14
E. EXHAUST REQUIREMENTS
1. GeneralExhaustDuctWorkInformation
Exhaust duct work should be designed and installed by a qualified professional. Improperly
sized duct work will create excessive back pressure which results in slow drying, increased use
of energy, overheating of the dryer, and shutdown of the burner by the airflow (sail) switches,
burnerhi-limits,orbasket(tumbler)hi-heatthermostats.
CAUTION: DRYERMUSTBEEXHAUSTEDTOTHEOUTDOORS.
CAUTION:IMPROPERLYSIZEDORINSTALLEDEXHAUSTDUCTWORKCAN
CREATEAPOTENTIALFIREHAZARD.
The duct work should be laid out in such a way that the duct work travels as directly as
possible to the outdoors with as few turns as possible. Single or independent dryer venting is
recommended.
HorizontalVenting:
Whensingledryerventingisused,thelengthofductwork,fromthedryertotheoutsideexhaustoutlet,
shouldnotexceedfifteen(15)feet.Theminimumdiameterofthisductworkmustbeatleast10-inches(even
thoughthedryerexhaustductforgasandelectricunitsisonly8-inches).Inthecaseofmultiple(common)dryer
venting,thedistancefromthelastdryertotheoutsideexhaustoutletshouldnotexceedfifteen(15)feet.The
shapeoftheductworkisnotcriticalsolongastheminimumcross-sectionalareaisprovided. Itissuggestedthat
theuseof90°turnsbeavoided;use30°and/or45°anglesinstead.Theradiusoftheelbowsshouldpreferably
be1-1/2timesthediameteroftheduct. Includingbasket(tumbler)/dryerelbowconnectionsorelbowsusedfor
outsideprotectionfromtheweather,nomorethan two (2) elbowsshouldbeusedintheexhaustductrun. If
morethantwo (2)elbowsare used,thecross sectionalareaof the ductworkmust beincreased. ALLduct
workshouldbesmoothinsidewithnoprojectionsfromsheet metal screws or otherobstructionswhichwill
collectlint. Whenaddingducts,theducttobeaddedshouldoverlaptheducttowhichitistobeconnected. ALL
ductworkjointsmustbetapedtopreventmoistureandlintfromescapingintothebuilding. Inspectiondoors
shouldbeinstalledatstrategicpointsintheexhaustductworkforperiodicinspectionandclean-outoflintfrom
theductwork.
VerticalVenting:
When single dryer venting is used the length of the duct work from the dryer to the outside
exhaustoutletshouldnotexceedtwenty(20)feet.Theminimumdiameterofthisductworkmustbeatleast
12-inches(eventhoughthedryerexhaustductforgasandelectricunitsisonly8-inches)Inthecaseofmultiple
(common)dryerventing,thedistancefromthelastdryertotheoutsideexhaustoutletshouldnotexceedtwenty
(20)feet.Theshapeoftheductworkisnotsocriticalsolongastheminimumcrosssectionalareaisprovided.It
issuggestedthattheuseof90º turnsbeavoided; use 30ºand/or45ºbendsinstead..Theradiusoftheelbows
shouldpreferablybe1-1/2timesthediameteroftheduct. ALLductwork shouldbesmoothinsidewithno
projectionsfromsheetmetalscrewsorotherobstructionswhichwillcollectlint. Whenaddingducts,theductto
beaddedshouldoverlaptheducttowhichitistobeconnected. ALLductworkjointsmustbetapedtoprevent
moistureandlintfromescapingintothebuilding. Inspectiondoorsshouldbeinstalledatstrategicpointsinthe
exhaustductworkforperiodicinspectionandclean-outoflintfromtheductwork.
IMPORTANT: Exhaustbackpressuremeasuredbyamanometerintheexhaustduct
shouldnotexceed0.3-inchesofwatercolumn.
IMPORTANT: Minimumductworkdiameterforhorizontalventingis10-inchesandfor
verticalventingtheminimumis12-inches..