ABB REJ 521 User manual

REJ 521
Earth-Fault Relay
Operator’s Manual


3
Earth-Fault Relay
Operator’s Manual
REJ 521
1MRS 752179-MUM
Issued: 14.09.98
Version: C/15.08.02
Checked: A.S.
Approved: L.N.
We reserve the right to change data without prior notice.
Contents
1. Introduction ............................................................................... 5
1.1. About this manual ..........................................................................5
1.2. The use of the relay .......................................................................5
1.3. Features .........................................................................................5
1.4. Guarantee ......................................................................................6
2. Safety information ..................................................................... 7
3. Instructions ................................................................................ 8
3.1. HMI features ...................................................................................8
3.1.1. Front panel ..........................................................................8
3.1.2. Display ................................................................................9
3.1.2.1. Display test at power up ........................................9
3.1.2.2. Display idle mode ..................................................9
3.1.2.3. Display backlight ...................................................9
3.1.2.4. How to adjust the display contrast ......................10
3.1.3. How to use the push-buttons ............................................10
3.1.4. How to select language .....................................................11
3.1.5. Main menu ........................................................................12
3.1.6. Submenu ...........................................................................12
3.1.7. How to switch between the front and the rear connector ..12
3.1.8. Passwords ........................................................................13
3.2. HMI operation levels ....................................................................14
3.2.1. Main level ..........................................................................14
3.2.2. User level ..........................................................................14
3.2.2.1. Menu groups of the user level .............................14
3.2.2.2. How to monitor measured values ........................14
3.2.2.3. How to monitor recorded data .............................15
3.2.2.4. INFO ....................................................................16
3.2.3. Technical level ..................................................................16
3.2.3.1. Menu system of parameters ................................16
3.2.3.2. How to change settings ......................................17
3.2.3.3. Configuration .......................................................18
3.2.3.4. How to acknowledge and reset indications,
output contacts and memorized values ...............19
3.2.4. Menu chart ........................................................................20
3.3. Protection relay indications ..........................................................21
3.3.1. Indicator LEDs ..................................................................21
3.3.1.1. Green indicator LED ............................................21
3.3.1.2. Yellow indicator LED ...........................................21
3.3.1.3. Red indicator LED ...............................................22

4
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
3.3.2. Indication messages .........................................................22
3.3.2.1. Alarm indication messages .................................22
3.3.2.2. Disturbance recorder indication ..........................23
3.3.2.3. Internal fault ........................................................23
4. Technical description .............................................................25
5. Service ......................................................................................26
5.1. General ........................................................................................26
5.2. Commissioning testing .................................................................26
5.2.1. Function test .....................................................................26
5.2.2. Binary input test ................................................................27
5.2.3. LED test ............................................................................27
5.3. Secondary injection testing ..........................................................27
5.3.1. Testing of the earth-fault measuring transformer ..............29
5.3.2. Testing of the earth-fault stages .......................................29
5.3.2.1. Low-set stage I0> ................................................29
5.3.2.2. High-set stage I0>> .............................................29
5.3.3. Testing of the self-supervision system (IRF) ....................30
5.4. Spare parts ..................................................................................30
6. Ordering information ..............................................................31
7. References ...............................................................................32
8. Index .........................................................................................33
9. Abbreviations ..........................................................................35
10.Customer feedback ................................................................ 36

