ABB KSONIK MICRO Administrator Guide

KSONIK MICRO
Ultrasonic Level Transmitter
Operation instruction manual OI/KMICRO-EN Rev. B
Ultrasonic level measurement
with GAP technology
K-TEK Products
Introduction
This operation instruction manual provides the following
information:
–Quick start instructions for distance, level and flow - see
page 3
–Installation procedures - see page 6
–Instructions on how to change parameters - see page 8
–Configuration guidelines for distance/level - see page 9

2KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
Table Of Contents
1.0 Introduction.............................................................................................................................................................3
2.0 Quick Start for Distance..........................................................................................................................................3
3.0 Quick Start for Level...............................................................................................................................................4
4.0 Quick Start for Flow................................................................................................................................................4
5.0 Changing Parameters.............................................................................................................................................5
6.0 Installation ..............................................................................................................................................................6
7.0 Key Descriptions.....................................................................................................................................................8
7.1 Security Code.................................................................................................................................................8
8.0 Conguration Distance / Level................................................................................................................................9
8.1 Distance / Level Mode..................................................................................................................................10
8.2 Conguration Flow........................................................................................................................................14
8.3 Flow Mode....................................................................................................................................................15
9.0 Working with Key Pad in Run Mode.....................................................................................................................19
10.0 Run Mode Screen in Distance / Level Mode ........................................................................................................19
11.0 Onscreen KSCOPE ..............................................................................................................................................20
12.0 Examples..............................................................................................................................................................21
12.1 Distance Measurement...............................................................................................................................21
12.2 Level Measurement....................................................................................................................................21
12.3 Level Measurement and Engineering Units................................................................................................22
12.4 Level Measurement Using the Lineariser Function ....................................................................................22
12.5 Level Measurement Using the Lineariser Function with Non-Linear Vessel ..............................................23
12.6 Venturi Flume .............................................................................................................................................24
12.7 V-Notch.......................................................................................................................................................24
12.8 Working with the Simulator.........................................................................................................................25
13.0 Fault Finding.........................................................................................................................................................26
14.0 Terminal Connections ...........................................................................................................................................27
15.0 RMA Form ............................................................................................................................................................28
16.0 Declaration of Conformity.....................................................................................................................................29
17.0 Warranty ...............................................................................................................................................................30

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 3
The KSONIK MICRO works on the non-contact principle of ultrasonics.
A pulse of energy emits from the Transducer at the speed of sound and
is detected on its return. The Transmitter can distinguish the difference
between the correct echo and other ambient noise. When the signal
returns, the KSONIK MICRO measures the time period, and then
knowing the speed of sound, it can accurately calculate the distance
from the material to the Transducer. The KSONIK MICRO will adjust the
4-20mA output, accordingly.
In distance mode, the KSONIK MICRO measures distance from the
transducer. This means the 20mA will be the furthest point and the 4mA
will be the closest point.
In level mode, the KSONIK MICRO measures level in a tank. This
means at the furthest point or when the tank is empty, the instrument
will read 4mA. At the closest point the tank will be full and the instrument
will read 20mA.
The Open Channel ow meter uses a level measurement from the
KSONIK MICRO and converts the reading into a ow measurement.
A microprocessor then controls the output functions of the relay, display
and the analogue output signals.
KSONIK MICRO
Ultrasonic Level Transmitter and Switch
2.0 Quick Start for Distance
KSONIK MICRO was designed to be user friendly with a very simple conguration program. This allows the technician to set
up KSONIK MICRO without the aid of a complicated source-code book. There are no references to any codes in KSONIK
MICRO. The set up procedure is all menu-driven with the aid of questions and multiple-choice answers.
Aim the transducer at a wall about 2 m away and check the display. It should read the following:
If the reading is above 2.000 m then move the instrument closer to the wall.
If the reading is below 2.000 m then move the instrument away from the wall.
You may now proceed and check other parameters.
1.0 Introduction
Dist. 2.000 m
mA Output: 7.20 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 20.00%

4KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
3.0 Quick Start for Level
1. Connect up the power to the instrument described on the KSONIK MICRO face label or in the KSONIK MICRO
manual under terminal connections on page 51.
2. Press
3. Use to get to the default security Code 5159 and then press
4. Use to select level and then press
5. Press
Aim the transducer at a wall about 2.000 m away and check the display. It should read the following:
If the Level reading is below 8.000 m then move the instrument closer to the wall. If the Level reading is above 8.000 m
then move the instrument away from the wall. You may now proceed and check other parameters
4.0 Quick Start For Flow
1. Connect up the power to the instrument as described on the KSONIK MICRO face or in the KSONIK MICRO
manual under terminal connections on page 51.
2. Press
3. Use to get to the default security Code 5159 and then press
4. Use to select level and then press
5. Press
Aim the transducer at a wall about 1.5 m away and check the display. It should read the following:
If the head reading is below 0.500 m or below 64.86 Lt/s then move the transducer closer to the wall. If the head reading
is above 0.500 m or above 64.86 Lt/s then move the transducer away from the wall. You may now proceed and check
other parameters.
SCROLL
▼
▼
ENTER ENTER
ENTER
RUN
▼
▼
Level 8.000 m
mA Output: 17.47 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 84.21%
Flow: 64.86 Lt/S
T: 00001513408 Lt
Head: 0.500
mA Output: 5.03 mA
Instant: 1.502 m
Temperature: 20°C
Percentage: 6.48%
SCROLL
▼
▼
ENTER ENTER
ENTER
RUN
▼
▼

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 5
5.0 Changing Parameters
Step 1
Simply press The SECURITY CODE prompt should be displayed.
Step 2
Enter the code 5159 by pressing the keys
Step 3
To conrm security code press
Dist. 2.000 m
mA Output: 7.20 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 20.00%
SCROLL
Scroll Up Down Enter Run
▼
▼
Scroll Up Down Enter Run
Scroll Up Down Enter Run
Enter the Code:
5000
Enter the Code:
5159
ENTER

6KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
If Code has been accepted, the screen will display
If Code has not been accepted, the screen will display
If the security code has been changed and forgotten then contact the nearest K-TEK agent for override code.
To carry on with programming go to page 16.
6.0 INSTALLATION
The KSONIK MICRO is protected to IP65. The Transmitter is dust and waterproof so it can be mounted outside. The
KSONIK MICRO should be mounted using the bracket supplied. Do not install the KSONIK MICRO in areas of high vibration
as this may cause failure. Do not install the KSONIK MICRO in the close vicinity of electrical cable, SCR’s or variable speed
drives. The installation of KSONIK MICRO is the most important section of this manual and has been divided up into 6 sub
sections.
1. The KSONIK MICRO must be tted at least 0.50 m / 1.64 ft above the highest point of level.
2. Always use the plastic nut. The KSONIK MICRO must be tted to a rigid support. Use mild steel or a suitable plastic.
Do not use stainless steel as this can cause ringing.
Mode
Dist. Level Flow
Units: Meters
Empty Dist.: 10.000 m
Span: 10.000 m
Blanking: 0.500 m
Rate: 1.0 m/min
Application: Liquids
2
Dist. 2.000 m
mA Output: 7.20 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 20.00%
Steel bracket with
4 screws for mounting
Wall

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 7
3. The KSONIK MICRO must be perpendicular to the material it is measuring with a clear line of sight and must not be
above beams or lling points.
4. The transducer should be perpendicular to liquid level.
5. If the KSONIK MICRO is in a coned vessel, it must be positioned over the cone. This ensures that the Transducer
receives the true echo and not one from the sides of the cone.
INCORRECT CORRECT
THIS IS INCORRECT AS THE
FILLING POINT IS OBSCURING
THE KMICRO’S LINE OF SIGHT
THIS IS CORRECT AS THE FILL-
ING POINT IS NOT OBSCURING
THE KMICRO’S LINE OF SIGHT
INCORRECT CORRECT

8KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
SCROLL
▼
ENTER
RUN
▼
6. When a standpipe is being used it must be as wide as possible; i.e. the pipe diameter must be at least half its
height, preferably made of plastic. The base MUST have a 45° chamfer to reduce the echo size from the bottom of the
standpipe. No welding should be present on the inside of the pipe as this causes false echoes.
7. If any large electrical equipment is installed in the vicinity, then earthed steel conduit must be used.
7.0 KEY DESCRIPTION
KSONIK MICRO is “user friendly” having only 5 keys and a menu driven display. The keys are listed below with their
appropriate functions.
This is used to initially access the programming and then to run through the various menus.
This key is used to INCREASE the value in the various commands. This key also starts the simulation
mode increasing in level. See page 48 for details.
This key is used to INCREASE the value in the various commands. This key also starts the simulation
mode decreasing in level. See page 48 for details.
When a value has been changed it is only accepted by pressing the ENTER key. The ENTER key while
in run mode scrolls through the relay status screen and onscreen KScope screen.
See page 32 for details.
When programming is complete, press RUN to return KSONIK MICRO back to the run mode.
7.1 Security Code
To advance to the programming mode the correct security code must be entered. The factory default code is 5159. This
code can be changed in the programming mode. If you forget the security code please contact your local ABB agent for
the override code.

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 9
8.0 CongurationDistance/Level
FLOW MODE
BASIC OPTIONS DEFAULTS
SECURITY CODE 0-9999 5159
MODE DISTANCE/LEVEL/FLOW DISTANCE
UNITS METERS/FEET METERS
EMPTY DISTANCE 0.4-15.00 m 10 m
SPAN 0.1-15.00 m 10 m
BLANKING 0.3-14.90 m 0.50 m
RATE OF CHANGE 0.01-20.0 m/min 1.00 m/min
APPLICATION LIQUIDS/SOLIDS LIQUIDS
FACTORY RESET NO/YES NO
TEMPERATURE COMPENSATION OFF/ON OFF
SIMULATE NO/YES NO
SET PASSWORD NO/YES NO
BACKLIGHT OFF/ON (1-60MIN) / PERM 2 MIN
LOSSTIME 30-900SEC 300SEC
LOGTIME 3.6mA, 4.0mA, 20mA, 21mA, HOLD HOLD
FAILSAFE 3.6mA, 4.0mA, 20mA, 21mA, Hold Hold
FAILSAFE
ENGINEERING UNITS NONE, aaa-zzz, AAA-ZZZ,0-9 NONE
MAXIMUM VALUE 0-99999 10000
DECIMAL POINT 0-3 2
ZERO OFF SET -50 mm TO 50 mm 0
SETUP RELAY NO/YES NO
RELAY OFF/LO/HI OFF
SETPOINT SPAN 0 m
RESET POINT SPAN 0 m
PUMP CYCLE OFF/FIFO/ROTATE OFF
CLEAR RELAY NO/YES NO
SETUP LINEARISER NO/YES NO
ACTIVATE LINEARISER NO/YES NO
SETPOINT 1-21 1
HEIGHT 0m-SPAN 0 m
PERCENTAGE 0-100% 0%

10 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
8.1 Distance/LevelMode
SECURITY CODE
Security code to advance to programming.
DEFAULT 5159
MODE
Choose between Distance, Level.
DEFAULT Distance
UNITS
Choose between Feet and Meters.
DEFAULT Meters
EMPTY DISTANCE
This is the distance from the face of the transducer to the bottom of the tank.
DEFAULT 10.00 m
SPAN
This gure is the measuring range of the instrument i.e. distance from the bottom of the tank to the highest point being
measured. Remember, the material must not approach within 0.50 meters of the transducer face or within the blanking
distance of the transducer.
DEFAULT 10.00 m
BLANKING
This is the area where an echo cannot be processed because the return echo would be received while the transducer
is still ring.
DEFAULT 0.50 m
RATE OF CHANGE
This is used to set up the rate of change of the level output. The rate of change governs the rate at which the instrument
output change. By increasing the rate of change (4.00 m/min) it will allow the KSONIK MICRO to monitor rapid changes
in level. If the level moves faster than 1 m/minute in measurement increase the rate of change. If a more stable output is
required decrease the rate of change (0.30 m/min).
DEFAULT 1.00 m/min
APPLICATION
This selection can be used to select either liquid or solid applications. The solid application will provide more power to
locate the correct echo.
DEFAULT Liquids
FACTORY RESET
This prompt will reset all values entered back to factory setting except the password. Please write down all settings be-
fore using this function.
DEFAULT No
TEMPERATURE COMPENSATION
Sets temperature compensation on or off.
DEFAULT Off
SIMULATE
Simulates the level, relay outputs and mA outputs with the rate of change, selected.
DEFAULT No
SET PASSWORD

