ABB ACS800-07 User manual

ABB industrial drives
Description
Cabinet Options for ACS800-07/U7/17/37

Options covered in this manual
Code Description Page Code Description Page
B053 IP22 degree of protection 14 G317 Busbar supply terminals 30
B054 IP42 degree of protection 14 G330 Halogen-free materials and wiring 30
B055 IP54 degree of protection 14 G338 Additional wire markings 30
B059 IP54R degree of protection 15 G339
C121 Marine construction 16 G340
C129 UL listed 16 G341
C134 CSA marked 17 G342
D150 Brake choppers 18 H351 Top entry 32
D151 Brake resistors 18 H353 Top exit 32
E200 EMC filter for drives of category 3 in
TN systems
19 H358 US/UK gland/conduit plate 32
E202 EMC filter for drives of category 2 in
TN systems
20 H359 Common motor terminal cubicle 32
E210 EMC filter for drives of category 3 in
TN or IT systems
20 L505
2L505
Thermistor relays (1 or 2 pcs) 33
E205 du/dt filter 20 L506
5L506
8L506
Pt100 relays (3, 5 or 8 pcs) 34
E206 Sine output filter 20 L513 ATEX certified thermal protection with
PTC
36
E208 Common mode filter 21 M600 Starter for auxiliary motor fan 37
F250 Line contactor 24 M601
F251 gG line fuses 24 M602
F253 Load-switch disconnector 25 M603
F255 Air circuit breaker 26 M604
F259 Grounding switch 27 M605
F260 aR line fuses 25 M606
G300 Cabinet heater (external supply) 28
G304 115 V AC control voltage 29
G307 Terminals for external control voltage 29
G313 Output for motor heater (external
supply)
29

Cabinet Options for ACS800-07/U7/17/37
Description
3AUA0000053130 Rev A EN
EFFECTIVE: 27.3.2009
©2009 ABB Oy. All Rights Reserved.


Table of contents
5
Table of contents
Options covered in this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of contents
Introduction to the manual
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Availability of the options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Standard features
Degree of protection (B)
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IP22 (B053) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IP42 (B054) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IP54 (B055) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IP54R (B059) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Calculating the required static pressure difference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Construction (C)
Marine construction (C121) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
UL listed (C129) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CSA approved (C134) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Resistor braking (D)
Brake choppers (D150) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Brake resistors (D151) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Filters (E)
General about EMC filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
EMC filter (E200) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Table of contents
6
EMC filter (E202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
EMC filter (E210) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
du/dt filter (E205) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Sine output filter (E206) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Common mode filter (E208) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Line options (F)
Standard features of different drive types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ACS800-07 frames R5 to R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Standard features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ACS800-U7 frames R6 to R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ACS800-07 frames n×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Standard features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ACS800-17 and ACS800-37 frames R6, R7i and R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Standard features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
ACS800-17 and ACS800-37 frames n×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Standard features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Line contactor (F250) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
ACS800-07/U7 frames R5 to R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Frames n×R8i (ACS800-07) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
gG line fuses (F251) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
aR line fuses (F260) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Load-switch (F253) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Load-switch for 12-pulse units (+A004+F253) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Air circuit breaker (F255) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Grounding switch (F259) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Availability table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Heaters, external control voltage (G)
Cabinet heater with external supply (G300) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
What the option contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Example connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
115 V AC control voltage (G304) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Terminals for external control voltage (G307) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Output for motor heater (G313) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Example connection diagram: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Busbar supply terminals (G317) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Halogen-free materials and wiring (G330) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Additional wire markings (G338…G342) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Cabling (H)
Top entry (H351) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Top exit (H353) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
US/UK gland/conduit plate (H358) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Common motor terminal cubicle (H359) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Table of contents
7
I/O options (L)
I/O extension and interface modules (+L500, +L501, …) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Additional terminal block X2 (+L504) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Thermistor relays (+L505, +2L505) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
What the option contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Example connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Pt100 relays (+3L506, +5L506, +8L506) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
What the option contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Example connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Setting the alarm and trip levels of the Pt100 relay . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
ATEX certified thermal protection with PTC (+L513) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Starter for auxiliary motor fan (M)
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Example connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Trip limit setting ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Safety features (Q)

