ABB Relion 615 series Instructions for use

—
RELION® 615 SERIES
Line Differential Protection and
Control
RED615 ANSI
Application Manual


Document ID: 1MAC807603-MB
Issued: 2018-02-26
Revision: A
Product version: 5.0 FP1
© Copyright 2018 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and may
be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/mediumvoltage
www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties. All
persons responsible for applying the equipment addressed in this manual must satisfy
themselves that each intended application is suitable and acceptable, including that any
applicable safety or other operational requirements are complied with. In particular, any
risks in applications where a system failure and/or product failure would create a risk for
harm to property or persons (including but not limited to personal injuries or death) shall
be the sole responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This product has been designed to be connected and communicate data and information
via a network interface which should be connected to a secure network. It is the sole
responsibility of the person or entity responsible for network administration to ensure a
secure connection to the network and to take the necessary measures (such as, but not
limited to, installation of firewalls, application of authentication measures, encryption of
data, installation of anti virus programs, etc.) to protect the product and the network, its
system and interface included, against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information. ABB is not liable for
any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall ABB
be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities on
the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use
within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is
the result of tests conducted by ABB in accordance with the product standards EN 50263
and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and
EN 60255-27 for the low voltage directive. The product is designed in accordance with the
international standards of the IEC 60255 series and ANSI C37.90. This product complies
with the UL 508 certification.

Table of contents
Section 1 Introduction............................................................................5
This manual.............................................................................................. 5
Intended audience.................................................................................... 5
Product documentation.............................................................................6
Product documentation set..................................................................6
Document revision history................................................................... 6
Related documentation........................................................................7
Symbols and conventions.........................................................................7
Symbols...............................................................................................7
Document conventions........................................................................ 8
Functions, codes and symbols............................................................ 8
Section 2 RED615 overview................................................................13
Overview.................................................................................................13
Product version history...................................................................... 13
PCM600 and relay connectivity package version..............................13
Operation functionality............................................................................ 14
Optional features............................................................................... 14
Physical hardware.................................................................................. 15
Local HMI................................................................................................16
Display...............................................................................................17
LEDs..................................................................................................18
Keypad.............................................................................................. 18
Web HMI.................................................................................................19
Authorization...........................................................................................20
Communication.......................................................................................21
Self-healing Ethernet ring.................................................................. 22
Ethernet redundancy......................................................................... 23
Protection communication and supervision....................................... 26
Section 3 RED615 standard configurations........................................ 27
Standard configurations..........................................................................27
Addition of control functions for primary devices and the use of
binary inputs and outputs.................................................................. 30
Connection diagrams..............................................................................32
Standard configuration D........................................................................ 34
Table of contents
RED615 ANSI 1
Application Manual

Applications....................................................................................... 34
Functions........................................................................................... 35
Default I/O connections................................................................ 35
Default disturbance recorder settings...........................................37
Functional diagrams.......................................................................... 39
Functional diagrams for protection............................................... 40
Functional diagrams for disturbance recorder.............................. 52
Functional diagrams for condition monitoring...............................53
Functional diagrams for control and interlocking.......................... 56
Functional diagrams for measurement functions..........................59
Functional diagrams for IO and alarm LEDs................................ 61
Functional diagrams for other functions....................................... 64
Functional diagrams for other timer logics....................................64
Functional diagrams for communication.......................................66
Standard configuration E........................................................................ 66
Applications....................................................................................... 66
Functions........................................................................................... 67
Default I/O connections................................................................ 67
Default disturbance recorder settings...........................................69
Functional diagrams.......................................................................... 71
Functional diagrams for protection............................................... 72
Functional diagrams for disturbance recorder.............................. 83
Functional diagrams for condition monitoring...............................84
Functional diagrams for control and interlocking.......................... 87
Functional diagrams for measurement functions..........................89
Functional diagrams for IO and alarm LEDs................................ 91
Functional diagrams for other functions....................................... 93
Functional diagrams for other timer logics....................................93
Functional diagrams for communication.......................................94
Section 4 Requirements for measurement transformers.....................95
Current transformers...............................................................................95
Current transformer requirements for overcurrent protection............ 95
Current transformer accuracy class and accuracy limit factor......95
Non-directional overcurrent protection......................................... 96
Example for non-directional overcurrent protection......................97
Section 5 Protection relay's physical connections...............................99
Inputs...................................................................................................... 99
Energizing inputs............................................................................... 99
Phase currents............................................................................. 99
Table of contents
2RED615 ANSI
Application Manual