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
5
1. Introduction
1.1. About this manual
This manual provides the user with basic information on the earth-fault relay REJ
521 and presents detailed instructions on how to use the Human-Machince Interface
(HMI) of the relay, also known as the Man-Machine Interface (MMI). In addition to
the instructive part, a short chapter on the service of the relay has been included.
1.2. The use of the relay
The REJ 521 is intended for non-directional earth-fault protection in medium
voltage distribution networks but can also be used for protection of generators,
motors and transformers.
The REJ 521 is based on a microprocessor environment. A self-supervision system
continuously monitors the operation of the electronics and the software.
The HMI includes a Liquid Crystal Display (LCD) which makes the local use of the
relay safe and easy.
Local control of the relay can be carried out using a portable computer connected to
the front connector and remote control via the rear connector connected to the
distribution automation system through the serial interface and the fibre-optic bus.
1.3. Features
• Low-set non-directional earth-fault stage with definite-time or indefinite
minimum time (IDMT) characteristic
• High-set non-directional earth-fault stage with instantaneous or definite-time
characteristic
• Circuit-breaker failure protection unit (CBFP)
• Disturbance recorder
• recording time up to 28 seconds
• triggering by a start or a trip signal from either of the two protection stages and/
or by a binary input signal
• records the analogue channel and five digital channels
• adjustable sampling rate
• Non-volatile memory for
• up to 60 event codes
• setting values
• disturbance recorder data
• recorded data of the five last events with time stamp
• number of starts for each stage
• alarm indication messages and LEDs showing the status at the moment of
power failure
• one accurate current input
• Galvanically isolated binary input with a wide input voltage range

6
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
• All settings can be modified with a personal computer
• HMI with an alphanumeric LCD and manoeuvring buttons
• IEC 60870-5-103 and SPA bus communication protocols
• Two normally open power output contacts
• Two change-over signal output contacts
• Output contact functions freely configurable for desired operation
• Optical PC-connector for two-way data communication (front)
• RS-485 connector (rear) for system communication
• Continuous self-supervision of electronics and software. At an internal relay fault
(IRF), all protection stages and outputs are blocked.
• User-selectable rated frequency 50/60 Hz
• User-selectable password protection for the HMI
• Display of primary current values
• Multi-language support
1.4. Guarantee
Please inquire the guarantee of your nearest ABB representative.

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
7
2. Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected
National and local electrical safety regulations must always be
followed
The device contains components which are sensitive to electrostatic
discharge
The frame of the device has to be carefully earthed
Only a competent electrician is allowed to carry out the electrical
installation
Non-observance can result in death, personal injury or substantial
property damage
Breaking the sealing tape on the rear panel of the device will result in
loss of warranty and proper operation will no longer be guaranteed
!

8
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
3. Instructions
3.1. HMI features
3.1.1. Front panel
The front panel of the protection relay includes:
• an alphanumeric 2 x 16 characters’ LCD with backlight and contrast control
• three indicator LEDs (ready, start, trip)
• an HMI push-button section with four arrow buttons and buttons for clear and
enter
• an optically isolated serial communication port
)LJ )URQWYLHZRIWKHUHOD\
1. LCD
2. Optical PC-connector
3. HMI push-button section
4. Indicator LEDs:
• Left: Ready (green)
• Centre: Start (yellow)
• Right: Trip (red)
REJ 521
Order No: REJ521B 413-BAA
Article No: 1MRS118011
Serial No: ER 000001
Uaux = 110-240 Vac
Uaux = 48-220 Vdc
fn = 50/60 Hz
In = 0.2/1 A (Io)
In = 1/5 A (I)
C
E
STARTREADY TRIP
ABB
1
2
3
4
Frview_521

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
9
3.1.2. Display
3.1.2.1. Display test at power up
When the auxiliary voltage is connected to the relay:
1. The backlight will be turned on after the relay has performed the internal
power-up tests and entered into the protection mode.
2. The display will be tested by inverting it for a short time.
3. The display will be returned to the idle mode and the backlight turned off.
However, if the non-volatile function is active, a message shown on the display
before the auxiliary voltage was disconnected will reappear on the display.
)LJ 'LVSOD\WHVWDWSRZHUXS
3.1.2.2. Display idle mode
When the relay is in the idle mode, the station name will be displayed, which by
default is “- ABB -”. To change the station name, use SPA parameter M20.
)LJ 'LVSOD\LQWKHLGOHPRGH
3.1.2.3. Display backlight
• Normally the backlight of the display is off.
• The backlight is turned on at the touch of an arrow button on the HMI. If the HMI
panel has not been used for approximately five minutes, the backlight will be
turned off automatically.
• A power saving built-in feature: pressing the [C] button will turn the backlight off
within 20 seconds.
Powup
C
E
STARTREADY TRIP
Idle
C
E
- ABB -
STARTREADY TRIP