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 11
This prompt will allow you to change the default factory code. Should the factory code be forgotten please contact a local
ABB agent for an override password.
DEFAULT No
BACKLIGHT
Choose between switching on the backlight for 1 - 60 minutes, switch off the backlight or to switch the backlight perma-
nently on.
DEFAULT 2 Min
LOSSTIME
This is the amount of time between last receiving a correct echo and going into the Fail-safe condition. This time period
is timed in seconds. This cannot be reduced to less than 30 seconds.
DEFAULT 300 Sec
FAILSAFE
If a loss of echo condition is reached then the 4-20mA output will follow the congured settings 3.60mA, 4mA, 20mA,
21mA or Hold the reading at the last recognized echo. This is usually due to a cable being cut or the instrument not being
set up correctly.
DEFAULT Hold
ENGINEERING UNITS
This prompt will allow you to display in your own engineering units and can be made up from alphanumeric characters.
DEFAULT None
MAXIMUM VALUE/DECIMAL POINT
This is the maximum value the engineering units can be displayed instead of reading meters (m) or feet (ft).
DEFAULT 10000
After the maximum value is set the number of decimal points can be adjusted.
DEFAULT 2
ZERO OFFSET
Choose between –50 mm to 50 mm for setting the offset of the instrument.
DEFAULT 0
SETUP RELAY
Select yes to enter the relay menu and set up the relay parameters.
DEFAULT No
RELAY
The relay can be used either for a high alarm or a low alarm. A high alarm has its reset below the set point, and a low
alarm has its reset above the set point. DEFAULT Off
SET POINT
This is the value where the relay will set.
DEFAULT 0 m
RESET POINT
This is the value where the relay will reset.
DEFAULT 0 m
PUMP CYCLE
Not applicable on this instrument
CLEAR RELAY
Clears the number of cycles as well as the run hours recorded.
DEFAULT No
SETUP LINEARISER
This prompt will allow you to input a curve to linearise the vessel. The span is divided by 21 and you can input the new

12 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
height for each point as well as the corresponding percentage ll at that point. KSONIK MICRO prompts you at each
point.
DEFAULT No
ACTIVATE LINEARISER
This function activates the lineariser.
DEFAULT No
SET POINT
This is the number at which point the user is inputting a linearised point.
HEIGHT/PERCENTAGE
Height is the distance from the bottom of the tank to a corresponding point where a suitable percentage can be deter-
mined.
DEFAULT 0.00 m
Enter the percentage volume of vessel at a corresponding height.
DEFAULT 0.00 %

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 13
Set point 1
Height 0.0 m
Percentage 0.00%
Set point 7
Height 3.00 m
Percentage 30.00%
Set point 5
Height 2.00 m
Percentage 20.00%
Set point 11
Height 5.00 m
Percentage 50.00
Set point 6
Height 2.50 m
Percentage 25.00%
Set point 12
Height 5.00 m
Percentage 50.00%
Set point 2
Height 0.50 m
Percentage 5.00%
Set point 8
Height 3.50 m
Percentage 35.00%
Set point 3
Height 1.00 m
Percentage 10.00%
Set point 9
Height 4.00 m
Percentage 40.00%
Set point 4
Height 1.50 m
Percentage 15.00%
Set point 10
Height 4.50 m
Percentage 45.00%
Set point 13
Height 5.50 m
Percentage 55.00%
Set point 17
Height 8.00 m
Percentage 80.00%
Set point 20
Height 9.50 m
Percentage 95.00%
Set point 21
Height 10.00 m
Percentage 100.00%
Set point 14
Height 6.00 m
Percentage 60.00%
Set point 15
Height 7.00m
Percentage 70.00%
Set point 18
Height 8.50 m
Percentage 85.00%
Set point 16
Height 7.50 m
Percentage 75.00%
Set point 19
Height 9.00 m
Percentage 90.00%