Table of contents
8

Introduction to the manual
9
Introduction to the manual
What this chapter contains
The chapter describes the manual in short.
Applicability
The manual applies to the following air-cooled cabinet installed drives: ACS800-07,
ACS800-U7, ACS800-17, ACS800-37. The options concerned are listed on the
inside of the front cover.
Availability of the options
Note: All options described in this manual are not available for all drive types. Check
the availability from ACS800 Ordering Information (3AFE64556568), or with the
ACS800 Product Configurator (configuring tool for internal use).
Safety instructions
Target audience
The manual is intended for ABB sales and sales support personnel and drive
application engineers.
Purpose of the manual
The purpose of the manual is to introduce cabinet options which have not their own
manuals or are not described in the hardware manual or technical catalog.
Related documents
• Drive hardware manuals
• Cabinet option manuals
• Circuit diagrams delivered with the drive
Note: You can create circuit diagrams with the ACS800 Product Configurator
(configuring tool for internal use).
WARNING! Follow the safety instructions given in the hardware manual and other
manuals. Ignoring the instructions can cause physical injury or death, or damage to
the equipment.

Introduction to the manual
10
Contents
The manual lists the standard cabinet features of different drive types and describes
the available options in alphabetic order.

Standard features
11
Standard features
Note: The codes of the options included in the standard unit (when no options are
selected on ordering) are not printed on the type designation label.
Drive type Frames Features when no options are selected
ACS800-07
(45 to 560 kW)
R5, R6, R7, R8 IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC control voltage, control
panel CDP312R, no EMC filter, standard control program, bottom entry and exit of
cables, cable lead through entry, boards without coating, one set of default
language documents
ACS800-U7
(50 to 600 hp)
R5, R6, R7, R8 UL type 1 (IP21), US type main switch fuse with Class T or L fuses, 115 V AC
control voltage, control panel CDP312R, no EMC filter, standard control program
(US), common mode filter in frame R8 (+E208), top entry and exit of cables, cable
conduit entry, one set of default language documents
ACS800-07
(500 to 2800 kW)
n×R8i IP21 (UL type 1), main switch inside the diode supply module, no AC fuses,
230 V AC auxiliary control voltage, control panel CDP312R, standard control
program, du/dt filtering (+E205), common mode filtering (+E208), EMC filtering
(Category 3, TN or IT systems, +E210), bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
ACS800-17
(55 to 2500 kW)
R6 IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC auxiliary control
voltage, no EMC filter, standard control program, bottom entry and exit of cables,
cable lead through entry, coated boards, one set of default language documents
R7i, R8i IP21 (UL type 1), main switch fuse with aR fuses, line contactor, 230 V AC auxiliary
control voltage, control panel CDP312R, standard control program, EMC filtering
(Category 3, TN or IT systems, +E210), du/dt filtering in 690 V R8i (+E205),
common mode filtering (+E208), bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
n×R8i IP21 (UL type 1), air circuit breaker, aR fuses, 230 V AC auxiliary control voltage,
control panel CDP312R, RDCO-03, EMC filtering (Category 3, TN systems,
+E200), du/dt filtering (+E205), common mode filtering (+E208), standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents
ACS800-37
(55 to 2700 kW)
R6 IP21 (UL type 1), main switch fuse with aR fuses, 230 V AC auxiliary control
voltage, RDCO-03, control panel CDP312R, no EMC filter, standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents
R7i, R8i IP21 (UL type 1), main switch fuse with aR fuses, line contactor, 230 V AC auxiliary
control voltage, RDCO-03, control panel CDP312R, EMC filtering (Category 3, TN
or IT systems, +E210), du/dt filtering in 690 V R8i (+E205), common mode filtering
(+E208), standard control program, bottom entry and exit of cables, cable lead
through entry, coated boards, one set of default language documents
n×R8i IP21 (UL type 1), air circuit breaker, aR fuses, 230 V AC auxiliary control voltage,
RDCO-03, control panel CDP312R, EMC filtering (Category 3 in TN systems,
+E200), du/dt filtering (+E205), common mode filtering (+E208), standard control
program, bottom entry and exit of cables, cable lead through entry, coated boards,
one set of default language documents

Standard features
12
More information: ACS800 Ordering Information (3AFE64556568)

Degree of protection (B)
13
Degree of protection (B)
General
The degree of protection of the standard cabinet is IP21. The air outlet at the top of
the cabinet is covered with a brass grating. With doors open, the degree of
protection of the standard cabinet and all cabinet options is IP20. The live parts
inside the cabinet are protected against contact with clear plastic shrouds or metallic
gratings. The optional degree of protection may add extra fans, gratings and air
filters to the cabinet. Examples of cabinets with different degrees of protection are
shown below.
IP21 IP54 marine cabinet
IP42