10
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
3.1.2.4. How to adjust the display contrast
The display contrast is dependent on the temperature. The REJ 521 automatically
adjusts the contrast for optimum readability. The contrast can also be adjusted
manually. To adjust the contrast, the display must be in the idle mode.
• To increase the contrast, hold down the [E] button and adjust using the [↑] button.
• To decrease the contrast, hold down the [E] button and adjust using the [↓]
button.
)LJ $GMXVWLQJWKHGLVSOD\FRQWUDVW
Afterpower-startup oftherelay,thefactorydefaultvalueof thedisplaycontrastwill
automatically be restored.
3.1.3. How to use the push-buttons
The HMI includes push-buttons for manoeuvring the relay.
)LJ 1DYLJDWLRQEXWWRQV
The navigation buttons are used to view, select and edit desired menu items. To
move between the menu items, use the arrow buttons. The item to be edited is
selected and the value stored by pressing the [E] button. To increase or decrease the
activated digit and to shift the activated decimal point, use the [↑] and [↓] buttons.
To cancel and return the HMI to the idle mode, press the [C] button..
Contr
Eand
Push
increase
decrease
Table 3.1.3-1 Button navigation and editing
Desired step or operation Push-button
Step downward in the main menu or a submenu ↓
Step upward in the main menu or a submenu ↑
Entering a submenu from the main menu or a higher
submenu →
Leaving a submenu for the main menu or a higher
submenu ←
Increasing a value in the setting mode ↑
Decreasing a value in the setting mode ↓
Moving the cursor in the setting mode ← or →
Selecting the front connection at power up ←and →
Entering or leaving the setting mode, storing a new
value E
Entering the monitoring state E and ←
C
E
NavButt
down
left
up
right
Navigation push-buttons Clear and Enter buttons
Clear/Cancel
Enter

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
11
3.1.4. How to select language
The REJ 521 allows you to choose among several different languages. The default
language is English. For selectable languages, see the picture below.
)LJ 6HOHFWLRQRIODQJXDJH
1. Press an arrow button to access the main menu.
2. Select “CONFIGURATION” in the main menu and “LANGUAGE” in the
group menu.
3. Press the [→] button to enter the currently valid language.
4. Press the [E] button. The second line will start to flash indicating that it is
allowed to set the language. A password will be required depending on the state
of the password protection.
5. Move the cursor to the desired language and confirm the selection by pressing
the [E] button. The selected language will be shown on the display.
6. Press the [C] button to return the HMI to the idle mode.
By pressing the [C] button before confirming the selection, the former language will
remain active and the display will be returned to the view mode. Pressing the [C]
button again will return the display to the idle mode.
Adjusting the display contrast E and ↓ or ↑
Resetting or cancelling, leaving the setting mode
without storing a new value C
Acknowledging and resetting indications, output
contacts and memorized values E and C
Table 3.1.3-1 Button navigation and editing
LangSel
E
C
INFO ENGLISH
SVENSKA
SUOMI
DEUTSCH
FRANCAIS
ITALIANO
ESPAÑOL
Main Menu Group Menu Parameter Menu
Confirm
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
FUNCTION TEST/BI
COMMUNICATION
LANGUAGE
FREQUENCY
CONFIGURATION
CONFIGURATION