14 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
FLOW MODE
BASIC OPTIONS DEFAULTS
SECURITY CODE 0-9999 5159
MODE DISTANCE/LEVEL/FLOW DISTANCE
UNITS METERS/FEET METERS
EMPTY DISTANCE 0.4-15.0 m 2 m
SPAN 0.1-15.0 m 1.5 m
BLANKING 0.3-14.90 m 0.50 m
RATE OF CHANGE 0.01-20.0 m/min 0.50 m/min
APPLICATION LIQUIDS/SOLIDS LIQUIDS
FACTORY RESET NO/YES NO
TEMPERATURE COMPENSATION ON/OFF OFF
SIMULATE NO/YES NO
SET PASSWORD NO/YES NO
BACKLIGHT OFF/ON (1-60MIN)/PERM 2MIN
LOSSTIME 30-900SEC 300SEC
FAILSAFE 3.6mA, 4.0mA, 20mA, 21mA, Hold Hold
FAILSAFE
FLOW UNITS SEE LIST LT/SEC
MAXIMUM VALUE 1-99999 1000
ZERO OFF SET -50 mm TO 50 mm 0 mm
TOTALISER COUNT 1-1000000 1
TOTALISER UNITS A-Z, a-z, 0-9 Lt
TOTALISER RESET NO/YES NO
FLOW CURVE SEE LIST V-NOTCH
SETUP RELAY NO/YES NO
RELAY OFF/LO/HI/COUNTER OFF
SETPOINT SPAN 0 m
RESET POINT SPAN 0 m
PUMP CYCLE OFF/FIFO/ROTATE NO
COUNT VALUE 1-1000000 1000
CLEAR RELAY NO/YES NO
SETUP LINEARISER NO/YES NO
ACTIVATE LINEARISER NO/YES YES
SETPOINT 1-21 1
HEIGHT 0m-SPAN 0 m
PERCENTAGE 0-100% 0%
8.2 CONFIGURATION FLOW

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 15
8.3 FLOW MODE
SECURITY CODE
Security code to advance to programming.
DEFAULT 5159
MODE
Choose Flow.
DEFAULT Distance
UNITS
Choose between Feet and Meters.
DEFAULT Meters
EMPTY DISTANCE
This is the distance from the face of the transducer to the bottom of the ume.
DEFAULT 2 m
SPAN
This gure is measuring the range of the instrument i.e. distance from the bottom of the ume to the highest point being
measured.
Remember, the material must not approach within 0.5 meters of the transducer face or within the blanking distance of
the transducer.
DEFAULT 1.5 m
BLANKING
This is the area where an echo cannot be processed because the return echo would be received while the transducer
is still ring.
DEFAULT 0.5 m
RATE OF CHANGE
This is used to set up the rate of change of the level output. The rate of change governs the rate at which the instrument
outputs changes. By increasing the rate of change (4.0 m/min) it will allow the KSONIK MICRO to monitor rapid changes
in ow. If the level moves faster than 0.5 m/min then increase the rate of change. If a more stable output is required de-
crease the rate of change (0.3 m/min).
DEFAULT 0.5 m/min
APPLICATION
This selection can be used to select either liquid or solid applications. The solid application will provide more power to
locate the correct echo..
DEFAULT Liquids
FACTORY RESET
This prompt will reset all values entered back to factory setting except the password. Please write down all settings be-
fore using this function.
DEFAULT No
TEMPERATURE COMPENSATION
Sets temperature compensation on or off.
DEFAULT Off
SIMULATE
Simulates the head, Relay output and mA output at the rate of change selected.
DEFAULT No
SET PASSWORD
This prompt will allow you to change the default factory code. Should the factory code be forgotten please contact a local
ABB agent for an override password.
DEFAULT No

