If the fault is found to
be permanent, the IED stays in internal fault mode.
2.4.2 Fault record and Trip counter
The relay stores records of analog values for last five trip events in non-volatile
memory. The fault recording is triggered by the trip signal of a protection function.
Each fault record includes the rms current values of fundamental component for all
three phases and the neutral current at five different times along the trip event.
Figure 2: Fault record
These records enable the user to analyze the five most recent power system events.
The oldest recording is lost when a new fault recording is made.

Section 2 1MDU07212-YN Rev. D
REF601/REJ601/REM601 overview
12 REF601 / REJ601 / REM601
Application Manual
Additionally, the relay count the number of phase fault trip and earth fault trip into
dedicated trip counters. These trip counters cannot be reset by the user and are
stored in nonvolatile memory.
The values of fault records and trip counters are accessible locally LHMI and
remotely via communication interface of the relay.
2.4.3 Event Log
To collect sequence-of-events (SoE) information, the relay incorporates a non-
volatile memory to store 100 event logs. Each event log includes type of event
along with date and time stamping.The event logs are stored sequentially, the most
recent being first and so on.
The SoE information are accessible locally via LHMI and remotely via
communication interface of the relay.
Table 3: List of event types and related description
Sr.
No.
Event type
Description
Data considered
1
Power supply
presence
Unit ready contact activation will be stored as
an event. This unit ready contact is activated
when power supply is on and no internal
relay fault detected
Unit Ready
2
Trip circuit
supervision
When trip circuit becomes faulty, an event of
trip circuit faulty will be recorded. & when it
becomes health shall also record it as an
event
TCS fault ↑
TCS fault ↓
3
Setting
parameter
change
Settings (I>,I>>,I>>>,Io>,Io>> and
t>,t>>,t>>>,to>,to>>) alteration will be
captured as an event without setting value.
I>, I>>, I>>>, Io>,
Io>>, t>, t>>,t>>>,
to>, to>>
Circuit breaker failure protection settings -
IBF,I0BF,t Retrip,t Backup
Icbfp,I0cbfp,
t Retrip, t Backup
On change of Count value
Count Value
Negative sequence setting change - I2> and
tI2>
I2>, tI2>
Phase discontinuity setting change - I2/I1>
and tI2/I1>
I2/I1>, tI2/I1>
Thermal protection setting change-
ϑ0,Ib, t↑, t↓s, t↓r, ϑalm, ϑtrip, ϑstrinhibit,
ϑEM
ϑ0,Ib, t↑, t↓s, t↓r,
ϑalm, ϑtrip,
ϑstrinhibit, ϑEM
Under current parameter change - 3I< and
t3I<
3I< , t3I<
Phase reversal setting change –I2R> and
tI2R>
I2R> , tI2R>
Auto resclose function setting change -
Mode,CB Ready, Activate t Shot, Pulse tp,
cycle t1, cycle t2,cycle t3, cycle t4, Reclaim
tr, Block tb
O→I - Mode, CB
Ready, Activate t #
of Cycle, Pulse tp,
cycle t1, cycle t2,
cycle t3, cycle t4,
Reclaim tr, Block tb
Motor startup and stall protection parameter
change I start> ,Istartup, t startup,
t lockrotor, Max Strt, tn, Restrain 68M
I start> ,Istartup,
t startup,
t lockrotor,
Max Strt, tn,
Restrain 68M

1MDU07212-YN Rev. D Section 2
REF601/REJ601/REM601 overview
REF601 / REJ601 / REM601 13
Application Manual
Table 3: List of event types and related description, continue
Sr.
No.
Event type
Description
Data considered
4
Protection start
Start event by I>,I>>, I>>> ,Io> OR Io>> will
be captured as individual event for both
rising and dropping
Start I> ↑
Start I>> ↑
Start I>>> ↑
Start I0> ↑
Start I0>> ↑
Start I> ↓
Start I>> ↓
Start I>>> ↓
Start I0> ↓
Start I0>> ↓
On I2> start both rising and falling signal
Start I2> ↑
Start I2> ↓
On I2/I1> start both rising & falling signal
Start I2/I1> ↑
Start I2/I1> ↓
On thermal alarm output signal for both rising
& falling signal
3Ith> Alarm ↑
3Ith> Alarm ↓
On phase reversal start
I2R> Start ↑
I2R> Start ↓
On start of motor output activation and
deactivation
I2tn< Mstr ↑
I2tn< Mstr ↓
5
Protection trip
In the event of Tripping, which protection
stage (I>, I>>, I>>>, Io> and Io>>) caused
trip will be captured as an event information.
Event shall be available for both rising &
dropping
Trip I> ↑
Trip I>> ↑
Trip I>>> ↑
Trip I0> ↑
Trip I0>> ↑
Trip I> ↓
Trip I>> ↓
Trip I>>> ↓
Trip I0> ↓
Trip I0>> ↓
On I2> trip both rising & falling signal
Trip I2> ↑
Trip I2> ↓
On I2/I1> trip both rising & falling signal
Trip I2/I1> ↑
Trip I2/I1> ↓
On undercurrent trip
3I< Trip ↑
3I< Trip ↓
On phase reversal trip
I2R> Trip ↑
I2R> Trip ↓
On trip output activation & deactivation due
to either stall protection or I2t protection
tall Trip ↑
Stall Trip ↓
I2t Trip ↑
I2t Trip ↓
On thermal trip output signal for both rising &
falling signal
3Ith> Trip ↑
3Ith> Trip ↓
6
IRF
“IRF”–internal relay fault shall be captured
as an event.
IRF codes
7
Breaker open
When breaker open cmd
Breaker Open
8
Breaker close
When breaker close cmd
Breaker Close
9
Remote trip
When remotely trip command issued
Remote Trip
10
Reset
When reset of protection trip, LEDs and
screen done
Reset