12
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
3.1.5. Main menu
The main menu contains five main groups:
• MEASUREMENTS
• RECORDED DATA
• SETTINGS
• CONFIGURATION
•INFO
)LJ 7KHGLVSOD\VKRZLQJWKHILUVWPDLQPHQXJURXS
• To navigate between the main menu groups, use the [↑] and [↓] buttons.
• To return the display to the idle mode, press the [C] button.
The display will be returned to the idle mode on expiration of the timeout.
3.1.6. Submenu
The menu structure contains several subgroups. The name of the main menu group
is always shown on the first line. On the second line either the name of the group
menu, the name of the parameter and the parameter value, or just the parameter
value, in which case it is also the name of the parameter, is shown.
)LJ 7KHGLVSOD\VKRZLQJWKHILUVWVXEPHQX
• To enter a submenu, press the [→] button; to exit, press the [←] button.
• Press the [C] button to return the display to the idle mode.
• To navigate between the main levels in the submenus, use the [↑] or [↓] button.
3.1.7. How to switch between the front and the rear connector
The relay is provided with two serial connectors: rear connector RS-485 and the
front optical PC-connector, of which the former is the default connector. To switch
between the front and the rear connector, use the Front/Rear selector of the HMI:
Meas
C
E
MEASUREMENTS
STARTREADY TRIP
C
E
MEASUREMENTS
I0 In:0.74
STARTREADY TRIP
Subm_521

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
13
1. Select “COMMUNICATION” under the main menu group
“CONFIGURATION”.
2. Move the cursor to the currently used setting (“REAR CONNECTION/FRONT
CONNECTION”) and press the [E] button. The lower line will start to flash.
3. Select the desired setting using the [↑] or [↓] button and press the [E] button to
confirm the selection.
When the front connection has been selected but there has not been any
communication for approximately five minutes, the rear connection will
automatically be activated. To disable this function, press the [←] and [→] buttons
simultaneously when applying the auxiliary voltage to the relay.
)LJ 6ZLWFKLQJEHWZHHQIURQWDQGUHDUFRQQHFWLRQ
3.1.8. Passwords
There are two passwords: one for the HMI and one for SPA bus communication.
The HMI password protects all user-changeable values from being changed by an
unauthorized person. The HMI password protection function will remain inactive
until the default password has been replaced. The default HMI password is “999”
and the default SPA password “001”.
The passwords can be changed but not read from a remote unit. The SPA password
can be changed via the serial bus by first entering the currently valid password into
parameter V160 and then entering the new password into parameter V161. The HMI
password can be changed via parameter V162. For changing the passwords via the
HMI, see also section Configuration.
As soon as the default HMI password has been replaced, the password will be
required for altering parameter values. Once the valid password has been given, the
HMI will remain in the setting mode until returned to the idle mode.
Fr_r
E
C
INFO
Main Menu Group Menu Parameter Menu
Confirm
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
CONFIGURATION
FUNCTION TEST/BI
COMMUNICATION
LANGUAGE
FREQUENCY
CONFIGURATION
PASSWORD SPA :xxx
PASSWORD HMI :xxx
REAR CONNECTION
BAUD RATE :x.x
COUNTER :xxx
UNIT ADDRESS :xxx
IEC 103 SET :x
PROTOCOL:SPA

14
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
)LJ 3DVVZRUGUHTXHVWIRUHGLWLQJVHWWLQJSDUDPHWHUV
3.2. HMI operation levels
3.2.1. Main level
The main level of the HMI consists of a user and a technical level. The user level is
used for measuring and monitoring whereas the technicallevel is used for advanced
protection relay setting and can beconfigured to demand a password. The password
will be required after the default value “999” has been replaced.
3.2.2. User level
3.2.2.1. Menu groups of the user level
The user level contains three menu groups:
• MEASUREMENTS = monitors the measured value
• RECORDED DATA = stored alarm event values from the protection stages
• INFO = information on the relay, e.g. relay name, serial number
Data of every menu group can be monitored without a password.
3.2.2.2. How to monitor measured values
Measured values can be monitored either via “MEASUREMENTS” in the HMI
menu or by activating the monitoring state.
To access measured values via the HMI menu:
1. Press the [→] button in the main menu group “MEASUREMENTS” to see the
measured value of I0. The value is shown as a multiple of the rated current, In, of
the energizing input.
2. Press the [→] button once more to see the corresponding value in amperes. If the
conversion factor has not been set, dashes will be displayed instead.
3. Press the [C] button to return the HMI to the idle mode.
C
E
STARTREADY TRIP
Passwd
SETTINGS
PASSWORD :000