16 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
BACKLIGHT
Choose between switching on the backlight for 1-60 minutes, switch off the backlight or to switch the backlight perma-
nently on.
DEFAULT 2 Min
LOSSTIME
This is the time, in seconds, between last receiving a correct echo and going into the Fail-safe condition. Minimum 30
seconds.
DEFAULT 300 Sec
FAILSAFE
If the loss of echo condition is reached then the 4-20mA output will follow the congured settings 3.6mA, 4mA, 20mA,
21mA or Hold the reading at the last recognized echo. This is usually due to a cable being cut.
DEFAULT Hold
FLOW UNITS
Units can be set via the alphanumeric display to the desired value.
DEFAULT LT/SEC
MAXIMUM VALUE
This is the maximum ow rate of the ume.
DEFAULT 1000
ZERO OFFSET
Choose between –50 mm to 50 mm for small errors on the instrument.
DEFAULT 0
TOTALISER COUNT
Choose a value where the counter will increment for a certain unit of ow between 1-1000000 when in Flow mode.
DEFAULT 1
TOTALISER UNITS
Indication of units the totaliser is set up for.
DEFAULT Lt
TOTALISER RESET
Reset the totaliser counter when in Flow mode.
DEFAULT No
FLOW CURVE
The ow element can be selected. Select from the list below:
V-notch (5/2)
Venturi (3/2)
Parshall ume 1- 96 inch
Rectangular weir (3/2)
Own curve (21 point lineariser)
DEFAULT V-Notch
SETUP RELAY
This prompt will allow a user to enter the menu to set up the relay parameters. DEFAULT No

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 17
RELAY
The relay can be used either for a high alarm, a low alarm or counter in ow mode. The difference is that a high alarm
has its reset below the set point, and a low alarm has its reset above the set point. The counter will output a pulse every
time a certain value is reached from the totaliser, which increments by more than a user dened value when in ow mode.
DEFAULT Off
SET POINT
This is the distance value whereby the relay will set.
DEFAULT 0 m
RESET POINT
This is the distance value whereby the relay will reset.
DEFAULT 0 m
PUMP CYCLE
Not applicable on this instrument
COUNT VALUE
Choose a value where the relay will pulse between 1-1000000 when in Flow mode.
DEFAULT 1000
CLEAR RELAY
Clears the number of cycles as well as the run hours recorded.
DEFAULT No
SETUP LINEARISER
This prompt will allow you to input a curve to linearise the ume. The span is divided by 21 and you can input the new
height for each point as well as the corresponding percentage ll at that point. KSONIK MICRO prompts you at each
point.
DEFAULT No
ACTIVATE
This function activates the lineariser.
DEFAULT Yes
SET POINT
This is the number at which point the user is inputting a linearised point.
HEIGHT/PERCENTAGE
Height is the distance of the ume from the bottom to a point where a suitable percentage volume can be determined.
DEFAULT 0.00 m
Enter the percentage volume of ume at a corresponding distance away from the bottom of the vessel or ume.
DEFAULT 0.00%

18 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
Set point 1
Height 0.0 m
Percentage 0.00%
Set point 12
Height 0.825 m
Percentage 40.79%
Set point 5
Height 0.300 m
Percentage 8.94%
Set point 16
Height 1.125 m
Percentage 64.95%
Set point 6
Height 0.375 m
Percentage 12.50%
Set point 17
Height 1.200 m
Percentage 71.55%
Set point 2
Height 0.075 m
Percentage 1.12%
Set point 13
Height 0.900 m
Percentage 46.48%
Set point 3
Height 0.150 m
Percentage 3.16%
Set point 14
Height 0.975 m
Percentage 52.40%
Set point 4
Height 0.225 m
Percentage 5.80%
Set point 15
Height 1.050 m
Percentage 58.57%
Set point 7
Height 0.450 m
Percentage 16.43%
Set point 19
Height 1.350 m
Percentage 85.38%
Set point 11
Height 0.750 m
Percentage 35.36%
Set point 18
Height 1.275 m
Percentage 78.37%
Set point 8
Height 0.525 m
Percentage 20.71%
Set point 20
Height 1.425 m
Percentage 92.59%
Set point 9
Height 0.600 m
Percentage 25.30%
Set point 21
Height 1.500 m
Percentage 100.00%
Set point 10
Height 0.675 m
Percentage 30.19%

