ABB TTH300 Series User manual

Operating Instruction OI/TTH300-EN Rev. D
TTH300
Head-mount temperature transmitter
Measurement made easy

2 OI/TTH300-EN Rev. D | TTH300
Short product description
Head-mount temperature transmitter for the measurement of
the temperature of liquid and gaseous measuring media.
Further information
A
dditional documentation on TTH300 is available to download
free of charge at www.abb.com/temperature.
A
lternatively, scan this code:
Manufacturer
A
BB Automation Products GmbH
Process Automation
Schillerstr. 72
32425 Minden
Germany
Tel: +49 571 830-0
Fax: +49 571 830-1806
Customer service center
Tel: +49 180 5 222 580
Change from one to two columns

TTH300 | OI/TTH300-EN Rev. D 3
Contents
1Safety............................................................................... 5
1.1General information and instructions .................... 5
1.2Warnings ............................................................. 5
1.3Intended use........................................................ 5
1.4Improper use ....................................................... 5
1.5Warranty provisions ............................................. 5
2Use in potentially explosive atmospheres according to
ATEX and IECEx.............................................................. 6
2.1Ex-marking .......................................................... 6
2.1.1Transmitter .......................................................... 6
2.1.2LCD indicators..................................................... 6
2.2Temperature data ................................................ 6
2.2.1Transmitter .......................................................... 6
2.2.2LCD indicators..................................................... 6
2.3Electrical data ...................................................... 7
2.3.1Transmitter .......................................................... 7
2.3.2LCD indicators..................................................... 7
2.4Installation instructions......................................... 7
2.4.1ATEX / IECEx....................................................... 7
2.4.2IP protection rating of housing ............................. 7
2.4.3Electrical connections .......................................... 8
2.5Commissioning.................................................... 9
2.6Operating instructions.......................................... 9
2.6.1Protection against electrostatic discharges .......... 9
3Use in potentially explosive atmospheres in accordance
with FM and CSA .......................................................... 10
3.1Ex-marking ........................................................ 10
3.1.1Transmitter ........................................................ 10
3.1.2LCD indicators................................................... 10
3.2Installation instructions....................................... 11
3.2.1FM / CSA........................................................... 11
3.2.2IP protection rating of housing ........................... 11
3.2.3Electrical connections ........................................ 11
3.3Commissioning.................................................. 11
3.4Operating instructions........................................ 11
3.4.1Protection against electrostatic discharges ........ 11
4Function and System Design........................................ 12
4.1Input functionality............................................... 12
4.1.1Sensor Redundancy .......................................... 12
4.1.2Sensor drift monitoring....................................... 12
4.1.3Sensor error adjustment according to Callendar-
Van Dusen......................................................... 13
5Product identification.................................................... 13
5.1Name plate........................................................ 13
6Transport and storage .................................................. 14
6.1Inspection.......................................................... 14
6.2Transporting the device ..................................... 14
6.3Storing the device.............................................. 14
6.3.1Ambient conditions ............................................ 14
6.4Returning devices .............................................. 14
7Installation ..................................................................... 14
7.1Installation options ............................................. 14
7.1.1Installation in the cover of the connection head .. 14
7.1.2Installation on the measuring inset...................... 15
7.1.3Installation on the top-hat rail ............................. 15
7.2Installing / removing the optional LCD indicator .. 15
7.3Electrical connections ........................................ 16
7.3.1Conductor material ............................................ 16
7.3.2Pin configuration ................................................ 17
7.3.3Electrical data for inputs and outputs ................. 18
7.4Power supply..................................................... 20
7.4.1Power supply - HART ........................................ 20
7.4.2Power supply - PROFIBUS / FOUNDATION
Fieldbus............................................................. 21
8Commissioning.............................................................. 21
8.1General remarks ................................................ 21
8.2Checks prior to commissioning .......................... 21
8.3Basic Setup ....................................................... 21
9Operation....................................................................... 22
9.1Safety instructions.............................................. 22
9.2Hardware settings.............................................. 22
9.3Menu navigation ................................................ 22
9.4HART menu levels ............................................. 23
9.5PROFIBUS PA and FOUNDATION Fieldbus H1
menu levels........................................................ 23
9.5.1Process display.................................................. 24
9.5.2Switching to the information level(PROFIBUS PA
and FOUNDATION Fieldbus only)....................... 25
9.5.3Switching to the configuration level
(parameterization) .............................................. 25
9.5.4Selecting and changing parameters ................... 26
9.6HART parameter overview ................................. 27
9.7HART parameter description.............................. 28
9.7.1Menu: Device Info .............................................. 30
9.7.2Menu: Display.................................................... 30
9.7.3Menu: Process Alarm......................................... 30
9.7.4Menu: Communication....................................... 30
9.7.5Menu: Calibrate ................................................. 31
9.7.6Menu: Diagnosis ................................................ 31
9.7.7Activating write protection.................................. 31
9.7.8Deactivating write protection .............................. 31
9.8PROFIBUS PA and FOUNDATION Fieldbus
parameter overview............................................ 32
9.9PROFIBUS PA and FOUNDATION Fieldbus
parameter description ........................................ 33
9.9.1Menu: Device Setup........................................... 33
9.9.2Menu: Device Info .............................................. 34
9.9.3Menu: Communication....................................... 34
9.9.4Menu: Service Menu .......................................... 35
9.9.5Menu: Display.................................................... 35
9.9.6Menu: Calibrate ................................................. 36
9.10Factory settings ................................................. 36

4 OI/TTH300-EN Rev. D | TTH300
10Diagnosis / error messages.......................................... 37
10.1Diagnostic information ....................................... 37
10.1.1Monitoring of operating data .............................. 37
10.1.2Operating hours statistics .................................. 37
10.2Calling up the error description .......................... 37
10.3Possible HART error messages.......................... 38
10.4Possible PROFIBUS PA and FOUNDATION
Fieldbus error messages.................................... 39
11Maintenance.................................................................. 40
11.1Cleaning ............................................................ 40
12Repair ............................................................................ 40
12.1Returning devices .............................................. 40
13Recycling and disposal................................................. 40
13.1Disposal ............................................................ 40
13.2Information on ROHS Directive 2011/65/EC....... 40
14Spare parts, consumables and accessories................ 40
15Specifications................................................................ 41
16Declaration of conformity ............................................. 41
17Appendix ....................................................................... 42
17.1Return form ....................................................... 42