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
15
)LJ 0HDVXUHPHQWV
To access measured values by activating the monitoring state:
1. Press the [E] and [←] buttons simultaneously to view the measured value of I0.
2. To exit, press the [C] button.
The display has to be in the idle mode to be able to activate the monitoring state.
)LJ 0RQLWRULQJVWDWH
The prerequisite for monitoring primary values is that serial parameter M80 has
been set via serial communication.
3.2.2.3. How to monitor recorded data
The contents of the event register are found under the main menu group
“RECORDED DATA”.
1. Choose “RECORDED DATA” in the main menu and press the [→] button to
enter the first event.
2. To navigate between the events, use the [↑] and [↓] buttons.
3. To enter or exit a submenu, use the [→] or [←] button.
4. To return the HMI to the idle mode, press the [C] button.
Meas_men_521
C
INFO
I0 In:x.xx I0 A:x.xx
Main Menu Group Menu Parameter Menu
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
MEASUREMENTS MEASUREMENTS
+
- ABB -
E
Monitor_521
Io X.XX

16
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
)LJ 5HFRUGHGGDWD
3.2.2.4. INFO
The main menu group “INFO” contains information about the relay, such as type,
software, article and serial numbers. Use this data when you need to order service,
for instance. The submenu found under the software number displays the additional
build number.
)LJ ,1)2
3.2.3. Technical level
3.2.3.1. Menu system of parameters
The interactive communication between the operator and the HMI is based on
menus. Press an arrow button to activate the main menu. If the default password is
in use, no password will be required to change the parameters. If the password
protection isin use,“***”willbe shown onthedisplayuntilthevalidHMIpassword
has been given.
The views are used for reading setting parameters, measured values, etc. The
parameters are divided into two main groups:
• SETTINGS
• CONFIGURATION
Recd_521
INFO
C
1. I0 In:x.xx
1. t0> %:xxx
1. t0>> %:xxx
Main Menu Group Menu Parameter Menu
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
NUMBER OF STARTS
5. EVENT
4. EVENT
3. EVENT
RECORDED DATA
1. EVENT
2. EVENT Cancel
1. xx.xx;xx.xx
1. xx-xx-xx
RECORDED DATA
START I0>> :xxx
RECORDED DATA
START I0> :xxx
Info_521
C
INFO INFO
INFO
1MRS090413-BAA
ERxxxxxxxxxxxx
1MRS118013 B
REJ 521
2xx
Main Menu Parameter Menus
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
17
3.2.3.2. How to change settings
The actualsettings are found in the first submenu and are not editable. These in turn
consist of the settings of either group 1 or 2, depending on which one has been
selected to be active. The settings of groups 1 and 2 can be edited in the setting
mode; refer to the instructions later in this section.
Bothsetting groupshave theirrelatedregisters.By switching betweensettinggroups
1 and 2, a whole group of settings can be changed at the same time. You can switch
between these setting groups in three different ways:
1. by selecting “GROUP 1/GROUP 2” under the main menu group “SETTINGS”.
2. with a binary input signal, provided that switchgroup SGB1/4 has been set to 1.
3. with parameter V150 via the serial communication bus
)LJ 6HWWLQJJURXSVHWWLQJJURXS
When a large number of settings are to be altered, e.g. during commissioning of
relay systems, it is recommended that a personal computer provided with the
necessary software should be used. If not available, or when only a few settings are
to be altered, proceed as follows:
1. Select the main menu group “SETTINGS” and further “PROTECT.STAGES”.
Press the [→] button to enter the first submenu group.
2. Use the arrow button [↓] to select the parameter to be changed and press the [→]
button.
3. To enter setting group 2, press the [↓] button. The active setting group is
indicated by an asterisk “*”.
4. Enter the setting mode by pressing the [E] button. If the default password has
been replaced, the text “PASSWORD” will appear on the display demanding a
password. If the default password “999” is still valid, no password will be
required.
5. The first digit or the setting value of the parameter to be edited will start to flash.
Use the [→] and [←] buttons to move the cursor and the [↑] and [↓] buttons to
increase or decrease the number.
6. To store a new value and return the display to the view mode, press the [E]
button. If the parameter is of a numerical kind, the display will confirm the
storage by once flashing “---” on the display.
7. To exit the setting mode without saving the changes, press the [C] button once
before confirming and the display will be returned to the view mode.
8. Press the [C] button once more and the display will be returned to the idle mode.
Gr1_Gr2_521
E
C
I0> In:x.xx
Submenu Parameter Menu
Confirm
Cancel
SETTINGS
GRP 2 I0>:x.xx
* GRP 1 I0>:x.xx
SETTINGS