Operation instruction manual |KSONIK MICRO Ultrasonic Level Transmitter 19
9.0 Working with the Key Pad in Run Mode
In run mode the key has an alternative function. While in run mode
the screen looks similar to the following:
Press once. The screen changes to the status screen of the relays.
Press again and the screen goes to the onscreen KSCOPE.
Note: The screen reverts back to normal run mode within 2 minutes.
Pressing again while in the onscreen KScope screen will revert the
screen into normal run mode.
10.0 RunModeScreeninDistance/LevelMode
ENTER
ENTER
ENTER
ENTER
Dist. 2.000 m
mA Output: 7.20 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 20.00%
Relay State Hour Cycles
REL 1: OFF LO 0 2
Em
2v E 0.4
D 13.1
G 99
P 15
15.0
1. The graphical representation of the percentage ll of the application.
2. The instantaneous distance that the instrument is measuring at that specic time. Please note that this value can
change on each pulse.
3. The temperature, which is being measured at the transducer, if temperature compensation has been enabled.
4. The value of percentage ll of the instrument.
5. The mA output of the instrument.
6. The average Distance/Level value which is calculated.
Dist. 2.000 m
mA Output: 7.20 mA
Instant: 2.000 m
Temperature: 20°C
Percentage: 20.00%

20 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
THE RELAY STATE SCREEN
Press while in run mode to get the RELAY STATE SCREEN.
1. Relay state headings.
2. The number of cycles the relay has been through.
3. The number of hours the relay has been on.
4. The state at which the relay is at ON, OFF, HI, LO and CO-Counter.
5. The relay indication number.
11.0 Onscreen KScope
Press twice while in run mode in order to get to the onscreen KScope.
ENTER
Relay State Hour Cycles
REL 1: Off LO 0 2
1. Description of column
5. Relay number
5. Relay state 3. Hours relay has been on
2. Number of cycles
ENTER
1. The maximum returned echo size in volts e.g. 0.4V
2. Displayed instant distance from transducer to substance or object being measured. e.g.13.1 m
3. The Gain needed to get the particular returned echo signal to give a particular measurement. e.g. 50%
4. The amount of power needed to obtain an echo. e.g. 15% power
5. Maximum distance or span. e.g. 15.0 m
6. Graphical representation of the echo received by the transducer.
7. Threshold line whereby any echoes below this line will not be accepted.
8. Indication of good echo, noise, or loss of echo. e.g. E for good echo, N for noise or O for loss of echo.
9. The maximum voltage scale of the Onscreen KScope.
10. The echo loss timer started when no signal is present.
Table of contents
Other ABB Transmitter manuals

ABB
ABB 266 HART Series User manual

ABB
ABB AquaMaster4 User manual

ABB
ABB TTF300 User manual

ABB
ABB TB82PH User manual

ABB
ABB 4600 Series User manual

ABB
ABB AWT420 User manual

ABB
ABB TTH300 Series Installation instructions

ABB
ABB TTF350 Training manual

ABB
ABB 266 HART Series User manual

ABB
ABB AquaMaster 3 FET200 User manual
Popular Transmitter manuals by other brands

Temco
Temco MAGIC II Installation and Calibration

Amphony
Amphony T800 User and installation guide

Trilithic
Trilithic Seeker HL Operation manual

King gates
King gates Myo quick start guide

PR electronics
PR electronics 5343 manual

BECKER-Antriebe
BECKER-Antriebe Centronic PLUS EC548 PLUS Assembly and operating instructions