TTH300 | OI/TTH300-EN Rev. D 5
1Safety
1.1 General information and instructions
These instructions are an important part of the product and
must be retained for future reference.
Installation, commissioning, and maintenance of the product
may only be performed by trained specialist personnel who
have been authorized by the plant operator accordingly. The
specialist personnel must have read and understood the
manual and must comply with its instructions.
For additional information or if specific problems occur that are
not discussed in these instructions, contact the manufacturer.
The content of these instructions is neither part of nor an
amendment to any previous or existing agreement, promise or
legal relationship.
Modifications and repairs to the product may only be
performed if expressly permitted by these instructions.
Information and symbols on the product must be observed.
These may not be removed and must be fully legible at all
times.
The operating company must strictly observe the applicable
national regulations relating to the installation, function testing,
repair and maintenance of electrical products.
1.2 Warnings
The warnings in these instructions are structured as follows:
DANGER
The signal word "DANGER" indicates an imminent danger.
Failure to observe this information will result in death or
severe injury.
WARNING
The signal word "WARNING" indicates an imminent danger.
Failure to observe this information may result in death or
severe injury.
CAUTION
The signal word "CAUTION" indicates an imminent danger.
Failure to observe this information may result in minor or
moderate injury.
NOTE
The signal word "NOTE" indicates useful or important
information about the product.
The signal word "NOTE" is not a signal word indicating a
danger to personnel. The signal word "NOTE" can also refer
to material damage.
1.3 Intended use
This device is intended for the following uses:
— To measure the temperature of fluid, pulpy or pasty
substances and gases or resistance/voltage values.
The device has been designed for use exclusively within the
values stated on the name plate and within the technical limit
values specified on the data sheets.
— The maximum and minimum operating temperature limits
must not be exceeded or undershot.
— The permissible ambient temperature must not be
exceeded.
— The housing's degree of protection must be observed
during operation.
1.4 Improper use
The following are considered to be instances of improper use
of the device:
— Material application, e.g. by painting over the name plate
or welding/soldering on parts.
— Material removal, e.g. by spot drilling the housing.
1.5 Warranty provisions
Using the device in a manner that does not fall within the
scope of its intended use, disregarding this manual, using
underqualified personnel, or making unauthorized alterations
releases the manufacturer from liability for any resulting
damage. This renders the manufacturer's warranty null and
void.

6 OI/TTH300-EN Rev. D | TTH300
2Use in potentially explosive
atmospheres according to ATEX and
IECEx
NOTICE
— Further information on the approval of devices for use in
potentially explosive atmospheres can be found in the
explosion protection test certificates (at
www.abb.com/temperature).
— Depending on the design, a specific marking in
accordance with ATEX or IECEx applies.
2.1 Ex-marking
2.1.1 Transmitter
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for
use in Zone 0, 1 and 2.
Model TTH300-E1H
Type examination certificate PTB 05 ATEX 2017
II 1 G Ex ia IIC T6 Ga
II 2 (1) G Ex [ia] ib IIC T6 Gb (Ga)
II 2 G (1D) Ex [iaD] ib IIC T6 Gb (Da)
Model TTH300-E1P and TTH300-E1F
Type examination certificate PTB 09 ATEX 2016 X
II 1G Ex ia IIC T6
II 2(1)G Ex [ia] ib IIC T6
II 2G(1D) Ex [iaD] ib IIC T6
Non-sparking ATEX
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for
use in Zone 2.
Model TTH300-E2X
Declaration of conformity
II 3 G Ex nA IIC T1-T6 Gc
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
Model TTH300-H1H
IECEx certificate of conformity IECEx PTB 09.0014X
Model TTH300-H1P and TTH300-H1F
IECEx certificate of conformity IECEx PTB 11.0108X
Ex ia IIC T6
Ex [ia] ib IIC T6
Ex [iaD] ib IIC T6
2.1.2 LCD indicators
ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EC in
case of corresponding purchase orders and is approved for
use in Zone 0, 1 and 2.
Type Examination Test Certificate: PTB 05 ATEX 2079 X
II 1G Ex ia IIC T6 Ga
Non-sparking ATEX
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for
use in Zone 2.
Declaration of conformity
II 3 G Ex nA IIC T1-T6 Gc
IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
IECEx certificate of conformity IECEx PTB 12.0028X
Ex ia IIC T6
2.2 Temperature data
2.2.1 Transmitter
ATEX/IECEx intrinsic safety, non-sparking ATEX
Temperature class Permissible ambient temperature range
Device category 1
use
Device category 2 / 3
use
T6 -50 … 44 °C
(-58 ... 111.2 °F)
-50 … 56 °C
(-58 ... 132.8 °F)
T5 -50 … 56 °C
(-58 ... 132.8 °F)
-50 … 71 °C
(-58 ... 159.8 °F)
T4-T1 -50 … 60 °C
(-58 ... 140.0 °F)
-50 … 85 °C
(-58 ... 185.0 °F)
2.2.2 LCD indicators
ATEX/IECEx intrinsic safety, non-sparking ATEX
Temperature class Permissible ambient temperature range
Device category 1
use
Device category 2 / 3
use
T6 -40 … 44 °C
(-40 … 111.2 °F)
-40 … 56 °C
(-40 … 132.8 °F)
T5 -40 … 56 °C
(-40 … 132.8 °F)
-40 … 71 °C
(-40 … 159.8 °F)
T4-T1 -40 … 60 °C
(-40 … 140 °F)
-40 … 85 °C
(-40 … 185 °F)