18
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
)LJ 6HWWLQJV
3.2.3.3. Configuration
In general, the parameters found under “CONFIGURATION” are usually set only
once by the customer during commissioning of the relay. These parameters are not
related to the protection functions.
)LJ &RQILJXUDWLRQ
To alter a parameter, proceed as follows:
1. Select the main menu group “CONFIGURATION” and enter the desired
parameter using the arrow buttons.
2. Enter the setting mode by pressing the [E] button. If the default password has
been replaced, the text “PASSWORD” will appear on the display demanding a
INFO
C
CBFP
SGF
SGB
SGR
E
I0> In:x.xx
t0> :x.xx
I0>> In:x.xx
t0>> :x.xx
SGF2 :xxx
SGF3 :xxx
SGF1 :xxx
SGB1 :xxx
SGR2 :xxx
SGR3 :xxx
SGR4 :xxx
SGR1 :xxx
CBFP s:x.xx
DISABLED MIN:xxx
Sett_521
Main Menu Group Menu Parameter Menus
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
Cancel
SETTINGS
PROTECT. STAGES
GROUP 1/GROUP 2
NEW TRIP IND.
MEMORY SETTINGS
Edit/Confirm
SETTINGS
GRP 2 I>:x.xx
* GRP 1 I>:x.xx
SETTINGS
SETTINGS
* GRP 1 SGF1:xxx
GRP 2 SGF1:xxx
GRP 2 SGR1:xxx
SETTINGS
* GRP 1 SGR1:xxx
SETTINGS
SETTINGS
SETTINGS
SETTINGS
SETTING GROUP X
SETTINGS
SETTINGS
MEM.SETTINGS :xxx
GRP 2 SGB1:xxx
SETTINGS
* GRP 1 SGB1:xxx
SETTINGS
Config
E
C
INFO
Main Menu Group Menu Parameter Menu
Confirm
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
CONFIGURATION
FUNCTION TEST/BI
COMMUNICATION
LANGUAGE
FREQUENCY
CONFIGURATION
PASSWORD SPA :xxx
PASSWORD HMI :xxx
REAR CONNECTION
BAUD RATE :x.x
COUNTER :xxx
UNIT ADDRESS :xxx
IEC 103 SET :x
PROTOCOL:SPA

1MRS 752179-MUM Earth-Fault Relay
Operator’s Manual
REJ 521
19
password. If the default password “999” is still valid, no password will be
required.
3. The text or the first digit of the setting value of the parameter to be edited will
start to flash. Set the digit/character using the [↑] and [↓] buttons. The next digit/
character to be set is activated by pressing the [→] or [←] button (when setting
an enumerator, however, the left and right arrows have no function).
4. To store a new value and return the display to the view mode, press the [E]
button. If the parameter is of a numerical kind, the display will confirm the
storage by once flashing “---” on the display.
5. To exit the setting mode without saving changes, press the [C] button once
before confirming and the display will be returned to the view mode.
6. Press the [C] button once more and the display will be returned to the idle mode.
)LJ 6HWWLQJWKH+0,SDVVZRUG
If a setting value beyond the allowed limits is confirmed in the setting mode, the
former value will be restored.
3.2.3.4. How to acknowledge and reset indications, output contacts and
memorized values
• To clear the LEDs and the display, press the [C] button. The LEDs and the
display will be cleared only if the fault situation has disappeared.
• Press the [C] button for at least five seconds to unlatch the output contacts. Note
that the LEDs and the display have to be cleared before this.
• Press the [C] and [E] buttons simultaneously for at least half a second to perform
a master reset, i.e. to clear indications and memorized values and to unlatch the
output contacts. The display being inverted confirms this action. Memorized
values include recorded data, disturbance recorder data and average values.
Setpar
E
C
Confirm
Cancel
Parameter Menu
CONFIGURATION
PASSWORD HMI :xxx