Degree of protection (B)
14
Definitions
According to IEC/EN 60529, the degree of protection is indicated by an IP code
where the first numeral means protection against ingress of solid foreign objects,
and the second numeral protection against ingress of water. The IP codes of the
standard cabinet and options covered in this manual are defined below.
* meaning for protection of persons: against access to hazardous parts with finger
IP22 (B053)
This option provides the degree of protection of IP22 (UL type 1). It adds plastic
gratings and fabric filter mats on the standard cabinet air inlet gratings.
ACS800-07 frames R7 and R8: The option contains an additional fan.
IP42 (B054)
This option provides the degree of protection of IP42 (UL type 2). It equips the
cabinet air inlets with filter housings containing fabric air filter mats between the inner
metallic grating and the outer plastic grating.
ACS800-07 frame R6: The option may contain an additional fan.
ACS800-07 frames R7 and R8: The option contains an additional fan.
IP54 (B055)
This option provides the degree of protection of IP54 (UL type 12). It equips the
cabinet air inlets with filter housings containing folded board air filter mats between
the inner metallic grating and the outer plastic grating. Additional fans on the cabinet
roof of the power cubicles are included.
IP code The equipment is protected …
First numeral Second numeral
IP20 against ingress of solid foreign objects >
12.5 mm diameter *
not protected against water
IP21 against ingress of solid foreign objects >
12.5 mm diameter *
against vertically dripping water
IP22 against ingress of solid foreign objects >
12.5 mm diameter *
against dripping (15° tilting) water
IP42 against ingress of solid foreign objects >
1mm
against dripping (15° tilting) water
IP54 dust-protected against splashing water

Degree of protection (B)
15
IP54R (B059)
This option provides the degree of protection of IP54R (UL type 12) with a collar for
fitting an air outlet duct. The collar is located on the cabinet roof either directly or on
the extra fan housing (ACS800-07 frames R7 and R8). The option equips the
cabinet air inlets with filter housings containing folded board air filter mats between
the inner metallic grating and the outer plastic grating.
Note: The ventilation system must keep the static pressure in the air outlet duct
sufficiently below the pressure of the room where the drive is located in order that
the cabinet fans can produce the required air flow through the cabinet. Ensure that
no dirty or moist air is able to flow backward to the drive in any case, even during off-
time or while servicing the drive or the ventilation system.
Calculating the required static pressure difference
The required static pressure difference between the exit air duct and the drive
installation room can be calculated as follows:
where
pddynamic pressure
air density (kg/m3)
vmaverage air velocity in the exit duct(s) (m/s)
qrated air flow of the drive (m3/s)
Accross-sectional area of the exit duct(s) (m2)
Example
The cabinet has 3 exit openings of 315 mm diameter. The rated air flow of the
cabinet is 4650 m3/h =1.3 m3/s.
Ac= 3 • 0.3152• / 4 = 0.234 m2
vm= q/ At= 1.3 / 0.234 = 5.5 m/s
pd= 0.5 • • Um2= 0.5 • 1.1 • 5.52= 17 Pa
The required pressure in the exit air duct is then, 1.5…2 • 17 Pa = 26…34 Pa, below
the pressure in the room.
More information: Contact ABB.
ps= (1.5…2) • pd
ǻ
pd= 0.5 •
ȡ
• vm2
vm= q/ Ac
ȡ
ʌ
ȡ

Construction (C)
16
Construction (C)
Marine construction (C121)
The option includes the following accessories and features:
• reinforced mechanics
• grab railings
• door flush bolt which allows the door to open 90 degrees and prevents it from
slamming close
• self-extinctive materials
• flat bars at base of the cabinet for fastening
• fastening braces at the top of the cabinet.
Required options: Appropriate additional wire marking option (+G338…+G342, page
30) according to the requirements of the classification society
Related options: halogen-free materials and wiring (+G330)
More information: Hardware manual
UL listed (C129)
The option includes factory inspection of the cabinet according to UL 508C and the
following accessories and features:
• US type main switch fuse or main disconnector and AC fuses (n×R8i)
• top entry and exit of cables
• US cable conduit entry (plain plate without ready-made holes)
• 115 VAC control voltage when needed
• all components UL Listed/Recognized
• maximum supply voltage 600 V.
Related options: +H358 (cable conduit entry)

Construction (C)
17
CSA approved (C134)
The option includes the following accessories and features:
• US/CSA type main switch fuse
• bottom entry and exit of cables
• US cable conduit entry (plain plate without ready-made holes)
• 115 VAC control voltage when needed
• all components UL/CSA listed/recognized
• maximum supply voltage 600 V.