TTH300 | OI/TTH300-EN Rev. D 7
2.3 Electrical data
2.3.1 Transmitter
Intrinsic safety type of protection Ex ia IIC (part 1)
TTH300-E1H
TTH300-H1H
Supply circuit
TTH300-E1P/-H1P
TTH300-E1F/-H1F
Supply circuit 1)
FISCO ENTITY
max. Voltage Ui= 30 V Ui≤ 17.5 V Ui≤ 24.0 V
Short-circuit current Ii= 130 mA Ii≤ 183 mA2) I
i≤ 250 mA
max. Performance Pi= 0.8 W Pi≤ 2.56 W2) P
i≤ 1.2 W
Internal inductance Li= 0.5 mH Li≤ 10 H Li≤ 10 H
Internal capacitance Ci= 0.57 nF3) C
i≤ 5 nF Ci≤ 5 nF
1) FISCO in accordance with 60079-27
2) II B FISCO: Ii ≤ 380 mA, Pi ≤ 5.32 W
3) Only applies to HART variants. From HW rev. 1.07, previously 5 nF
Intrinsic safety type of protection Ex ia IIC (part 2)
Measurement circuit:
resistance thermometer,
resistances
Measurement circuit:
thermocouples,
voltages
max. Voltage Uo= 6.5 V Uo= 1.2 V
Short-circuit current Io= 25 mA Io= 50 mA
max. Performance Po= 38 mW Po= 60 mW
Internal inductance Li= 0 mH Li= 0 mH
Internal capacitance Ci= 49 nF Ci= 49 nF
Maximum permissible
external inductance
Lo= 5 mH Lo= 5 mH
Maximum permissible
external capacitance
Co= 1.55 F Co= 1.05 F
Intrinsic safety type of protection Ex ia IIC (part 3)
LCD indicator interface
max. Voltage Uo= 6.2 V
Short-circuit current Io= 65.2 mA
max. Performance Po= 101 mW
Internal inductance Li= 0 mH
Internal capacitance Ci= 0 nF
Maximum permissible external
inductance
Lo= 5 mH
Maximum permissible external
capacitance
Co= 1.4 F
2.3.2 LCD indicators
Intrinsic safety type of protection Ex ia IIC
Supply circuit
Max. voltage Ui= 9 V
Short-circuit current Ii= 65,2 mA
Max. power Pi= 101 mW
Internal inductance Li= 0 mH
Internal capacitance Ci= 0 nF
2.4 Installation instructions
2.4.1 ATEX / IECEx
The installation, commissioning, maintenance and repair of
devices in potentially explosive atmospheres must only be
carried out by appropriately trained personnel. Works may be
carried out only by persons, whose training has included
instructions on different types of ignition protection types and
installation techniques, concerned rules and regulations as
well as general principles of zoning. The person must possess
the relevant expertise for the type of works to be executed.
When operating with combustible dusts, EN 60079-31 must
be complied with.
The safety instructions for electrical apparatus in potentially
explosive areas must be complied with, in accordance with the
directive 2014/34/EU (ATEX) and e.g. IEC
60079-14 (Installation of equipment in potentially explosive
atmospheres).
To ensure safe operation, the respectively applicable
requirements must be met for the protection of workers.
2.4.2 IP protection rating of housing
The temperature transmitter and LCD indicator types A and
AS must be installed such that the IP rating of at least IP20 is
achieved in accordance with IEC 60529.

8 OI/TTH300-EN Rev. D | TTH300
2.4.3 Electrical connections
Earthing
If, for functional reasons, the intrinsically safe circuit needs to
be earthed by means of a connection to the potential
equalization, it may only be earthed at one point.
Intrinsic safety installation check
If transmitters are operated in an intrinsically safe circuit, proof
that the interconnection is intrinsically safe must be provided
in accordance with IEC/EN 60079-14 as well as
IEC/EN 60079-25.
The supply isolators / DCS inputs must feature intrinsically
safe input protection circuits in order to eliminate hazards
(spark formation).
In order to provide proof of intrinsic safety, the electrical limit
value must be used as the basis for the EC-type examination
certificates for the equipment (devices); this includes the
capacitance and inductance values of the cables.
Proof of intrinsic safety is said to have been provided if the
following conditions are fulfilled when a comparison is carried
out in relation to the limit values of the equipment:
Transmitters
(intrinsically safe equipment)
Supply isolator / DCS input
(related equipment)
Ui≥ Uo
Ii≥ Io
Pi≥ Po
Li+ Lc(cable) ≤ Lo
Ci+ Cc(cable) ≤ Co
Field (Ex area) Control room (safe area)
Fig. 1
ATransmitter BSupply isolator / DCS input with supply / Segment
coupler
Installation in a potentially explosive atmosphere
Transmitters can be installed in all kinds of industrial sectors.
Potentially explosive systems are divided into zones, meaning
that a wide range of different instruments are also required.
For this, pay attention to the country-specific guidelines and
certificates!
NOTICE
Ex relevant specifications must be taken from the EC-type
examination certificates and other relevant certificates that
apply in each case.
With transmitters for PROFIBUS PA and FOUNDATION
Fieldbus H1 applications, FISCO interconnection methods can
be used.
ATEX - Zone 0
Designation: II 1 G Ex ia IIC T6 Ga
Ex-area Zone 0 Safe area
Fig. 2
ASensor BTransmitter in the housing with IP rating IP 20
Cseparator [Ex ia] Dinterface for LCD display
When using the transmitter in Zone 0, it must be installed in a
suitable housing with IP -rating IP 20. The input for the supply
isolator must have an [Ex ia] design.
When using the transmitter in Zone 0, you must ensure that
impermissible electrostatic charging of the temperature
transmitter is prevented (observe the warnings on the device).
As the user, it is your responsibility to ensure that the sensor
instrumentation meets the requirements of applicable
explosion protection standards.
A10096
AB
+
-
+
-
A11229
ia
ia
J
D
ia
ACB