20
1MRS 752179-MUM
Earth-Fault Relay
Operator’s Manual
REJ 521
3.2.4. Menu chart
)LJ 0HQXVWUXFWXUH
+
M_ch_521
- Station name -
CBFP
SGF
SGB
SGR
1. I0 In:x.xx
1. t0> %:xxx
1. t0>> %:xxx
I0 In:x.xx I0 A:x.xx
I0> In:x.xx
t0> :x.xx
I0>> In:x.xx
t0>> :x.xx
SGF2 :xxx
SGF3 :xxx
SGF1 :xxx
SGB1 :xxx
SGR2 :xxx
SGR3 :xxx
SGR4 :xxx
SGR1 :xxx
CBFP s:x.xx
DISABLED MIN:xxx
1MRS090413-BAA
ERxxxxxxxxxxxx
1MRS118013 B
REJ 521
INFO INFO
2xx
INFO
DEUTSCH
FRANCAIS
ITALIANO
ESPAÑOL
ENGLISH
SVENSKA
SUOMI
I0 x.xx
- ABB -
E
C
1. xx.xx;xx.xx
1. xx-xx-xx
Note: Parameter M80 must be set
NUMBER OF STARTS
5. EVENT
4. EVENT
3. EVENT
MEASUREMENTS
RECORDED DATA
MONITORING STATE:
SETTINGS SETTINGS
PROTECT. STAGES
GROUP 1/GROUP 2
NEW TRIP IND.
RECORDED DATA
SETTINGS
* GRP 1 SGF1:xxx
GRP 2 SGF1:xxx
GRP 2 SGR1:xxx
SETTINGS
* GRP 1 SGR1:xxx
Note: ABB is the default
MEASUREMENTS
MEMORY SETTINGS
MEASUREMENTS
SETTINGS
SETTINGS
START I0>> :xxx
RECORDED DATA
START I0> :xxx
SETTINGS
SETTINGS
RECORDED DATA
1. EVENT
2. EVENT
SETTINGS
SETTING GROUP X
SETTINGS
SETTINGS
MEM.SETTINGS :xxx
GRP 2 I>:x.xx
* GRP 1 I>:x.xx
SETTINGS
GRP 2 SGB1:xxx
SETTINGS
* GRP 1 SGB1:xxx
SETTINGS
CONFIGURATION CONFIGURATION
FUNCTION TEST/BI
COMMUNICATION
LANGUAGE
FREQUENCY
CONFIGURATION
FREQUENCY :xx
CONFIGURATION
CONFIGURATION
FUNC. TEST :x
BI STATUS :x
LED TEST
CONFIGURATION
PASSWORD SPA :xxx
PASSWORD HMI :xxx
REAR CONNECTION
BAUD RATE :x.x
COUNTER :xxx
UNIT ADDRESS :xxx
IEC 103 SET :x
PROTOCOL:SPA
Note: Exit
Table of contents
Other ABB Relay manuals

ABB
ABB TF65 User manual

ABB
ABB SSR42 User manual

ABB
ABB RELION 650 SERIES User manual

ABB
ABB REL-300 Manual

ABB
ABB CIRCUIT SHIELD 437W Series User manual

ABB
ABB CA-16 User manual

ABB
ABB Relion 615 series Instructions for use

ABB
ABB RED670 Relion 670 series Quick start guide

ABB
ABB MG-6 Manual

ABB
ABB CT-S Series User manual