Resistor braking (D)
18
Resistor braking (D)
Brake choppers (D150)
The option contains brake chopper(s) for feeding braking energy to brake resistors
to be dissipated there.
The customer must connect brake resistors to the drive.
ACS800-07/U7 frames R5 to R8: The brake choppers are located inside the drive
module.
Standard option for ACS800-07 frame 2×R8i and ACS800-37 frames up to 2×R8i.
The brake choppers are located in their own cubicles. The number of the choppers
depends on the drive size. The choppers are of type NBRA.
ACS800-07 and ACS800-37 frames 3×R8i and above: Application-engineered
option
Not available for ACS800-17.
More information: Hardware manual and NBRA-6xx Braking Choppers Installation
and Start-up Guide (3AFY58920541 [English])
Brake resistors (D151)
The option contains brake resistors. The number of the brake resistors depends on
the drive size. The resistors are of type SAFUR.
ACS800-07 frames R5 to R8 and ACS800-37: Not available with options +B055,
B059, +C121, +C129 and +C134.
Standard option for ACS800-07 frame 2×R8i and ACS800-37 frames up to 2×R8i.
ACS800-07 and ACS800-37 frames 3×R8i and above: Application-engineered
option
ACS800-07 frames n×R8i: Not available with options +B055, +B059, +C129 and
+C134. With marine construction (+C121) available only for 500 V and 690 V units.
ACS800-U7 and ACS800-17: Not available.
More information: Hardware manual

Filters (E)
19
Filters (E)
General about EMC filtering
The EMC filter options protect the drive and equipment connected to the electrical
power system against radio-frequency interference. This means that the drive
operates without problems and does not disturb or interfere with any other product or
system within its locality.
Definitions
EMC stands for electromagnetic compatibility.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic
premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
TN system means a grounded electrical power system. IT system means an ungrounded electrical
power system.
More information: Technical Guide No. 3 – EMC Compliant Installation and
Configuration for a Power Drive System (3AFE61348280 [English])
EMC filter (E200)
This option provides electromagnetic compatibility for drives of category 3 in TN
(grounded) systems.
Option for ACS800-07 frame R5 and ACS800-U7/17/37 frame R6.
Not available for
• ACS800-07 frames R6 to R8 and n×R8i
• ACS800-U7 frames R6 to R8
• ACS800-17/37 frames R7i, R8i and n×R8i.

Filters (E)
20
EMC filter (E202)
This option provides electromagnetic compatibility for drives of category 2 in TN
(grounded) systems.
ACS800-07/U7 frames R7 and R8: The option adds the cabinet width.
ACS800-17/37 frames R7i and R8i: Requires +H359.
ACS800-07/U7/17/37 frames R5 to R8, R7i, R8i: Not available for 690 V units.
ACS800-07 frames n×R8i: Available only for -0610-3 and -0760-5 equipped with 6-
pulse supply. Requires +F253 and +F260.
ACS800-17 frames n×R8i: Available only for -0640-3 and -0770-3, -0780-5, -0870-5.
ACS800-37 frames n×R8i: Available only for -0640-3, -0770-3, -0780-5, -0870-5.
EMC filter (E210)
This option provides electromagnetic compatibility for drives of category 3 in TN
(grounded) systems and IT (ungrounded) systems.
Option for ACS800-07/U7 frames R6 to R8.
Standard for ACS800-07 frames n×R8i and ACS800-17/37 other frames than R6.
Not available for ACS800-17/37 frame R6.
du/dt filter (E205)
The du/dt filter protects the motor insulating system by reducing the voltage rise
speed at the motor terminals. The filter also protects the motor bearings by reducing
the bearing currents.
Option for ACS800-07/17/37 frames R6 to R8.
Standard for ACS800-07/17/37 frames n×R8i.
More information on when the option is required: See section Checking the
compatibility of the motor and the drive in the drive hardware manual.
Sine output filter (E206)
The option consists of single- or threephase reactors and delta- or star-connected
capacitors at the output of the drive. It is a low-pass filter that suppresses the high
frequency components of the drive output. The filter is fitted in a separate cubicle
with a cooling fan which rotates whenever the drive is powered. The available output
current of some drive types may be reduced.
ACS800-07: Not available for frames R5 and R6 except 0135-3, 0205-3, 0165-5,
0255-5, 0145-7 and 0175-7. Not available for 0260-7, 0490-7, 0610-7 or with C121,
C129 or E205.
This manual suits for next models
3
Table of contents
Other ABB Industrial Equipment manuals

ABB
ABB Turbo Systems Switzerland Power2 550-M44 User manual

ABB
ABB CIO-01 User manual

ABB
ABB 2 Series Specification sheet

ABB
ABB HT562660 User manual

ABB
ABB HT609417 User manual

ABB
ABB HT588340 User manual

ABB
ABB HT608843 User manual

ABB
ABB Ekip UP+ User manual

ABB
ABB HT564496 User manual

ABB
ABB A145-M65 User manual