TTH300 | OI/TTH300-EN Rev. D 9
ATEX - Zone 1 (0)
Designation: II 2 (1) G Ex [ia] ib IIC T6 Gb (Ga)
Zone 0
or 1
Ex-area Zone 1 Safe area
Fig. 3
ASensor BTransmitter in the housing with IP rating IP 20
Cseparator [Ex ib] Dinterface for LCD display
When using the transmitter in Zone 1, it must be installed in a
suitable housing with IP rating IP20. The input for the supply
isolator must have an [Ex ib] design. When using the
transmitter in Zone 1, you must ensure that impermissible
electrostatic charging of the temperature transmitter is
prevented (observe the warnings on the device). As the user, it
is your responsibility to ensure that the sensor instrumentation
meets the requirements of applicable explosion protection
standards. The sensor can be installed in Zone 1 or Zone 0.
ATEX - Zone 1 (20)
Designation: II 2 G (1D) Ex [iaD] ib IIC T6 Gb (Da)
Zone 0, 1
or 20
Ex-area Zone 1 Safe area
Fig. 4
ASensor BTransmitter in the housing with IP rating IP 20
Cseparator [Ex ib] Dinterface for LCD display
When using the transmitter in Zone 1, it must be installed in a
suitable housing with IP rating IP20. The input for the supply
isolator must have an [Ex ib] design.
When using the transmitter in Zone 1, you must ensure that
impermissible electrostatic charging of the temperature
transmitter is prevented (observe the warnings on the device).
As the user, it is your responsibility to ensure that the sensor
instrumentation meets the requirements of applicable
explosion protection standards. The sensor can be installed in
Zone 0, Zone 1, or Zone 20.
ATEX - Zone 2
Designation: II 3 G Ex nA IIC T1-T6 Gc
Ex-area Zone 2 Safe area
Fig. 5
ASensor BTransmitter in the housing with IP rating IP 54
Cseparator Dinterface for LCD display
When using the transmitter in Zone 2, observe the following:
— The temperature transmitter must be installed in its own
housing. This housing must at least meet IP rating IP54 (in
accordance with EN 60529) and the other requirements of
the potentially explosive atmosphere (e. g. a certified
housing).
— External measures must be made for the power supply
circuit in order to prevent the rated voltage from being
exceeded by more than 40% in the event of transient
disturbances.
— The electrical connections may only be opened or closed
when there is no hazardous atmosphere.
— When using the transmitter in Zone 2, you must ensure
that impermissible electrostatic charging of the
temperature transmitter is prevented (observe the
warnings on the device).
2.5 Commissioning
The commissioning and parameterization of the device may
also be carried out in potentially explosive atmospheres using
a handheld terminal that has been approved accordingly under
consideration of an intrinsic safety installation check.
Alternatively, an Ex modem can be connected to the circuit
outside the potentially explosive atmosphere.
2.6 Operating instructions
2.6.1 Protection against electrostatic discharges
The plastic parts inside the device can store electrostatic
charges.
Make sure that no electrostatic charges can accumulate when
handling the device.
A11127
ib
ia
J
D
ia
CBA
A11128
ib
ib
ia
J
D
ia
CBA
A11129
J
CB
D
A

10 OI/TTH300-EN Rev. D | TTH300
3Use in potentially explosive
atmospheres in accordance with FM
and CSA
NOTICE
— Further information on the approval of devices for use in
potentially explosive atmospheres can be found in the
explosion protection test certificates (at
www.abb.com/temperature).
— Depending on the design, a specific marking in
accordance with FM or CSA applies.
3.1 Ex-marking
3.1.1 Transmitter
FM Intrinsically Safe
Model TTH300-L1H
Control Drawing SAP_214829
Model TTH300-L1P
Control Drawing TTH300-L1P (IS)
Model TTH300-L1F
Control Drawing TTH300-L1F (IS)
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC T6
FM Non-Incendive
Model TTH300-L2H
Control Drawing 214831 (Non-Incendive)
Model TTH300-L2P
Control Drawing TTH300-L2P (NI_PS)
TTH300-L2P (NI_AA)
Model TTH300-L2F
Control Drawing TTH300-L2F (NI_PS)
TTH300-L2F (NI_AA)
Class I, Div. 2, Groups A, B, C, D
CSA Intrinsically Safe
Model TTH300-R1H
Control Drawing 214826
Model TTH300-R1P
Control Drawing TTH300-R1P (IS)
Model TTH300-R1F
Control Drawing TTH300-R1F (IS)
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, Ex ia Group IIC T6
CSA Non-Incendive
Model TTH300-R2H
Control Drawing SAP_214824 (Non-Incendive)
SAP_214896 (Non-Incendive)
Model TTH300-R2P
Control Drawing TTH300-R2P (NI_PS)
TTH300-R2P (NI_AA)
Model TTH300-R2F
Control Drawing TTH300-R2F (NI_PS)
TTH300-R2F (NI_AA)
Class I, Div. 2, Groups A, B, C, D
3.1.2 LCD indicators
FM Intrinsically Safe
Control Drawing SAP_214 748
I.S. Class I Div 1 and Div 2, Group: A, B, C, D or
I.S. Class I Zone 0 AEx ia IIC T1)
Ui/ Vmax = 9 V, Ii/ Imax < 65.2 mA, Pi= 101 mW, Ci= 0.4 F, Li= 0
FM Non-Incendive
Control Drawing SAP_214 751
N.I. Class I Div 2, Group: A, B, C, D or Ex nL IIC T2), Class I Zone 2
Ui/ Vmax = 9 V, Ii/ Imax < 65.2 mA, Pi= 101 mW, Ci= 0.4 F, Li= 0
CSA Intrinsically Safe
Control Drawing SAP_214 749
I.S. Class I Div 1 and Div 2; Group: A, B, C, D or
I.S Zone 0 Ex ia IIC T1)
Ui/ Vmax = 9 V, Ii/ Imax < 65.2 mA, Pi= 101 mW, Ci< 0.4 F, Li= 0
CSA Non-Incendive
Control Drawing SAP_214 750
N.I. Class I Div 2, Group: A, B, C, D oder Ex nL IIC T2), Class I Zone 2
Ui/ Vmax = 9 V, Ii/ Imax < 65.2 mA, Pi= 101 mW, Ci< 0.4 F, Li= 0
1) Temp. Ident: T6 Tamb 56 °C, T4 Tamb 85 °C
2) Temp. Ident: T6 Tamb 60 °C, T4 Tamb 85 °C