Ground current............................................................................. 99
Phase voltages............................................................................. 99
Ground voltage........................................................................... 100
Sensor inputs..............................................................................100
Auxiliary supply voltage input.......................................................... 100
Binary inputs....................................................................................100
RTD/mA inputs................................................................................ 102
Outputs................................................................................................. 102
Outputs for tripping and controlling..................................................102
Outputs for signalling.......................................................................103
IRF...................................................................................................104
Protection communication options........................................................104
Section 6 Glossary............................................................................ 107
Table of contents
RED615 ANSI 3
Application Manual

4

Section 1 Introduction
1.1 This manual
The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
1.2 Intended audience
This manual addresses the protection and control engineer responsible for planning, pre-
engineering and engineering.
The protection and control engineer must be experienced in electrical power engineering
and have knowledge of related technology, such as protection schemes and principles.
1MAC807603-MB A Section 1
Introduction
RED615 ANSI 5
Application Manual

1.3 Product documentation
1.3.1 Product documentation set
Planning &
purchase
Engineering
Installation
Commissioning
Operation
Maintenance
Decommissioning,
deinstallation & disposal
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual
Communication protocol manual
IEC 61850 engineering guide
Point list manual
Cyber security deployment guideline
GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V2 EN
Figure 1: The intended use of documents during the product life cycle
Product series- and product-specific manuals can be downloaded from the
ABB Web site http://www.abb.com/relion.
1.3.2 Document revision history
Document revision/date Product version History
A/2018-02-26 5.0 FP1 First release
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
Section 1 1MAC807603-MB A
Introduction
6RED615 ANSI
Application Manual

1.3.3 Related documentation
Name of the document Document ID
Modbus Communication Protocol Manual 1MAC057386-MB
DNP3 Communication Protocol Manual 1MAC052479-MB
IEC 61850 Engineering Guide 1MAC053584-RG
Engineering Manual 1MAC108982-MB
Installation Manual 1MAC051065-MB
Operation Manual 1MAC054853-MB
Technical Manual 1MAC059074-MB
Cyber Security Deployment Guideline 1MAC052704-HT
1.4 Symbols and conventions
1.4.1 Symbols
The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.
The warning icon indicates the presence of a hazard which could result in
personal injury.
The caution icon indicates important information or warning related to the
concept discussed in the text. It might indicate the presence of a hazard
which could result in corruption of software or damage to equipment or
property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.
1MAC807603-MB A Section 1
Introduction
RED615 ANSI 7
Application Manual

Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. Therefore, comply
fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons.
To navigate between the options, use and .
• Menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in nonvolatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "Enabled" and "Disabled".
• Input/output messages and monitored data names are shown in Courier font.
When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned,
the dimension is in mm.
• This document assumes that the parameter setting visibility is "Advanced".
1.4.3 Functions, codes and symbols
Table 1: Functions included in the relay
Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Protection
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1 3I>>> (1) 50P-3
Three-phase directional overcurrent
protection, low stage
DPHLPDOC1 3I> -> (1) 67/51P-1
DPHLPDOC2 3I> -> (2) 67/51P-2
Three-phase directional overcurrent
protection, high stage
DPHHPDOC1 3I>> -> (1) 67/50P-1
Non-directional ground-fault protection, high
stage
EFHPTOC1 Io>> (1) 50G-1
Table continues on next page
Section 1 1MAC807603-MB A
Introduction
8RED615 ANSI
Application Manual

Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Directional ground-fault protection, low stage DEFLPDEF1 Io> -> (1) 67/51N-1
DEFLPDEF2 Io> -> (2) 67/51N-2
Directional ground-fault protection, high
stage
DEFHPDEF1 Io>> -> (1) 67/50N-1
Admittance-based ground-fault protection EFPADM1 Yo> -> (1) 21YN-1
EFPADM2 Yo> -> (2) 21YN-2
EFPADM3 Yo> -> (3) 21YN-3
Wattmetric-based ground-fault protection WPWDE1 Po> -> (1) 32N-1
WPWDE2 Po> -> (2) 32N-2
WPWDE3 Po> -> (3) 32N-3
Transient/intermittent ground-fault
protection
INTRPTEF1 Io> -> IEF (1) 67NIEF
Harmonics-based ground-fault protection HAEFPTOC1 Io>HA (1) 51NHA
Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46-1
NSPTOC2 I2> (2) 46-2
Phase discontinuity protection PDNSPTOC1 I2/I1> (1) 46PD
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G
ROVPTOV2 Uo> (2) 59N-1
ROVPTOV3 Uo> (3) 59N-2
Three-phase undervoltage protection PHPTUV1 3U< (1) 27-1
PHPTUV2 3U< (2) 27-2
PHPTUV3 3U< (3) 27-3
Three-phase overvoltage protection PHPTOV1 3U> (1) 59-1
PHPTOV2 3U> (2) 59-2
PHPTOV3 3U> (3) 59-3
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U-1
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47-1
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81-1
FRPFRQ2 f>/f<,df/dt (2) 81-2
FRPFRQ3 f>/f<,df/dt (3) 81-3
FRPFRQ4 f>/f<,df/dt (4) 81-4
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1 3Ith>F (1) 49F-1
Three-phase thermal overload protection,
two time constants
T2PTTR1 3Ith>T/G/C (1) 49T-1
Binary signal transfer BSTGGIO1 BST (1) BST-1
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 50BF-1
Three-phase inrush detector INRPHAR1 3I2f> (1) INR-1
Table continues on next page
1MAC807603-MB A Section 1
Introduction
RED615 ANSI 9
Application Manual

Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Switch onto fault CBPSOF1 SOTF (1) SOTF-1
Master trip TRPPTRC1 Master Trip (1) 86/94-1
TRPPTRC2 Master Trip (2) 86/94-2
Multipurpose protection MAPGAPC1 MAP (1) MAP-1
MAPGAPC2 MAP (2) MAP-2
MAPGAPC3 MAP (3) MAP-3
MAPGAPC4 MAP (4) MAP-4
MAPGAPC5 MAP (5) MAP-5
MAPGAPC6 MAP (6) MAP-6
MAPGAPC7 MAP (7) MAP-7
MAPGAPC8 MAP (8) MAP-8
MAPGAPC9 MAP (9) MAP-9
MAPGAPC10 MAP (10) MAP-10
MAPGAPC11 MAP (11) MAP-11
MAPGAPC12 MAP (12) MAP-12
MAPGAPC13 MAP (13) MAP-13
MAPGAPC14 MAP (14) MAP-14
MAPGAPC15 MAP (15) MAP-15
MAPGAPC16 MAP (16) MAP-16
MAPGAPC17 MAP (17) MAP-17
MAPGAPC18 MAP (18) MAP-18
Fault locator SCEFRFLO1 FLOC (1) 21FL-1
Line differential protection with in-zone
power transformer
LNPLDF1 3Id/I> (1) 87L-1
High-impedance fault detection PHIZ1 HIF (1) HIZ-1
Power quality
Current total demand distortion CMHAI1 PQM3I (1) PQI-1
Voltage total harmonic distortion VMHAI1 PQM3U (1) PQVPH-1
Voltage variation PHQVVR1 PQMU (1) PQSS-1
Voltage unbalance VSQVUB1 PQUUB (1) PQVUB-1
Control
Circuit-breaker control CBXCBR1 I <-> O CB (1) 52-1
Disconnector control DCXSWI1 I <-> O DCC (1) 29DS-1
DCXSWI2 I <-> O DCC (2) 29DS-2
Grounding switch control ESXSWI1 I <-> O ESC (1) 29GS-1
Table continues on next page
Section 1 1MAC807603-MB A
Introduction
10 RED615 ANSI
Application Manual

Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Disconnector position indication DCSXSWI1 I <-> O DC (1) 52-TOC
DCSXSWI2 I <-> O DC (2) 29DS-1
DCSXSWI3 I <-> O DC (3) 29DS-2
Grounding switch indication ESSXSWI1 I <-> O ES (1) 29GS-1
ESSXSWI2 I <-> O ES (2) 29GS-2
Autoreclosing DARREC1 O -> I (1) 79
Synchronism and energizing check SECRSYN1 SYNC (1) 25
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM (1) 52CM-1
Trip circuit supervision TCSSCBR1 TCS (1) TCM-1
TCSSCBR2 TCS (2) TCM-2
Current circuit supervision CCSPVC1 MCS 3I (1) CCM
Fuse failure supervision SEQSPVC1 FUSEF (1) 60-1
Protection communication supervision PCSITPC1 PCS (1) PCS-1
Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM-1
Measurement
Load profile record LDPRLRC1 LOADPROF (1) LoadProf
Three-phase current measurement CMMXU1 3I (1) IA, IB, IC
Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0
Residual current measurement RESCMMXU1 Io (1) IG
Three-phase voltage measurement VMMXU1 3U (1) VA, VB, VC
VMMXU2 3U (2) VA, VB, VC (2)
Residual voltage measurement RESVMMXU1 Uo (1) VG-1
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0
Single-phase power and energy
measurement
SPEMMXU1 SP, SE SP, SE-1
Three-phase power and energy
measurement
PEMMXU1 P, E (1) P, E-1
RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1)
Frequency measurement FMMXU1 f (1) f
IEC 61850-9-2 LE sampled value sending SMVSENDER SMVSENDER SMVSENDER
IEC 61850-9-2 LE sampled value receiving
(voltage sharing)
SMVRECEIVER SMVRECEIVER SMVRECEIVER
Other
Table continues on next page
1MAC807603-MB A Section 1
Introduction
RED615 ANSI 11
Application Manual

Function IEC 61850 IEC 60617 ANSI/C37.2-2008
Minimum pulse timer TPGAPC1 TP (1) 62TP-1
TPGAPC2 TP (2) 62TP-2
TPGAPC3 TP (3) 62TP-3
TPGAPC4 TP (4) 62TP-4
Minimum pulse timer (second resolution) TPSGAPC1 TPS (1) 62TPS-1
Minimum pulse timer (minute resolution) TPMGAPC1 TPM (1) 62TPM-1
Pulse timer PTGAPC1 PT (1) 62PT-1
PTGAPC2 PT (2) 62PT-2
Time delay off TOFGAPC1 TOF (1) 62TOF-1
TOFGAPC2 TOF (2) 62TOF-2
TOFGAPC3 TOF (3) 62TOF-3
TOFGAPC4 TOF (4) 62TOF-4
Time delay on TONGAPC1 TON (1) 62TON-1
TONGAPC2 TON (2) 62TON-2
TONGAPC3 TON (3) 62TON-3
TONGAPC4 TON (4) 62TON-4
Set-reset SRGAPC1 SR (1) SR-1
SRGAPC2 SR (2) SR-2
SRGAPC3 SR (3) SR-3
SRGAPC4 SR (4) SR-4
Move MVGAPC1 MV (1) MV-1
MVGAPC2 MV (2) MV-2
Generic control point SPCGAPC1 SPC (1) SPC-1
SPCGAPC2 SPC (2) SPC-2
Analog value scaling SCA4GAPC1 SCA4 (1) SCA4-1
SCA4GAPC2 SCA4 (2) SCA4-2
SCA4GAPC3 SCA4 (3) SCA4-3
SCA4GAPC4 SCA4 (4) SCA4-4
Integer value move MVI4GAPC1 MVI4 (1) MVI4-1
Generic up-down counters UDFCNT1 UDCNT (1) CTR-1
UDFCNT2 UDCNT (2) CTR-2
UDFCNT3 UDCNT (3) CTR-3
UDFCNT4 UDCNT (4) CTR-4
Section 1 1MAC807603-MB A
Introduction
12 RED615 ANSI
Application Manual

