14
Terminal data for the power cables
Notes:
• The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load.
• The terminals do not accept a conductor that is one size larger than the maximum specified wire size.
• The maximum number of conductors per terminal is 1.
Weights and free space requirements
This table shows the requirements for the ambient conditions when the drive is in operation (installed for stationary use).
039A-4 38.0 34.0 38.0 34.0 18.5 25.0 OFAF000H50 170M1565 JJS-60 3×10 + 10 8 R3
046A-4 45.0 40.0 45.0 40.0 22.0 30.0 OFAF000H63 170M1566 JJS-60 3×10 + 10 8 R3
062A-4 62 52 62 52 30 40 OFAF000H80 170M1567 JJS-80 3×25 + 16 4 R4
073A-4 73 65 73 65 37 50 OFAF000H100 170M1568 JJS-100 3×35 + 16 2 R4
088A-4 88 77 88 77 45 60 OFAF000H100 170M1569 JJS-110 3×50 + 25 1/0 R5
106A-4 106 96 106 96 55 75 OFAF00H125 170M3817 JJS-150 3×70 + 35 2/0 R5
145A-4 145 124 145 124 75 100 OFAF00H160 170M3817 JJS-200 3×95 + 50 3/0 R6
169A-4 169 156 169 156 90 125 OFAF0H250 170M5809 JJS-225 3×120 + 70 250 MCM R7
206A-4 206 180 206 180 110 150 OFAF1H315 170M5810 JJS-300 3×150 + 70 300 MCM R7
246A-4 246 240 246 240 132 200 OFAF1H355 170M5812 JJS-350 2×(3×70+35) 2×2/0 R8
293A-4 293 260 293 260 160 250 OFAF2H425 170M6812D JJS-400 2×(3×95+50) 2×3/0 R8
363A-4 363 361 363 361 200 300 OFAF2H500 170M6814D JJS-500 2×(3×120+70) 2×250
MCM
R9
430A-4 430 414 430 414 250 350 OFAF3H630 170M8554D JJS-600 2×(3×150+70) 2×300
MCM
R9
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 listing.
3) The drive is suitable for use on a circuit capable of delivering not more than 100000 symmetrical amperes (rms) at 480 V
maximum when protected by the fuses given in this table.
4) Refer to
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives
(3AXD50000645015 [English]) for additional UL
fuses and circuit breakers that can be used as branch circuit protection.
Frame
size
T1/U, T2/V, T3/W, L1, L2, L3, R-, R+/UDC+ PE
Min. wire size (solid/
stranded)
Max. wire size (solid/
stranded)
Tightening torque Max. wire size (solid/
stranded)
Tightening torque
mm2AWG mm2AWG N·m lbf·ft mm2AWG N·m lbf·ft
R1 0.2/0.2 24 6/4 10 1.0 0.7 16/16 6 1.5 1.1
R2 0.5/0.5 20 16/16 6 1.5 1.1 16/16 6 1.5 1.1
R3 0.5/0.5 20 35/35 2 3.5 2.6 35/35 2 1.5 1.1
R4 0.5/0.5 20 50 1 4.0 3.0 35/35 2 1.5 1.1
R5 6 10 70 2/0 5.6 4.1 -
R6 25 4 150 300 MCM 30 22.1 180 1)
1) Applicable only to 230 V drives. In 400/480 V drives, cable clamp is used for grounding.
350 MCM 1) 9.8 1) 7.2 1)
R7 95 3/0 240 500 MCM 40 29.5 180 1) 350 MCM 1) 9.8 1) 7.2 1)
R8 2×50 2×1/0 2×150 2×300 MCM 40 29.5 2×180 1) 2×300 MCM1) 9.8 1) 7.2 1)
R9 2×95 2×3/0 2×240 2×500 MCM 70 51.6 -
Frame
size
Weights Free space requirements for vertical installation
Stand alone Side by side 1)
1) Without free space on the sides.
IP21 (UL
Type 1)
IP55 (UL
Type 12)
IP21 (UL Type 1) IP55 (UL Type 12) All types All types
Above Below 2)
2) Measured from the drive frame, not from the cable box.
Above Below2) Sides Above Below2)
kg lb kg lb mm in mm in mm in mm in mm in mm in mm in
R1 4.6 10.1 4.8 10.6 150 5.9 86 3.4 137 5.4 116 4.6 150 5.9 200 7.9 200 7.9
R2 6.6 14.6 6.8 15.0 150 5.9 86 3.4 137 5.4 116 4.6 150 5.9 200 7.9 200 7.9
R3 11.8 26.0 13.0 28.7 200 7.9 53 2.1 200 7.9 53 2.0 150 5.9 200 7.9 200 7.9
R4 19.0 41.9 20.0 44.1 53 2.1 200 7.9 53 2.0 200 7.9 150 5.9 200 7.9 200 7.9
R5 28.3 62.4 29.0 64.0 100 4.0 200 7.9 100 4.0 200 7.9 150 5.9 200 7.9 200 7.9
R6 42.4 93.5 43.0 94.8 155 6.1 300 11.8 155 6.1 300 11.8 150 5.9 200 7.9 300 11.8
R7 54 119.1 56 123.5 155 6.1 300 11.8 155 6.1 300 11.8 150 5.9 200 7.9 300 11.8
R8 69 152.2 77 169.8 155 6.1 300 11.8 155 6.1 300 11.8 150 5.9 200 7.9 300 11.8
R9 97 213.9 103 227.1 200 7.9 300 11.8 200 7.9 300 11.8 150 5.9 200 7.9 300 11.8