TTH300 | OI/TTH300-EN Rev. D 11
3.2 Installation instructions
3.2.1 FM / CSA
The installation, commissioning, maintenance and repair of
devices in areas with explosion hazard must only be carried
out by appropriately trained personnel.
The operator must strictly observe the applicable national
regulations with regard to installation, function tests, repairs,
and maintenance of electrical devices. (e.g. NEC, CEC).
3.2.2 IP protection rating of housing
The temperature transmitter and LCD indicator types A and
AS must be installed such that the IP rating of at least IP20 is
achieved in accordance with IEC 60529.
3.2.3 Electrical connections
Earthing
If, for functional reasons, the intrinsically safe circuit needs to
be earthed by means of a connection to the potential
equalization, it may only be earthed at one point.
Intrinsic safety installation check
If transmitters are operated in an intrinsically safe circuit, proof
that the interconnection is intrinsically safe must be provided
in accordance with IEC/EN 60079-14 as well as
IEC/EN 60079-25.
The supply isolators / DCS inputs must feature intrinsically
safe input protection circuits in order to eliminate hazards
(spark formation).
In order to provide proof of intrinsic safety, the electrical limit
value must be used as the basis for the EC-type examination
certificates for the equipment (devices); this includes the
capacitance and inductance values of the cables.
Proof of intrinsic safety is said to have been provided if the
following conditions are fulfilled when a comparison is carried
out in relation to the limit values of the equipment:
Transmitters
(intrinsically safe equipment)
Supply isolator / DCS input
(related equipment)
Ui≥ Uo
Ii≥ Io
Pi≥ Po
Li+ Lc(cable) ≤ Lo
Ci+ Cc(cable) ≤ Co
Field (Ex area) Control room (safe area)
Fig. 6
ATransmitter BSupply isolator / DCS input with supply / Segment
coupler
Installation in a potentially explosive atmosphere
Transmitters can be installed in all kinds of industrial sectors.
Potentially explosive systems are divided into zones, meaning
that a wide range of different instruments are also required.
For this, pay attention to the country-specific guidelines and
certificates!
NOTICE
Ex relevant specifications must be taken from the EC-type
examination certificates and other relevant certificates that
apply in each case.
With transmitters for PROFIBUS PA and FOUNDATION
Fieldbus H1 applications, FISCO interconnection methods can
be used.
3.3 Commissioning
The commissioning and parameterization of the device may
also be carried out in potentially explosive atmospheres using
a handheld terminal that has been approved accordingly under
consideration of an intrinsic safety installation check.
Alternatively, an Ex modem can be connected to the circuit
outside the potentially explosive atmosphere.
3.4 Operating instructions
3.4.1 Protection against electrostatic discharges
The plastic parts inside the device can store electrostatic
charges.
Make sure that no electrostatic charges can accumulate when
handling the device.
A10096
AB
+
-
+
-

12 OI/TTH300-EN Rev. D | TTH300
4Function and System Design
Digital transmitters are communication-ready devices with
microprocessor-controlled electronics. They conform to the
requirements of housing IP rating IP20 and are suitable for
integration into DIN A and DIN B sensor heads.
With HART transmitters, an FSK signal is superimposed on the
4 … 20 mA output signal in accordance with the HART
standard to facilitate bidirectional communication.
With PROFIBUS PA transmitters, communication takes place
in accordance with PROFIBUS - MBP (IEC 61158-2),
PROFIBUS PA profile 3.01.
With FF transmitters, communication takes place in
accordance with FOUNDATION Fieldbus H1 (IEC 61158-2),
ITK Version 5.x.
The transmitters can be configured, polled, and tested using a
DTM or an EDD.
As an option, the transmitter can be fitted with a type A or a
type AS LCD indicator. Type AS is used exclusively for
visualizing current process values. Type A also supports the
option of configuring the transmitter. It is recommended that
you use this combination.
The electrical connection between the LCD display and
transmitter is provided by a 6-pin flat ribbon cable with a plug
connector. The LCD display can only be operated when
connected to transmitters that have an LC display interface.
4.1 Input functionality
4.1.1 Sensor Redundancy
To enhance system availability, the TTH300 has two sensor
inputs.
The second sensor input can be used redundantly for both
resistance thermometers (2 x three-wire circuit or 2 x two-wire
circuit) and thermocouples, or for a mixture of the two.
Sensor redundancy (or sensor backup) always involves
measuring the temperature of the two sensors and calculating
the mean value on the basis of this.
This value is provided at the output of the transmitter. Should
a sensor fail, the temperature measurement for the sensor that
remains in operation is provided at the output of the
transmitter.
A relevant diagnostic message is provided via the EDD or
DTM, or shown on the display. The measured value remains
available and maintenance measures can be taken at the
same time.
4.1.2 Sensor drift monitoring
When two sensors are connected, sensor drift monitoring can
be activated via the EDD or DTM.
The sensor drift monitoring can be activated for the following
sensor types:
— 2 x resistance thermometer (RTD), two-wire circuit
— 2 x resistance thermometer (RTD), three-wire circuit
— 2 x resistor (potentiometer), two-wire circuit
— 2 x resistor (potentiometer), three-wire circuit
— 2 x thermocouple
— 2 x voltage
— 1 x resistance thermometer (RTD), two-wire circuit, and
1 x thermocouple
— 1 x resistance thermometer (RTD), three-wire circuit, and
1 x thermocouple
— 1 x resistance thermometer (RTD), four-wire circuit, and
1 x thermocouple
To activate sensor drift monitoring, the transmitter must first
be configured for the sensor types referred to above.
Following this, the maximum permissible sensor deviation
must be configured, e.g., 1 K.
Since sensor response times may differ slightly, it is then
necessary to configure a limit time period during which the
sensor deviation has to constantly exceed the maximum set.
If the transmitter records a larger sensor deviation during the
defined time period, a HART, EDD, and DTM diagnostic
notification - "Maintenance required" - is generated according
to NE 107. At the same time, diagnostic information is shown
on the LCD display.
If drift monitoring is used for the same types of sensor (2 x
Pt100 or 2 x thermocouple), the mean value calculated from
the two sensors is mapped to the transmitter's output signal
as a process variable in redundancy mode.
If a thermocouple is used for Pt100 drift monitoring, the Pt100
sensor (see chapter "Electrical connections" on page 11) must
be connected to channel 1 and the thermocouple to
channel 2.
The measured value from channel 1 (Pt100) is mapped to the
transmitter output as a process variable.
NOTICE
Before configuring the maximum permissible sensor
deviation for drift monitoring, sensor adjustment with respect
to the sensor channel 1 value must be carried out with the
help of the TTH300 DTM.