Section 2 RED615 overview
2.1 Overview
RED615 is a phase-segregated two-end line differential protection and control relay
designed for utility and industrial power systems, including radial, looped and meshed
distribution networks with or without distributed power generation. RED615 is also
designed for the protection of line differential applications with a transformer within the
protection zone. RED615 relays communicate between substations over a fiber optic link
or a galvanic pilot wire connection. RED615 is a member of ABB’s Relion® product
family and part of its 615 protection and control product series. The 615 series relays are
characterized by their compactness and withdrawable-unit design. Re-engineered from
the ground up, the 615 series has been guided by the IEC 61850 standard for
communication and interoperability of substation automation equipment.
The relay provides unit type main protection for overhead lines and cable feeders in
distribution networks. The relay also features current-based protection functions for
remote back-up for down-stream protection relays and local back-up for the line
differential main protection. Standard configurations D and E include directional
overcurrent and voltage based protection functions.
The relay is adapted for the protection of overhead line and cable feeders in isolated
neutral, resistance grounded, compensated (impedance grounded) and solidly grounded
networks. Once the relay has been given the application-specific settings, it can directly
be put into service.
The 615 series relays support a range of communication protocols including IEC 61850
with Edition 2 support, process bus according to IEC 61850-9-2 LE, Modbus® and
DNP3.
2.1.1 Product version history
Product version Product history
5.0 FP1 Product released
2.1.2 PCM600 and relay connectivity package version
• Protection and Control IED Manager PCM600 2.8 or later
• RED615 Connectivity Package Ver.5.1 or later
1MAC807603-MB A Section 2
RED615 overview
RED615 ANSI 13
Application Manual

• Parameter Setting
• Signal Monitoring
• Event Viewer
• Disturbance Handling
• Application Configuration
• Signal Matrix
• Graphical Display Editor
• Communication Management
• IED User Management
• IED Compare
• Firmware Update
• Fault Record tool
• Load Record Profile
• Lifecycle Traceability
• Configuration Wizard
• AR Sequence Visualizer
• Label Printing
• IEC 61850 Configuration
• IED Configuration Migration
• Differential Characteristics Tool
Download connectivity packages from the ABB Web site
http://www.abb.com/substationautomation or directly with Update
Manager in PCM600.
2.2 Operation functionality
2.2.1 Optional features
• Autoreclosing
• Modbus TCP/IP or RTU/ASCII
• DNP3 TCP/IP or serial
• Admittance-based ground-fault protection
• Wattmetric-based ground-fault protection
• Harmonics-based ground-fault protection
• Power quality functions
• Fault locator
• RTD/mA measurement (configuration D only)
• IEC 61850-9-2 LE (with 2 × LC only)
• IEEE 1588 v2 time synchronization (with 2 × LC only)
Section 2 1MAC807603-MB A
RED615 overview
14 RED615 ANSI
Application Manual
Other manuals for Relion 615 series
41
This manual suits for next models
1
Table of contents
Other ABB Relay manuals
Popular Relay manuals by other brands

Grundfos
Grundfos Magna Installation and operating instructions

KinCony
KinCony KC868-H32w user manual

Circutor
Circutor RGU-10 quick start guide

Pilz
Pilz PNOZ e6.1p operating instructions

Siemens
Siemens SIRIUS 3ZX1012-0RU11-1DA1 operating instructions

Novatek-electro
Novatek-electro REV-120 operating manual

Stahl
Stahl IS1+ 9477/15 Series operating instructions

Siemens
Siemens 5TT5 200 operating instructions

Extron electronics
Extron electronics SCP 150 AAP user manual

sisel
sisel ENDA EPDA1 Series instructions

Contrinex
Contrinex YRB-4EML-31S Applications manual

Allen-Bradley
Allen-Bradley 140G Series quick start guide