Section 2 1MDU07212-YN Rev. D
REF601/REJ601/REM601 overview
14 REF601 / REJ601 / REM601
Application Manual
Table 3: List of event types and related description, continue
Sr.
No.
Event type
Description
Data considered
11
Blocking
When blocking by binary input, And shall
have event for both rising & dropping
BI Blocking ↑
BI Blocking ↓
12
Breaker
position
When breaker open, close or maintenance
position sensed by associated binary input
CB POS CLS ↑
CB POS CLS ↓
CB POS OPN ↑
CB POS OPN ↓
CB Maint ↑
CB Maint ↓
13
Memory read
fail
In case unable to read Event from EEPROM,
a message i.e. ”Memory Read Fail”will be
displayed for that particular event
Memory Read Fail
14
Hardware test
When in test menu, initiate hardware test
Hardware Test
15
Binary output
test
When in test menu , initiate binary output test
BO Test
16
Functional test
When in test menu, initiate protection
function test
Functional Test
17
Power Off
When binary input is mapped to register
power off situation & power supply to IED
goes OFF.
Power Off
18
Breaker Failure
Stage 1, 2
output
On breaker failure receive stage 1 output
BF Stage1 ↑
BF Stage2 ↑
BF Stage1 ↓
BF Stage2 ↓
19
Breaker Failure
receive trip
output
On breaker failure receive trip output
BF RecTrip BO↑
BF RecTrip BO↓
20
Breaker Failure
receive trip
Acceptance
On Acceptance of BF RecTrip input
BF RecTrip Acp ↑
21
Setting group
change
On change of setting group from one to
another
Setting SG Edt.
Setting SG No.
Setting SG Act.
22
Thermal reset
On reset of thermal function either from BI,
LHMI or communication.
3Ith> Reset
23
Thermal block
breaker close
On breaker close blocking output signal for
both rising & falling signal
3Ith> Blk Cls ↑
3Ith> Blk Cls ↓
On breaker close blocking output signal for
both rising & falling signal due to cumulative
startup protection
I2tn< BlkCl ↑
I2tn< BlkCl ↓
24
O→I close
On O→I close output
O→I close 1 ↑
O→I close 2 ↑
O→I close 3 ↑
O→I close 4 ↑
25
O→I FinalTr
On O→I final trip output
O→I FinalTr ↑
26
O→I Blocked
On O→I blocked output
O→I Blocked ↑
O→I Blocked ↓
27
O→I Stopped
On O→I stopped internal signal generated
O→I Stopped ↑
28
O→I Started
On O→I started internal signal generated
O→I Started ↑
29
Signal 1, 2, 3
On signal 1, 2, 3 output activation and
deactivation respectively
Signal 1 ↑
Signal 2 ↑
Signal 3 ↑
Signal 1 ↓
Signal 2 ↓
Signal 3 ↓
This manual suits for next models
3
Table of contents
Other ABB Controllers manuals

ABB
ABB IRC5 Compact User manual

ABB
ABB COMMANDER 310 User manual

ABB
ABB IRC5 Compact User guide

ABB
ABB IRC5 Compact User manual

ABB
ABB COM600 series User manual

ABB
ABB Advant Controller 450 User manual

ABB
ABB C310 Operating instructions

ABB
ABB MS132-K User manual

ABB
ABB NIESSEN 2260 Series User manual

ABB
ABB ControlMaster CM15 User manual

ABB
ABB ACQ580 Troubleshooting guide

ABB
ABB ACS880-07 User manual

ABB
ABB C505 User manual

ABB
ABB ControlMaster CM10 User manual

ABB
ABB RHD Series Original operating manual

ABB
ABB ES/S 4.1.2.1 User manual

ABB
ABB MS165 User manual

ABB
ABB RHDE250 User manual

ABB
ABB ControlMaster CM15 Training manual

ABB
ABB MS132 User manual