TTH300 | OI/TTH300-EN Rev. D 13
4.1.3 Sensor error adjustment according to Callendar-
Van Dusen
Under normal circumstances, the standard Pt100
characteristic curve is used for resistance thermometer
measurement.
However, recent advances in technology now mean that
maximum measuring accuracy can be achieved where
necessary by carrying out individual sensor error adjustment.
Sensor characteristic curves are optimized by using a Pt100
polynomial in accordance with IST-90 / IEC 751, and
EN 60150, and by applying A, B, C, or Callendar-Van Dusen
coefficients.
The DTM or EDD can be used to set and store these sensor
coefficients (Callendar-Van Dusen) in the transmitter as a CVD
characteristic curve. Up to five different CVD characteristic
curves can be stored for HART and PROFIBUS PA, and up to
two can be stored for FOUNDATION Fieldbus.
5Product identification
5.1 Name plate
NOTE
Products that are marked with this symbol may
not be disposed of through municipal garbage
collection points.
NOTICE
The ambient temperature range on the name plate (10) refers
only to the transmitter itself and not to the measuring
element used in the measuring inset.
For devices with PROFIBUS PA or FOUNDATION Fieldbus,
the device-ID is also specified.
Fig. 7: HART name plate (example)
Fig. 8: PROFIBUS PA name plate (example)
Fig. 9: FOUNDATION Fieldbus name plate (example)
1Please pay attention to the manufacturer, manufacturer address,
manufacturing status, production year 2Observe product
documentation 3Safety integrity level (optional) 4Model number
5CE-symbols (EU conformity), if nothing is mentioned on the
additional label 6Hardware and Software Version 7Order
number 8TAG -Number (optional) 9Customer configuration
jAmbient temperature range kSupply voltage range, typical
current range, Log lSerial number mOrder number
Devices with an explosion-proof design are marked with the
following special data plate.
Fig. 10: Special data plate for explosion-protected apparatus
(example)
1Model number 2Temperature class Ex-Execution
3CE-symbols (EU conformity) and specific designations of the
quality assurance 4Safety class Ex-execution 5Ex-identification
A11241
1 3 4
5
8
9
j
m
l
k
2
6
7
A11242
A11243
A11240
5
1
3
4
2

14 OI/TTH300-EN Rev. D | TTH300
6Transport and storage
6.1 Inspection
Check the devices immediately after unpacking for possible
damage that may have occurred from improper transport.
Details of any damage that has occurred in transit must be
recorded on the transport documents.
All claims for damages must be submitted to the shipper
without delay and before installation.
6.2 Transporting the device
Observe the following instructions:
— Do not expose the device to moisture during transport.
Pack the device accordingly.
— Pack the device so that it is protected against vibrations
during transport, e.g., by using air-cushioned packaging.
6.3 Storing the device
Bear the following points in mind when storing devices:
— Store the device in its original packaging in a dry and
dust-free location.
— Observe the permitted ambient conditions for transport
and storage.
— Avoid storing the device in direct sunlight.
— In principle, the devices may be stored for an unlimited
period. However, the warranty conditions stipulated in the
order confirmation of the supplier apply.
6.3.1 Ambient conditions
The ambient conditions for the transport and storage of the
device correspond to the ambient conditions for operation of
the device.
Adhere to the device data sheet!
6.4 Returning devices
For the return of devices, follow the instructions in the chapter
"Repair" on page 40.
7Installation
7.1 Installation options
There are three options for installing the transmitter:
— Installation in the cover of the connection head (without
springs)
— Direct installation on the measuring inset (with springs)
— Installation on a top-hat rail
7.1.1 Installation in the cover of the connection head
Fig. 11
1. Release the screw plug 3for the cover of the connection
head
2. Open the
1cover.
3. Secure 2the transmitter 2 at the proper position on the
cover, using the captive screws found in the transmitter.
1
2
3
A10067

TTH300 | OI/TTH300-EN Rev. D 15
7.1.2 Installation on the measuring inset
Fig. 12
NOTICE
Before mounting the transmitter on the measuring inset,
remove the ceramic block on the measuring inset and the
captive screws in the transmitter.
To install the transmitter on the measuring inset, cambered
toothed discs and the corresponding mounting screws are
required; these must be ordered as separate accessories:
Measuring inset installation set (2 fixing screws, 2 springs,
2 toothed discs) order number: 263750
1. Remove the ceramic block from the measuring inset 3.
2. Remove the screws from the 2transmitter. Remove the
sleeves from the screw holes and then remove the
screws.
3. Insert new fixing screws 1from above in the fixing holes
of the transmitter.
4. Place the cambered toothed 4discs with curve facing
upward on the downward protruding screw thread.
5. Connect the power supply cable to the transmitter
according to connection diagram.
6. Place the transmitter in the housing on the measuring
inset and secure it.
NOTICE
The toothed discs between measuring inset and transmitter
are straightened when the screws are tightened. This
enables them to grip the mounting screws.
7.1.3 Installation on the top-hat rail
Fig. 13
When mounted on a top-hat rail, the transmitter can be placed
at a distance from the sensor in a housing that is suitable for
the ambient conditions.
7.2 Installing / removing the optional LCD indicator
Thanks to the LCD indicator interface, the TTH300 can be
operated using the LCD indicator.
The indicator must be removed to enable connection of the
sensor line or supply line:
— Carefully remove the LCD indicator from the transmitter
inset. The LCD indicator is held firmly in place, meaning
that you may have to use the tip of a screwdriver to pry it
loose. Take care to avoid any mechanical damage.
No tools are required to insert the LCD indicator:
1. Carefully insert the guide pins for the LCD indicator in the
guide holes of the transmitter inset. Make sure the black
connection socket fits into the terminal on the transmitter
inset.
2. Then press the LCD indicator in as far as it will go. Make
sure that the guide pins and connection socket are fully
inserted.
The position of the LCD indicator can be adjusted to suit the
mounting position of the transmitter, to ensure that the display
is as clearly legible as possible.
CAUTION
Make sure the flat ribbon cable does not get twisted or torn
when rotating the LCD indicator.
There are twelve positions at increments of 30°.
1. Carefully turn the LCD indicator to the left to release it
from its holder.
2. Carefully turn the LCD indicator until the required position
is reached.
3. Insert the LCD indicator into its holder again and turn it to
the right into the required position until it snaps into place.
A10066
1
2
3
4
A10103

16 OI/TTH300-EN Rev. D | TTH300
7.3 Electrical connections
DANGER
Improper installation and commissioning of the device
carries a risk of explosion.
For use in potentially explosive atmospheres, observe the
information in chapter "Use in potentially explosive
atmospheres according to ATEX and IECEx" on page 6 and
"Use in potentially explosive atmospheres in accordance with
FM and CSA" on page 10!
Observe the following information:
— The electrical connection may only be made by authorized
specialist personnel and in accordance with the electrical
circuit diagrams.
— The relevant regulations must be observed during
electrical installation.
— The electrical connection information in the manual must
be observed; otherwise, the type of electrical protection
may be adversely affected.
— Safe isolation of electrical circuits which are dangerous if
touched is only guaranteed if the connected devices
satisfy the requirements of DIN EN 61140
(VDE 0140 Part 1) (basic requirements for safe isolation).
— To ensure safe isolation, install supply lines so that they
are separate from electrical circuits which are dangerous if
touched, or implement additional isolation measures for
them.
— Connections must only be established in a dead-voltage
state.
— The transmitter has no switch-off elements. Therefore,
overcurrent protective devices, lightning protection, or
voltage disconnection options must be provided at the
plant.
— The power supply and signal are routed in the same line
and must be implemented as a SELV or PELV circuit in
accordance with the relevant standard (standard version).
For the Ex version, the guidelines stipulated by the Ex
standard must to be adhered to.
— You must check that the available supply power
corresponds to the information on the name plate.
NOTE
The signal cable wires must be provided with wire end
sleeves.
The slotted screws of the connection terminals are tightened
with a size 1 screwdriver (3.5 or 4 mm).
7.3.1 Conductor material
NOTE
Damage to components!
The use of rigid conductor material may cause wire breaks.
supply voltage
— Supply voltage cable: flexible standard cable material
— Maximum wire cross-section: 1.5 mm2(AWG 16)
Sensor connection
Depending on the sensor model, a variety of line materials can
be used for sensor connections.
The integrated internal reference junction makes it possible to
directly connect thermal compensating lines.
Change from tw o to one column

TTH300 | OI/TTH300-EN Rev. D 17
7.3.2 Pin configuration
Resistance thermometers (RTD) / resistors (potentiometers)
Fig. 14
APotentiometer, four-wire circuit BPotentiometer, three-wire circuit CPotentiometer, two-wire circuit D2 x RTD, three-wire circuit1)
E2 x RTD, two-year wire1) FRTD, four-wire circuit GRTD, three-wire circuit HRTD, two-wire circuit ISensor 1 JSensor 21)
KLCD-indicator-interface
1– 6sensor connection (from measuring inset) 7– 84 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
Thermocouples / voltages and resistance thermometer (RTD) / thermocouple combinations
Fig. 15
A2 x voltage meter1) B1 x voltage meter C2 x Thermoelement1) D1 x Thermoelement E1 x RTD, four--wire circuit and
1 x Thermoelement1) F1 x RTD, three--wire circuit and 1 x Thermoelement1) G1 x RTD, two--wire circuit and 1 x Thermoelement1)
HSensor 1 ISensor 21) JLCD-indicator-display
1– 6sensor connection (from measuring inset) 7– 84 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
Change from one to two columns
A10003-01
-
+
7
8
4
3
2
1
8
7
4
5
JJ
J
J J
J
J
J
K
3
1
2
5
4
6
I
ABC DE FG H
J
4
4
6
2222
333 3 3 33
3
4
11111111
2
6
A10004-01
-
+
7
8
4
3
2
1
8
7
J
3
1
2
5
4
6
+
-
+
-
+
-
+
-
+
-
+
-
J
J
J
+
-
+
-
2
11 11
5
6
222
5
6
+
-
55 5
4
66 6
22
333
11 1
H
I
AB CD E F G

18 OI/TTH300-EN Rev. D | TTH300
7.3.3 Electrical data for inputs and outputs
Input - resistance thermometer / resistances
Resistance thermometer
— Pt100 according to IEC 60751, JIS C1604, MIL-T-24388
— Ni according to DIN 43760
— Cu according to recommendation OIML R 84
Resistance measurement
— 0 … 500
— 0 … 5000
Sensor connection type
— Two-, Three-, Four wire-circuits
Connection lead
— Maximum sensor line resistance:
of 50 per line in accordance with NE 89
— Three-wire circuit:
Symmetrical sensor line resistances
— Two-wire circuit::
Compensation up to 100 total lead resistance
Measurement current < 300 A
Sensor short circuit < 5 (for resistance thermometers)
Sensor wire break
— Measuring range: 0 ... 500 > 0.6 ... 10 k
— Measuring range 0 ... 5 k > 5.3 ... 10 k
Corrosion detection in accordance with NE 89
— Three-wire resistance measurement > 50
— Four-wire resistance measurement > 50
Sensor error signaling
— Resistance thermometer - Sensor short circuit and sensor
wire breakage
— Linear resistance measurement: Sensor wire break
Input - thermocouples / voltages
Types
— B, E, J, K, N, R, S, T in accordance with IEC 60584
— U, L in accordance with DIN 43710
— C, D in accordance with ASTM E-988
Voltages
— -125 ... 125 mV
— -125 ... 1100 mV
Supply line
— Maximum sensor line resistance
1.5 k per wire, 3 k in total
Sensor wire break monitoring in accordance with NE 89
— Pulsed with 1 µA outside measurement interval
— Thermocouple measurement 5.3 ... 10 k
— Voltage measurement 5.3 ... 10 k
Input resistance > 10 M
Internal reference junction Pt1000, IEC 60751 Cl. B
(no additional jumpers necessary)
Sensor error signaling
— Thermocouple: wire break
— Linear voltage measurement: wire break
Functionality input
Free style characteristic curve / 32-point -sampling point table
— Resistance measurement up to max. 5 k
— Voltages up to max. 1.1 V
Sensor error adjustment
— Via Callendar-Van Dusen coefficients
— Via value table of 32 reference points
— Via single-point adjustment (offset adjustment)
— Via two-point adjustment
Input functionality
— 1 sensor
— 2 sensors:
mean measurement,
differential measurement,
sensor redundancy,
Sensor drift monitoring

TTH300 | OI/TTH300-EN Rev. D 19
HART output
Transmission behavior
— Temperature linear
— Resistance linear
— Voltage linear
Output signal
— Configurable 4 ... 20 mA (standard)
— Configurable 20 ... 4 mA
(Dynamic range: 3.8 ... 20.5 mA in accordance with NE 43)
Simulation mode 3.5 ... 23.6 mA
Induced current consumption < 3.5 mA
Maximum output current 23.6 mA
Configurable error current signal
— Overrange 22 mA (20.0 … 23.6 mA)
— Underrange 3.6 mA (3.5 … 4.0 mA)
PROFIBUS PA output
Output signal
— PROFIBUS – MBP (IEC 61158-2)
— Baud rate 31.25 kbit/s
— PA profile 3.01
— FISCO compliant (IEC 60079-27)
— ID number: 0x3470 [0x9700]
Error current signal
— FDE (Fault Disconnection Electronic)
Block structure
— Physical Block
— Transducer Block 1 – temperature
— Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
— Analog Input 1 – Primary Value (Calculated Value1))
— Analog Input 2 – SECONDARY VALUE_1 (sensor 1)
— Analog Input 3 – SECONDARY VALUE_2 (sensor 2)
— Analog Input 4 – SECONDARY VALUE_3 (reference
junction temperature)
— Analog Output – optional HMI display (Transducer Block 2)
— Discrete Input 1 – enhanced diagnosis 1 (Transducer Block 3)
— Discrete Input 2 – enhanced diagnosis 2 (Transducer Block 3)
1) Sensor 1, sensor 2 or difference or mean
FOUNDATION Fieldbus output
Output signal
— FOUNDATION Fieldbus H1 (IEC 611582-2)
— Baud rate 31.25 kbit/s, ITK 5.x
— FISCO compliant (IEC 60079-27)
— Device ID: 000320001F...
Error current signal
— FDE (Fault Disconnection Electronic)
Block structure1)
— Resource Block
— Transducer Block 1 – temperature
— Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
— Analog Input 1 – PRIMARY_VALUE_1 (sensor 1)
— Analog Input 2 – PRIMARY_VALUE_2 (sensor 2)
— Analog Input 3 – PRIMARY_VALUE_3 (calculated value2))
— Analog Input 4 – SECONDARY_VALUE (reference junction
temp.)
— Analog Output – optional HMI display
(Transducer Block 2)
— Discrete Input 1 – enhanced diagnosis 1
(Transducer Block 3)
— Discrete Input 2 – enhanced diagnosis 2
(Transducer Block 3)
— PID – PID controller
LAS (Link Active Scheduler) link master functionality
1) For the block description, block index, execution times, and block class, refer
to the interface description
2) Sensor 1, sensor 2 or difference or mean

20 OI/TTH300-EN Rev. D | TTH300
7.4 Power supply
Two-wire technology, polarity safe; power supply lines = signal
lines
NOTICE
Following calculations apply for standard applications. This
should be taken into consideration when working with the
higher maximum current.
7.4.1 Power supply - HART
Input terminal voltage
— Non-Ex application:
U
S= 11 ... 42 V DC
— Ex applications:
U
S= 11 ... 30 V DC
Max. permissible residual ripple for input terminal voltage
— During communication in accordance with HART FSK
"Physical Layer" specification.
Undervoltage detection on the transmitter
— If the terminal voltage on the transmitter falls below a
value of 10 V, this may lead to an output current of Ia≤
3.6 mA.
Maximum load
— RB= (supply voltage – 11 V) / 0.022 A
Fig. 16: Maximum load depending on input terminal voltage
ATTH300 BTTH300 In ia hazardous area design CHART
communication resistance
Maximum power consumption
— P = Usx 0.022 A
— e. g. Us= 24 V Pmax = 0.528 W
Voltage drop on the signal line
When connecting the devices, note the voltage drop on the
signal line. The minimum supply voltage on the transmitter
must not be undershot.
Fig. 17
ATransmitter BSupply isolator / PCS input with supply /
Segment coupler
U1min: Minimum supply voltage on the transmitter
U2min: Minimum supply voltage of the supply isolator /
DCS input
R: Line resistance between transmitter and supply
isolator
R250: Resistance (250 ) for HART functionality
Standard application with 4 ... 20 mA functionality
When connecting these components, observe the following
condition:
U1min ≤ U2min - 22 mA x R
Standard application with HART functionality
By adding the resistance R250 , the minimum input terminal
voltage U2min: U1min ≤ U2min - 22 mA x (R + R250) can be
increased.
For HART functionality, use supply isolators or DCS input
cards with a HART mark. If this is not possible, a resistance of
≥ 250 (< 1100 Ω) must be added to the interconnection.
The signal line can be operated with or without earthing. When
establishing a ground connection (minus side), make sure that
only one side of the terminal is connected to the equipotential
bonding.
Unless the profile HART protocol Rev. 7 is exclusively selected
during the ordering process, the device normally supports the
profile HART HART protocol Rev. 5 in the delivery
status. Subsequently user can change over to the profile
HART HART protocol Rev. 7 over a miniature switch. See
chapter for more details "Hardware settings" on page 22.
A11122
AB
+
-
U
1
+
U
2
-
R
R
250
Other manuals for TTH300 Series
6
This manual suits for next models
3
Table of contents
Other ABB Transmitter manuals